Table 3.  

Minimum Wire Size from Output of C-Power

Model Number

DC Amp Max

15’ Length

25’ Length

PS2415

15

12 AWG

12 AWG

PS2415

15

12 AWG

12 AWG

PS2430

30

10 AWG

10 AWG

PS2430

30

10 AWG

10 AWG

PS1230

30

10 AWG

10 AWG

External connections to the C-Power shall comply with the U.S. Coast Guard Electrical Regulations
(33CFR183 subpart I).

WARNING

Making AC Connections on Terminal Block 1 (TB1)

After determining the wire lengths and gauges, make the AC wiring connections to TB1. (Refer to the Block Dia-
gram in Figure 1.) To make connections to the terminal blocks:

Step

Action

1.

Remove the small screw in the center of the unit that secures the sliding door to the top cover

2.

Gently slide the door up until it stops

3.

Bring the AC input wire in through the left side access hole on the bottom of the C-Power

4.

Connect the WHT terminal to the white (neutral) input

5.

Connect the BLK terminal to the black (hot) AC input

6.

Connect the GRN terminal to the green (ground) input.

Making DC Connections on Terminal Block 2 (TB2)

After the appropriate wire lengths and gauges have been determined, make the DC connections to TB2. (Route
the DC wire through the right-side access hole on the bottom of the C-Power.) TB2 has one positive (+) terminal
and one negative (−) terminal.

Closing the Access Door

Before closing the access door, make sure that all electrical connections have been made properly. Also check
that all wiring is properly dressed with no exposed, bare wires. Pull down the C-Power access door and secure it
to the top cover with the small screw provided.

Changing Internal Fuses

Irregular conditions may cause one or more of the internal fuses to blow. ALWAYS determine there is no live pow-
er before replacing a fuse. To access the fuses, remove the small screw in the center of the unit that secures the
sliding door to the top cover. Slide the access door up until it stops. The AC fuse (F1) is located just above the
AC terminal block (TB1). The DC fuses (F2 & F3) are located above the DC terminal block (TB2). When replacing
fuses, use only fuses of the exact type and rating (See Table 4). Before reapplying power, pull down the access
door to close it. Once down, secure the access door to the top cover with the small screw provided.

Table 4.  

Internal Fuse Replacement Sizes

Model Number

AC Input (F1)

DC Output (F2)

DC Output (F3)

PS2415

12-Amp/250 Volt SLO-BLO 30-Amp/32 Volt FAST ACTING

PS1230

12-Amp/250 Volt SLO-BLO 30-Amp/32 Volt FAST ACTING

30-Amp/32 Volt FAST ACTING

PS2430

15-Amp/250 Volt SLO-BLO 40-Amp/32 Volt FAST ACTING

40-Amp/32 Volt FAST ACTING

Содержание C-Power

Страница 1: ...sue 1 Print 3 1 Charles Industries Ltd All rights reserved Printed in the United States of America C POWERR INSTALLATION INSTRUCTIONS OWNER S MANUAL 12 VDC 24 VDC 15 30 Amp MARINE ELECTRONIC POWER SUP...

Страница 2: ...leaning Precaution 3 Grounding Precautions 3 INSTALLING THE C POWER 4 Choosing Mounting Hardware 4 Mounting the C Power 4 Mounting the Optional Splash Guard 4 Choosing Electrical Wiring Hardware 4 Cho...

Страница 3: ...ty and operating instructions for the C Power Read the entire manual before usage Environmental Precaution Do not expose the C Power to rain snow or excessive moisture C Power Application Precaution T...

Страница 4: ...one side of the mounting hardware half way into the drilled mounting holes 6 Align the mounting slots on the C Power with the secured hardware and slide the C Power s mounting flange under the washers...

Страница 5: ...0V Access to PCB and TB1 TB2 F1 F2 F3 Fuses DC DC LOAD Note 2 Note 3 F3 Figure 1 C Power 15 30 Amp Block Diagram Choosing Wire Gauge Use Table 2 and Table 3 to determine the appropriate wire gauges Av...

Страница 6: ...2 Route the DC wire through the right side access hole on the bottom of the C Power TB2 has one positive terminal and one negative terminal Closing the Access Door Before closing the access door make...

Страница 7: ...turned on 2 Internal red LED on The unit is at half power because the ambient air is too hot The unit may be at half power because the fan is not working Full power will be restored when the temperat...

Страница 8: ...re U S Metric Weight 9 pounds 4 1 kilograms Height 13 25 inches 33 7 centimeters Width 9 5 inches 24 1 centimeters Depth 3 7 inches 9 4 centimeters AC Input 120 VAC nom 220 VAC nom See the label on th...

Отзывы: