MAINTENANCE AND STORAGE

The owner/operator is responsible for all periodic 
maintenance.

Complete all scheduled maintenance in a timely manner. 
Correct any issue before operating the generator.

Tampering with the factory set governor will void 
your warranty.

Engine Maintenance

To prevent accidental starting, remove and ground spark 
plug wire before performing any service.

Oil 

Change oil when the engine is warm. Refer to the oil 
specification to select the proper grade of oil for your 
operating environment.
1.  Set the generator on top of a work bench or table.
2.  Loosen the cover screws and remove the 

maintenance cover.

3.  Pop up the rubber maintenance plug, from below 

the drain bolt.

4.  Remove the drain bolt.
5.  Tilt the generator on its side and allow the oil to 

drain completely.

6.  Replace the drain bolt.
7.  Add standard engine oil and replace oil fill cap/

dipstick. DO NOT OVERFILL.

Spark Plugs

1.  Remove the spark plug cable from the spark plug.
2.  Use a spark plug socket tool or socket (not 

included) to remove the plug.

3.  Inspect the electrode on the plug. It must be clean 

and not worn to produce the spark required for 
ignition.

4.  Make certain the spark plug gap is 0.7 - 0.8 mm or 

(0.028 - 0.031 in.).

5.  Refer to the spark plug recommendation chart when 

replacing the plug.

6.  Carefully thread the plug into the engine.
7.  Use the spark plug socket (not included) to firmly 

install the plug.

8.  Attach the spark plug wire to the plug.

Maintenance, replacement, or repair of emission 
control devices and systems may be performed 
by any non-road engine repair establishment or 
individual.

NOTE

Never operate a damaged or defective generator.

WARNING

WARNING

Improper maintenance will void your warranty.

WARNING

Oil Cont’d.

0.7-0.8 mm

0.028-0.031 in.

Once oil has been added, a visual check should show 
oil about 1-2 threads from running out of the fill hole.
If using the dipstick to check oil level, DO NOT screw 
in the dipstick while checking.

NOTE

8.  Reinstall the maintenance cover and tighten the 

cover screws.

9.  Dispose of used oil at an approved waste 

management facility.

GFCI

Your generator is equipped with two (2) Ground Fault 
Circuit Interrupter (GFCI) duplexes. In the event of a 
ground fault, a GFCI trips automatically to stop the 
flow of electricity and prevent serious injury. The green 
indicating light on the receptacle will also turn off. Press 
the reset button located on the front of the receptacle to 
restore flow of electricity. (A) The green indicating light 
will also turn back on. GFCI does not protect against 
circuit overloads.

To ensure proper operation of the GFCI duplex, perform 
this test monthly:
1.  With the generator running, plug a lamp into the 

GFCI receptacle. Turn the lamp on.

2.  Press the “Test” button located on the front of 

the receptacle to trip the device. (A) This should 
immediately stop the flow of electricity and shut off 
the lamp. If the electricity is not stopped, do not 
use this receptacle until is has been serviced or 
replaced.

3.  Press the “Reset” button located on the front of 

the receptacle to restore the flow of electricity. If 
the indicator light does not go out and come back 
on or if the GFCI cannot be reset then it must be 
replaced.

A

For the GFCI receptacles to work properly the neutral wire 
must be bonded to ground or to the generator frame.  Your 
Champion generator comes with the neutral wire already 
bonded to the frame. If the bonding wire is removed then 
the GFCI receptacles will no longer function as designed. 
If the neutral bonding wire is removed to accommodate 
a transfer switch installation for connection to a house 
or building, then the transfer switch must not switch off 
the neutral connection to ground within the building. 
Champion Power Equipment recommends that you consult 
with a licensed, local electrician. Due to the variety of 
local codes, we cannot specifically advise you regarding 
modifications to the wiring of your portable generator.

WARNING

OPERATION

Содержание 73001i-DF (EU)

Страница 1: ... d e dos años G a r a n t í a l i m i t a d a d e dos años T h ree Year Limited Warran t y T h ree Year Limited Warran t y G a r a n t í a l i m i t a d a de un año G a r a n t í a l i m i t a d a de un año Garantie li m i t é e d e t r o i s a n s Garantie li m i t é e d e t r o i s a n s T wo Year Limited Warrant y G a rantie limitée de deux a n s T wo Year Limited Warrant y G a rantie limitée d...

Страница 2: ...rve the right to change alter or improve the product and this manual without prior notice Please familiarize yourself with the following symbols The safety symbol and key words are safety warnings Follow all safety messages to avoid accidents or injury CAUTION indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury CAUTION CAUTION used without the sa...

Страница 3: ...re dust or dirt DO NOT allow any material to block the cooling slots If connected devices overheat turn them off and disconnect them from the generator DO NOT use the generator if Electrical output is lost Equipment sparks smokes or emits flames Equipment vibrates excessively CAUTION Operation of this equipment may create sparks that can start fires around dry vegetation A spark arrester may be re...

Страница 4: ...fire prevention requirements La operación de este equipo puede originar chispas que pueden crear incendios cerca de la vegetación seca Es posible que se requiera un parachispas El operador deberá comunicarse con los organismos locales encargados de combatir incendios para conocer las leyes o reglamentos relacionados con los requisitos para prevenir incendios FOR USE IN A WEATHER PROTECTED AREA ONL...

