background image

Ordering Information

Optional Accessories

•  0-24 hour equalize timer
•  Automatic 24 hour equalize timer
•  Low DC voltage alarm relay

•  High DC voltage alarm relay
•  Current failure relay
•  AC power failure relay

•  DC cranking disconnect relay
• AC pilot 

light

Specifications

AC Input

108-132 volts/60 Hz (220 volts/50 Hz optional)

Operating Temperature

0º to 50º C (32º to 122º F)

Storage Temperature

-20º to 60º C (-4º to 140º F)

Cooling

Convection

DC Output

Float

2.16 VPC for lead Acid, 1.45 VPC for nickel cadmium

Equalize

2.33 VPC for lead Acid, 1.55 VPC for nickel cadmium

Current Limit

Approximately 135%

Enclosure

304 stainless steel hinged cover to facilitate installation

0

10

20 30

40

50

60

70

80

90 100

% OF RATED CHARGING CURRENT (AMPS)

VPC

2.5

2.4

2.3

2.2

2.1

2.0

1.9

1.8

Equalize

Float

Typical Output Curve

Contact your Charles sales representative for specific
product information.

When ordering, please specify:

1. Model number 
2. AC input: voltage & frequency 
3. Battery type and number of cells 
4. Ampere-hour capacity of battery 
5. Recharge time desired 
6. Description of load
7. Options

D-IND001-B01 Rev. 

3

12 Volt

Model

Number

Height
Inches

Width

Inches

Depth

Inches

Approx.

Weight

D.C. Output

Amps

System
Voltage

24 Volt

32 Volt

AE1206*

6

12

11

9

8.5

12

AE1210*

10

12

11

9

8.5

14

AE1220*

20

12

11

9

8.5

22

AE1230

30

12

11

9

8.5

26

AE2406*

6

24

11

9

8.5

14

AE2410*

10

24

11

9

8.5

22

AE2420*

20

24

16.5

15

8.5

38

AE2430

30

24

16.5

15

8.5

55

AE3210

10

32

11

9

8.5

26

AE3230

30

32

16

17

14.5

74

*UL Listed

Charles Industries, Ltd.
Industrial Group
5600 Apollo Drive
Rolling Meadows, IL 60008 USA

Voice: 

(847) 806-6300  

Fax:  

(847) 806-6352 

E-mail:

[email protected]

IS0 9000

REGISTERED 

QUALITY SYSTEM 

Отзывы: