24
LT5558 (ISS 7)
LAY FUEL BED
Important: -
Refer to the Health & Safety Notice located on page 3 of this booklet before laying or replacing any refractory
material.
In the event of replacing fuel bed components please use only the specified number of components as illustrated.
Only use fuel bed component provided for this appliance. In the interest of safety and efficiency of your appliance
when replacing the fuel bed it is essential that the existing fuel bed be removed and the new components are
replaced correctly as a complete set.
Lay fuel bed as described under Section 4.
Warning:
It is important that the fuel bed components are positioned as shown in these instructions.
If the fuel bed components are not positioned correctly this may result in damage to the glass.
REFIT GLASS PANEL
Refit glass panel. Prior to replacing the glass panel it may necessary to adjust the seal around the glass to ensure
it is not seen when the decorative trim or fascia is fitted.
CHECKING FOR COMBUSTION PRODUCTS CLEARENCE
IMPORTANT:-The smoke test must be carried out
with the fire starting from cold.
Light the fire and leave at maximum input.
Close all the doors and windows.
After five minutes fit the smoke match in a
holder and position as illustrated with the head
of the match just inside the test opening.
Run the match along the top edge All smoke
must be drawn into the test opening if the
clearance is satisfactory.
If spillage occurs wait a further five minutes and
repeat the test.
Repeat the test with doors open and with any extractor fans in other rooms in operation.
If spillage is detected the cause must be discovered and the fault corrected, if the fault cannot be corrected,
disconnect the fire from the gas supply and seek expert advice. Spillage can be caused by a restriction in the flue
system, down draught or insufficient ventilation into the room where the fire is installed.