Страница 5: ...d replace oil fill cap dipstick DO NOT OVERFILL 5 Check engine oil level daily and add as needed The recommended oil type is 10W 30 automotive oil NOTE Add Engine Oil DO NOT attempt to crank or start the engine before it has been properly filled with the recommended type and amount of oil Damage to the generator as a result of failure to follow these instructions will void your warranty CAUTION Ad...

Страница 6: ...g and storing turn off the cylinder valve and fuel valve and disconnect the cylinder Plug the outlet usually by a plastic protective cap if one is available Keep cylinders away from heat and ventilated when in a vehicle CAUTION Connecting LPG Cylinder Cont d Grounding Your generator must be properly connected to an appropriate ground to help prevent electric shock A ground terminal connected to th...

Страница 7: ...l or LPG To select the desired fuel source simply rotate the selector switch to the fuel symbol on the panel Turn the fuel selector switch to the 12 o clock vertical position for LPG operation A Turn the fuel selector switch to the 3 o clock horizontal position for petrol operation B A B LPG GAS When the battery switch is in the ON position the switch will light up if the battery is sending out a ...

Страница 8: ... by pouring warm water over the top of the tank Economy Control Switch The Economy Control switch can be activated in order to minimize fuel consumption and noise while operating the unit during times of reduced electrical output allowing the engine speed to idle during periods of non use The engine speed returns to normal when an electrical load is connected When the economy switch is off the eng...

Страница 9: ...fuel starvation has stopped the engine This usually takes a few minutes 6 Press the ignition switch to the OFF position 7 Turn battery switch to the Off Position Important Always ensure that the fuel valve and the ignition switch are in the OFF position when the engine is not in use When turning off the generator after LPG operation make sure the LPG cylinder knob is in the fully closed position N...

Страница 10: ...he dipstick to check oil level DO NOT screw in the dipstick while checking NOTE 8 Reinstall the maintenance cover and tighten the cover screws 9 Dispose of used oil at an approved waste management facility GFCI Your generator is equipped with two 2 Ground Fault Circuit Interrupter GFCI duplexes In the event of a ground fault a GFCI trips automatically to stop the flow of electricity and prevent se...

Страница 11: ...the generator Water can enter the generator through the cooling slots and damage the generator windings CAUTION Disconnect the Battery 1 Remove the battery panel cover 2 Remove the protective cover from the black negative battery lead 3 Disconnect the black negative lead from the black negative terminal on the battery and store the cap screw and nut 4 Repeat steps 1 2 for the red positive battery ...

Страница 12: ...sition When storing the generator for extended periods of time make sure that the ignition switch the fuel valve and the battery switch are set in the the the OFF position and the battery leads have been disconnected from the battery DANGER Troubleshooting Problem Cause Solution Generator will not start No fuel Add fuel Faulty spark plug Replace spark plug Unit loaded during start up Remove load f...

Страница 13: ...Off Yes Wheels Yes Wheel Type Solid Wheel Diameter 5 5 in CE Approved Yes 73001I DF EU WIRING DIAGRAM DC COIL DC DIODE _ DC12V CIRCUIT BREAKER 8A Y CONTROL UNIT PORTFIRE ECO SW EARTH TERMINAL OIL LEVEL SW SPARKING PLUG STOP SW L W G B Y R YELLOW BLACK BLUE GREEN RED WHITE Br WHITE BLUE GREEN YELLOW WHITE GREEN BROWN BLACK WHITE B W W L G Y W G GENERATOR ENGINE G RECEPTACLE AC COIL SUB COIL W B W O...

Страница 14: ...82 81 56 57 58 59 60 62 64 65 66 67 70 69 71 72 74 76 77 80 34 33 30 31 29 27 26 55 52 46 45 44 43 42 41 39 38 37 25 24 22 21 20 19 18 17 16 15 14 13 1 2 3 4 5 6 7 8 9 10 11 40 35 68 86 87 88 91 92 63 5 5 28 36 111 110 109 75 73 78 79 36 49 50 51 61 48 104 96 97 98 99 100 101 102 103 105 106 107 54 53 47 23 108 12 25 32 ...

Страница 15: ...8 0 2 1 8 5 M t u N e g a C 0 1 0 2 0 2 0 4 41 83 200701 03 2 Handle Left Blac e R 1 1 0 0 2 1 1 5 1 2 1 1 k 1 e l c a t p e c 1 k c a l B t f e L t e k c a r B 2 1 0 4 0 7 0 0 2 3 8 2 4 8 4 1 x 4 M w e r c S 4 1 4 0 9 1 8 1 2 2 1 0 1 k c a l B e g n a l F 4 M t u N k c o L 1 4 0 1 7 7 1 6 1 3 2 1 1 t h g i R r e t r o p p u S 5 0 0 0 6 1 0 2 3 8 3 4 2 n o t t u B h s u P r e k a e r B A 5 1 C A 5...

Страница 16: ...Page intentionally left blank Page intentionally left blank ...

Страница 17: ......

Отзывы: