201160 - 12,000W ELEcTRic START GENERATOR

OPERATiON

19

 

NOTicE

The generator engine works well with 10% or less ethanol 
blended gasoline. When using ethanol-gasoline blends there 
are some issues worth noting:

 

Ethanol-gasoline blends can absorb more water than 
gasoline alone. 

 

These ethanol blends can eventually separate, leaving 
water or a watery goo in the tank, fuel valve and 
carburetor. The compromised gasoline can be drawn into 
the carburetor and cause damage to the engine and/or 
create potential hazards. 

 

If a fuel stabilizer is used, confirm that it is formulated to 
work with ethanol-gasoline blends.

 

Any damages or hazards caused by using ethanol blended 
gasoline higher than 10% by volume, improperly stored 
gasoline, and/or improperly formulated stabilizers, are not 
covered by manufacturer’s warranty. 

It is advisable to always shut off the gasoline supply and 
run the engine to starvation after each use. See Storage 
instructions for extended non-use.

Grounding

Your generator must be properly connected to an appropriate 
ground to help prevent electric shock.

 

WARNiNG

Failure to properly ground the generator can result in electric 
shock.

A ground terminal connected to the frame of the generator has 
been provided (see Controls and Features for terminal location). 
For remote grounding, connect a length of heavy gauge 
(12 AWG minimum) copper wire between the generator ground 
terminal and a copper rod driven into the ground. We strongly 
recommend that you consult with a qualified electrician to ensure 
compliance with local electrical codes.

Neutral Floating*

 

Neutral circuit 

IS NOT

 electrically connected to the frame/

ground of the generator.

 

The generator (stator winding) is isolated from the frame and 
from the AC receptacle ground pin.

 

Electrical devices that require a grounded receptacle pin 
connection will not function if the receptacle ground pin is not 
functional.

Neutral Bonded to Frame*

 

Neutral circuit 

IS

 electrically connected to the frame/ground of 

the generator.

 

The generator system ground connects lower frame cross-
member below the alternator. The system ground is connected 
to the AC neutral wire.

* See your Specifications section for specified type of grounding.

OPERATiON

cO Shield

®

 - carbon Monoxide (cO) Detection 

and Auto-shutoff System

CO Shield

®

 technology monitors the accumulation of carbon 

monoxide (CO), a poisonous gas produced by engine exhaust when 
the generator is running. If CO Shield

®

 detects unsafe elevated 

levels of CO gas, it automatically shuts off the engine.

CO SHIELD

®

 IS NOT A SUBSTITUTE FOR AN INDOOR CARBON 

MONOXIDE ALARM OR FOR INDOOR OPERATION.

DO NOT allow engine exhaust fumes to enter a confined area 
through windows, doors, vents or other openings.

Generators must ALWAYS be used outdoors, far away from 
occupied buildings with engine exhaust pointed away from people 
and buildings.

If misused and operated in an unapproved and unsafe location 
that results in the accumulation of poisonous CO gas inside 
an enclosed or partially enclosed space, for example a house, 
garage or a garage with the door partially open, CO Shield

®

 will 

automatically shut off the generator and then will illuminate a 
blinking red LED light. 

Read the action label for next steps.

3783-L-SF

Move generator to an open, outdoor area. Point exhaust away.

Don’t run generators in enclosed areas (e.g. not in house or garage).

Mover el generador a un área abierta a la intemperie. Apunte el 

escape alejado. No corra los generadores en áreas cerradas (ej. no 

en una casa o garaje).

Déplacer le générateur vers un espace extérieur en plein air. Garder 

l’échappement loin. Ne pas faire 

fonctionner les générateurs dans un 

espace clos (ex., pas dans une maison 

ou un garage). 

EX

HA

UST

EL

 E

SC

APE

L’E

CH

AP

PE

MEN

T

POINT AWAY

DIRIJA ALEJADO

DIRIGER LOIN

AUTOMATIC SHUTOFF – YOU MUST:

APAGADO AUTOMÁTICO – USTED DEBE:

ARRÊT AUTOMATIQUE – VOUS DEVEZ :

Move to fresh air and 

get medical help if 

sick, dizzy or weak.

Mueva al aire fresco y obtenga asistencia 

medica si está enfermo, mareado, o débil.

Aller à l'air frais et obtenir de l'aide médicale 

si malade, étourdi ou faible.

ACTION LABEL

ETIQUETA DE ACCIÓN

ÉTIQUETTE D'ACTION

APN 3783-L-SF

Rev

A

Size

120 x 100 mm

Artwork Notes

2mm safe margin; to be printed on white substrate

UL969 certification

Revision Changes

This artwork belongs to Champion Power Equipment. The contents are confidential and privileged and shall not be disclosed to or used by or for 
outside parties without the explicit consent of Champion Power Equipment.

Colors

K

485

152

109

---

Содержание 201160

Страница 1: ...should remain with the product Specifications descriptions and illustrations in this manual are as accurate as known at the time of publication but are subject to change without notice This product m...

Страница 2: ...monoxide risks you ll be better prepared to protect your family from this colorless oderless threat CARBON MONOXIDE SAFETY THE BIG PICTURE KNOW THE SYMPTOMS Headache Nausea Shortness of breath Dizzin...

Страница 3: ...ection 21 Starting the Engine 21 Battery 22 Connecting Electrical Loads 22 Do Not Overload Generator 23 GFCI 23 Stopping the Engine 24 Moving the Generator 24 Operation at High Altitude 25 Maintenance...

Страница 4: ...effort has been made to ensure the accuracy and completeness of the information in this manual at the time of publication and we reserve the right to change alter and or improve the product and this...

Страница 5: ...guards in place Rotating parts can entangle hands feet hair clothing and or accessories Traumatic amputation or severe laceration can result Keep hands and feet away from rotating parts Tie up long ha...

Страница 6: ...sistance is felt and then pull rapidly to avoid kickback DO NOT start or stop the engine with electrical devices plugged in and turned on WARNING Although the generator contains a spark arrester maint...

Страница 7: ...ine outdoors in a well ventilated area DO NOT pump gasoline directly into the generator at the gas station Always use an approved container to transfer the fuel to the generator DO NOT overfill the ga...

Страница 8: ...ctanos como m nimo M ximo de etanol de 10 ESSENCE SANS PLOMB SEULEMENT Indice d octane minimal de 87 Maximum 10 d thanol K 109 Colors LPN 1110 L OP Rev B Size 46 x 46 mm Artwork Notes 3mm corner radiu...

Страница 9: ...before operation Electric Shock Failure to use in dry conditions and to observe safe practices can result in electric shock Improper connections to a building can allow current to backfeed into utili...

Страница 10: ...Off Run Push choke knob to RUN position Choke Pull choke knob to CHOKE position Circuit Breaker On Circuit Breaker Off Circuit Breaker Reset Flip Circuit Breaker Reset Push Locking Receptacle SYMBOL...

Страница 11: ...be disclosed to or used by or for outside parties without the explicit consent of Champion Power Equipment K CYAN 376 186 152 CG1 Starting the Engine DANGER Move generator outside and far away from w...

Страница 12: ...Cap Used to fill oil 3 Spark Plug Arrester and Muffler 4 Support Leg 5 Dipstick Used to check oil level 6 Never Flat Wheels 12 in 30 5 cm 7 Ground Terminal Consult an electrician for local grounding r...

Страница 13: ...120 240V AC 50A NEMA 14 50R May be used to supply electrical power for operation of 120 240 Volt AC 50 Amp single phase 60 Hz electrical loads B Y 120 240V AC 30A Locking NEMA L14 30R May be used to s...

Страница 14: ...ust when the generator is running If CO Shield detects elevated levels of CO gas it automatically shuts off the engine See CO Shield section for more information MODE DESCRIPTION 1 Voltage V Output vo...

Страница 15: ...s subject to the following two conditions 1 This device may not cause interference and 2 This device must accept any interference including interference that may cause undesired operation of the devic...

Страница 16: ...n roll through the wheel from the outside 4 Slide the wheel pin roll through the mount point on the frame 5 Secure with the R Pin 6 Install wheel hub cap onto wheel 7 Repeat steps 2 6 to attach the se...

Страница 17: ...000 ml Volume after oil and oil filter change 44 fl oz 1300 ml 5 Pull out dipstick and check engine oil level Add as needed DO NOT OVERFILL 6 Replace dipstick 7 Close engine access cover NOTICE Check...

Страница 18: ...e can expand after filling A minimum of in 6 4 mm of space left in the tank is required for gasoline expansion although more than in 6 4 mm is recommended Gasoline can be forced out of the tank as a r...

Страница 19: ...cifications section for specified type of grounding OPERATION CO Shield Carbon Monoxide CO Detection and Auto shutoff System CO Shield technology monitors the accumulation of carbon monoxide CO a pois...

Страница 20: ...minute after it was manually shut off This does not occur if generator shut off from a high CO event If CO Shield system experiences a fault and no longer provides protection the generator is shutoff...

Страница 21: ...properly cool before transport or for storage purposes Failure to follow proper safety precautions may result in personal injury damage to the generator and void the manufacturer s warranty WARNING Du...

Страница 22: ...nnect 3 phase loads to the generator DO NOT overload the generator Use only a high quality insulated compatible 3 wire or 4 wire grounded cord set rated equal to or greater volts and amps than the rec...

Страница 23: ...nt of a ground fault a GFCI trips automatically to stop the flow of electricity and prevent serious injury The green indicator light A on the receptacle will also turn off Press the RESET B button loc...

Страница 24: ...Generator CAUTION NEVER lift or carry the generator using the folding handle NEVER tilt sideways while moving the generator ALWAYS place the generator on its wheels in the upright position ALWAYS turn...

Страница 25: ...n a clean dry operating environment DO NOT expose the unit to extreme conditions excessive dust dirt moisture or corrosive vapors WARNING Never operate a damaged or defective generator WARNING Imprope...

Страница 26: ...plug types in Specifications when replacing the plug 6 Firmly re install the plug 7 Attach the spark plug cable to the spark plug 8 Repeat Steps 1 7 for spark plug on other side of engine Cleaning th...

Страница 27: ...ct our Technical Support Team at 1 877 338 0999 for all other service and or adjustment needs Generator Battery Your generator is equipped with an automatic battery charging circuit that charges the b...

Страница 28: ...er Check adjust valve clearance EVERY 3 YEARS Replace fuel line To be performed by knowledgeable experienced owners or CPE certified service centers STORAGE WARNING To avoid accidental or unintended i...

Страница 29: ...OTICE If the generator has been improperly stored for a period longer than 30 days with ethanol blended gasoline in the gasoline tank all fuel must be drained If the gasoline tank was properly emptied...

Страница 30: ...gine Oil Type 80 100 120 28 9 F C 17 8 6 7 4 4 15 6 26 7 37 8 48 9 10W 30 5W 30 Full Synthetic 10W 40 5W 30 NOTICE Temperature will affect engine oil and engine performance Change the type of engine o...

Страница 31: ...when CO Shield shutoffs occur due to accumulating carbon monoxide CO and if the red LED light blinks on the panel Move generator to an open outdoor area Point exhaust away from people and buildings Mo...

Страница 32: ...CO Shield continues to sense the fault and shuts off contact technical support Both CO Shield LEDs not blinking 10 times upon start up Starting the generator within 1 minute after being manually shuto...

Страница 33: ...beyond the product s limits modified installed improperly or connected incorrectly to any electrical component Normal maintenance is not covered by this warranty and is not required to be performed a...

Страница 34: ...gnosis parts and labor MANUFACTURER S EMISSION CONTROL SYSTEM WARRANTY COVERAGE This emission control system is warranted for two years subject to provisions set forth below If during the warranty per...

Страница 35: ...placement point for that part If the part fails prior to the first scheduled replacement the part shall be repaired or replaced by CPE according to Subsection d below Any such emissions related part r...

Страница 36: ...ister Mounting Brackets Carburetor Purge Port Connector TO OBTAIN WARRANTY SERVICE You must take your CPE engine or the product on which it is installed along with your warranty registration card or o...

Отзывы: