User’s Manual- Installation and Operation 

 

Characteristics 

 

Controls the collector pump and the auxiliary heating source. 

 

Measures and displays store and collector temperature from 0°C to +150°C. 

 

It has double thunder protection and galvanic insulation. 

 

Can perform delayed relay activation for improved protection. 

 

Anti-freeze protection. 

 

Use 

 

Solar thermal systems with forced circulation. 

 

For domestic hot water recirculation 

 

For auxiliary heating source (liquid or gas burners) utilization in thermosyphonic solar systems. 

 

Safety Instructions 

This device has been designed according to all up to date specifications and fulfills the necessary regulations in order to 

be safely operable for many years. During the design and construction phase has been taken into account every existing 

directive for such kind of equipment. You are kindly advised prior to installation and operation to consult this guide. Be 

sure you realize every consequence of your action and take all necessary precautions. If you don’t understand 

something do not hesitate to contact the manufacturer directly and take the advice of our technical personnel. 

 

Installation must be carried out from experienced authorized electrician. 

 

Do not open the plastic enclosure for any reason. Such action has danger of electric shock and nullifies the warranty. 

 

This device can be used as control device but never as safety device of an installation. 

 

Do not use the device for any other purpose except of those that has been designed for i.e. solar systems control. 

 

Do not use the device for life critical applications. 

 

This device is not water resistant. Install it in an indoor place away from rain, humidity and extreme weather conditions. 

 

This device is not a measuring instrument. 

 

Do not exceed the maximum limitations as referred below for any reason. 

 

During it’s operation the device keeps record for various operating information. The manufacturer maintains the right of 

using such information if for any reason the device will be returned to the factory. 

 

Installation 

The device can be installed in “

” shaped type of rail or directly to the wall. Select carefully the place for installation in 

order to avoid moisture. Reserve enough space for cables to pass through. A gap of 5 mm is recommended around the 

device for better ventilation. During the installation interrupt mains supply. Choose cables of suitable cross-section and 

insulation according to the applied current and voltage. The device is equipped with appropriate cable terminal clamps 

for easy and safe connection. Do not over tighten the screws. Study carefully the electrical connection diagram of 

Figures 1 and 2. 

 

ATTENTION! Terminals (7,8) and (9,10) constitute the “dry” contacts of the pump and the burner relay respectively. If 

you need to drive a mains operated pump or burner you have first to make the necessary connection between No 8, No  

10 and No12 terminals. 

 

The S1 temperature sensor must be of KS30-1K0 type while the S2 and S3 of RS301K5 type.  Insert the probes into 

correct diameter sockets for better temperature reading response and improved accuracy. Place the probes according 

to the Figure 1. The maximum distance between probe and device must not exceed 30m. The connection must be done 

with conventional thready two-conductor cable with cross section i.e. 0.5 mm to 1 mm. Use separate cables for probe 

and load or supply connections. Mixing low-level signal probe cables and load or supply cables affects devices 
performance. After the installation completion replace the front cover of the electric enclosure and ensure that when the 

device is operable only the front touch panel is user accessible. 

 

Setup 

The device contains luminous display in which parameters and messages are displayed. It also contains three light 

indicators colored red, yellow and green as well as three touch buttons. Became familiar with the front touch panel of the 

device as shown in Figure 2. 

 

By pressing momentarily button “POWER” the device toggles between ACTIVE and INACTIVE state. When the device 

switches to ACTIVE state the message “On” is displayed. The message “Off” is displayed when the device goes to 

INACTIVE state. Display shows the temperature which is defined by parameter diS the meaning of which will be 

explained below. 

 

In order to adjust the parameters of the device toggle first to ACTIVE state. The green indicator will be switched on. The 

display shows again the predefined temperature. To modify these values press momentarily the key “

” or “

”. The 

yellow indicator (SET/DEFROST) lights on as an indication of setup process. Display will show one after the other the 

mnemonics (abbreviations) of the parameter names as well as the respective pre-stored values. When the value of the 

parameter which needs change is shown at the display use  “

” and “

” keys to modify. The newly entered value will be 

automaticaly stored and the device will show the next. 

 

You can modify the following parameters: 

™

 

SEt   Is the temperature difference (S1-S2) in which the collector pump should be activated. 

™

 

dSu  This value is called delayed start-up and can be adjusted between 0 sec and 240 sec. It means the delay 

interval that should be elapsed before the pump relay will be activated. It is used to provide improved system stability. If 

no delayed startup is needed simply set this value to zero 

™

 

dt  Temperature difference hysteresis. This parameter defines how many degrees should the calculated temperature 

difference be reduced below the “SEt” value in order the device to switch off the collector pump. 

™

 

bt   Domestic hot water desired temperature. This parameter defines the temperature of domestic hot water which 

will be produced by utilizing only the auxiliary energy source. The actual domestic hot water temperature can be 

seriously higher depending to the solar activity.  

™

 

dbt   Auxiliary heating source activation hysteresis. Defines the minimum temperature decrease of the domestic hot 

water temperature (bt ) which needed in order the respective relay to be reactivated. 

™

 

dEF  Anti-freeze option. Choose “001” if you need anti-freeze protection or “000” if you don’t. The anti-freeze option 

when selected activates the collector pump when the S1 temperature is below 3°C. The relay is switched off again when 

S1 temperature is over 5°C. Anti-freeze protection is functional either in ACTIVE or INACTIVE state.  

™

 

diS   Defines which temperature will be shown during the normal operation. Choose «000» for showing the S1-S2 

difference, choose «001» for showing the S1 temperature, «002» for S2 and «003» for S3. 

After the completion of the parameter setup process the yellow indicator is switched off and the device returns from setup 

to the normal operation. 

 

If you need to pass rapidly through the parameters you can do it by pressing the “POWER” key instead of waiting some 

seconds.  

 

The setup process is graphically explained in Figure 3.

 

 

Operation 

By pressing momentarily the key “POWER” toggles the device between ACTIVE and INACTIVE state. While toggling 

between the states «On» and «Off» messages are shown accordingly. 

 

When the collector pump relay is activated the red indicator lights on. 

When the auxiliary heating source relay is activated the red dot of the rightmost digit lights on. 

If the delayed startup value has been set to a non zero value the defined delay in seconds must be elapsed prior to the 

pump relay activation. During this delay the green indicator flashes.  
In freezing environmental temperatures and only when the anti-freeze option is chosen the yellow indicator flashes the 

collector pump relay is activated.

 

 

In ACTIVE state 

 

green indicator lights on or flashes 

 

display shows the displayes temperature as  defined by diS parameter  

 

controls the collector pump according to the pre-stored parameters 

 

controls the auxiliary heating source according to the pre-stored parameters 

 

checks for freezing enironmental temperature if this option is enabled (parameter dEF)  

 

checks probes healthy condition 

 

In INACTIVE state 

 

green indicator is either switched off or flashing 

 

display shows the displayes temperature as  defined by diS paramete. 

 

controls the collector pump according to the pre-stored parameters 

 

auxiliary heating source is always deactivated 

 

checks for freezing enironmental temperature if this option is enabled (parameter dEF) 

 

checks probes healthy condition

 

 

 If you press the same key continuously the display shows “---” and then the temperature readings from probe «S1=» 

and «S2=». Then the device returns to the normal operation. This process is shown in Figure 4. If any kind of 

 A 

MP-DT    Integra 3P 

Differential Thermostat with Auxiliary Heating Source control 

& 3 sensors 

Содержание MP-DT Integra 3P

Страница 1: ...ρίου είναι 30m Η σύνδεση µπορεί να γίνει µε απλό πολύκλωνο καλώδιο δυο αγωγών π χ 2x1mm Μη χρησιµοποιείτε κοινά καλώδια για τη σύνδεση αισθητηρίων και ρελέ ή τάσης τροφοδοσίας Η χρήση κοινών καλωδίων από τα οποία διέρχονται ταυτόχρονα χαµηλής ισχύος σήµατα και ρεύµατα υψηλής τάσης ή έντασης επηρεάζει την απόδοση της συσκευής Μετά την ολοκλήρωση της εγκατάστασης τοποθετήστε το κάλυµµα της πρόσοψης ...

Страница 2: ...αυτή παρουσιάζεται αναλυτικά στο Σχήµα 4 Αν κάποιο αισθητήριο παρουσιάζει βλάβη τότε αντί για τη θερµοκρασία του εµφανίζεται το µήνυµα Err Αν η θερµοκρασία του αισθητηρίου υπερβαίνει τα όρια θερµοµέτρησης 0 C 150 C τότε αντί της θερµοκρασίας του αισθητηρίου εµφανίζονται τα µηνύµατα Lo και Hi αν η θερµοκρασία βρίσκεται κάτω από τους 0 C ή πάνω από τους 150 C αντίστοιχα Η λογική της λειτουργίας της ...

Страница 3: ...fined by parameter diS the meaning of which will be explained below In order to adjust the parameters of the device toggle first to ACTIVE state The green indicator will be switched on The display shows again the predefined temperature To modify these values press momentarily the key or The yellow indicator SET DEFROST lights on as an indication of setup process Display will show one after the oth...

Страница 4: ...echnical characteristics capabilities and operation of the device as described at the present manual can be modified without prior notice ΤΕΧΝΙΚΑ ΧΑΡΑΚΤΗΡΙΣΤΙΚΑ TECHNICAL CHARACTERISTICS Εύρος µέτρησης Θερµοκρασίας Temperature reading limits 0 C 150 C Θερµοκρασία λειτουργίας µονάδας Main unit operation temperature 20 C 60 C Ακρίβεια µέτρησης Reading accuracy 1 5 C Ηλεκτρική αντοχή επαφών ωµικό φορ...

Страница 5: ......

Страница 6: ...ding process Σχήµα 3 ιαδικασία ρύθµισης Figure 3 Setup process A Κότρωνος 27 Αιγάλεω Αθήνα Ελλάδα Τηλ 210 5693111 Φάξ 210 5693093 www charmeg gr 27 Kotronos str Aegaleo Athens Greece Tel 030 210 5693111 Fax 030 210 5693093 www charmeg gr Mpdt3p09 Doc MP_DT_Integra_3P_Users_Manual_gr_en_7 doc ...

Отзывы: