100423 - WIRELESS REMOTE START GENERATOR

OPERATION

14

5.  Screw on the gasoline cap and wipe away any spilled fuel.

!

 

CAUTION

Use regular unleaded unleaded gasoline with a minimum 
octane rating of 85 and an ethanol content of less than 10% 
by volume.

Do not mix oil and gasoline.

Fill tank to approximately 

¼

 in. (6.4 mm) below the top of 

the tank to allow for gasoline expansion.

DO NOT pump gasoline directly into the generator at the 
pump. Use an approved container to transfer the gasoline to 
the generator.

DO NOT fill tank indoors.

DO NOT fill tank when the engine is running or hot.

DO NOT overfill the tank.

DO NOT light cigarettes or smoke when filling the tank.

!

 

WARNING

Pouring gasoline too fast through the fuel screen may result 
in blow back of gasoline at the operator while filling.

"

 

NOTICE

Our engines work well with 10% or less ethanol blend 
gasoline. When using ethanol-gasoline blends there are 
some issues worth noting:

 

Ethanol-gasoline blends can absorb more water than 
gasoline alone. 

 

These blends can eventually separate, leaving water or a 
watery goo in the tank, fuel valve and carburetor. 

 

With gravity-fed supplies, the compromised gasoline can 
be drawn into the carburetor and cause damage to the 
engine and/or potential hazards. 

 

There are only a few suppliers of fuel stabilizer that are 
formulated to work with ethanol-gasoline blends.

 

Any damages or hazards caused by using improper 
gasoline, improperly stored gasoline, and/or 
improperly formulated stabilizers, are not covered by 
manufacturer’s warranty. 

It is advisable to always shut off the gasoline supply, run the 
engine to starvation and drain the tank when the equipment 
is not in use for more than 30 days.

Grounding

Your generator must be properly connected to an appropriate 
ground to help prevent electric shock.

!

 

WARNING

Failure to properly ground the generator can result in 
electric shock.

A ground terminal has been provided on the lower frame 
crossmember below the alternator. For remote grounding, 
connect of a length of heavy gauge (12 AWG minimum) copper 
wire between the generator ground terminal and a copper rod 
driven into the ground. We strongly recommend that you consult 
with a qualified electrician to ensure compliance with local 
electrical codes.

OPERATION

Generator Location

NEVER operate the generator inside any building, including 
garages, basements, crawlspaces and sheds, enclosure or 
compartment, including the generator compartment of a 
recreational vehicle. Please consult your local authority. In 
some areas, generators must be registered with the local 
utility. Generators used at construction sites may be subject 
to additional rules and regulations. Generators should be on 
a flat, level surface at all times. (Even while not in operation) 
Generators must have at least 5 ft. (1.5 m) of clearance from 
all combustible material. In addition to clearance from all 
combustible material, generators must also have at least 3 ft. 
(91.4 cm) of clearance on all sides to allow for adequate cooling, 
maintenance and servicing. Generators should never be started 
or operated in the back of a SUV, camper, trailer, in the bed of 
a truck (regular, flat or otherwise), under staircases/stairwells, 
next to walls or buildings, or in any other location that will not 
allow for adequate cooling of the generator and/or the muffler. 
DO NOT contain generators during operation. Allow generators 
to properly cool before transport or storage.

Place the generator in a well-ventilated area. DO NOT place the 
generator near vents or intakes where exhaust fumes could 
be drawn into occupied or confined spaces. Carefully consider 
wind and air currents when positioning generator.

Failure to follow proper safety precautions may void 
manufacturer’s warranty.

Содержание 100423

Страница 1: ...ad and understood before operating the product Failure to do so could result in serious injury This manual should remain with the product Specifications descriptions and illustrations in this manual a...

Страница 2: ...g the Engine 15 Battery 16 Connecting Electrical Loads 16 Do Not Overload Generator 16 Stopping the Engine 17 Operation at High Altitude 17 Maintenance 17 Cleaning the Generator 18 Changing the Engine...

Страница 3: ...ore each use Please always exercise common sense and always err on the side of caution when operating the product to ensure no accident property damage or injury occurs We want you to continue to use...

Страница 4: ...at could become caught WARNING Operation of this equipment may create sparks that can start fires around dry vegetation A spark arrestor may be required The operator should contact local fire agencies...

Страница 5: ...s excessively WARNING Medical and life support uses In case of emergency call 911 immediately NEVER use this product to power life support devices or life support appliances NEVER use this product to...

Страница 6: ...generator DO NOT overfill the gasoline tank Always keep gasoline away from sparks open flames pilot lights heat and other sources of ignition DO NOT light or smoke cigarettes When starting the generat...

Страница 7: ...aces stoves water heaters or other appliances that have a pilot light or other ignition source because they can ignite the fuel FOR USE IN A WEATHER PROTECTED AREA ONLY DO NOT EXPOSE TO RAIN Operating...

Страница 8: ...start the engine for wireless start and electric start 4 Air Filter Protects the engine by filtering dust and debris from the intake air 5 Recoil Starter Used to manually start the engine 6 Never Flat...

Страница 9: ...nables disables starting electrically Receptacles A W 120V AC 30A Locking NEMA L5 30R May be used to supply electrical power for operation of 120 Volt AC 30 Amp single phase 60 Hz electrical loads B t...

Страница 10: ...his function requires electrical current from the battery If the Ignition Switch is left in the ON position for extended periods several weeks the battery can be completely drained Moving the Ignition...

Страница 11: ...und to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential...

Страница 12: ...Repeat to attach the second Wheel Install the Support Leg 1 Attach the Support Leg D to the generator frame with Flange Bolts E and Flange Lock Nuts F 2 Slowly tip the generator back down so that it r...

Страница 13: ...hreshold level NOTICE The first 5 hours of run time are the break in period for the unit During the break in period stay at or below 50 of the running watt rating and vary the load occasionally to all...

Страница 14: ...help prevent electric shock WARNING Failure to properly ground the generator can result in electric shock A ground terminal has been provided on the lower frame crossmember below the alternator For r...

Страница 15: ...inst virtually all short duration voltage fluctuations Starting the Engine 1 Make certain the generator is on a flat level surface 2 Disconnect all electrical loads from the generator Never start or s...

Страница 16: ...ing but it is also recommended that the battery be fully charged at least once per month Connecting Electrical Loads Let the engine stabilize and warm up for a few minutes after starting Plug in and t...

Страница 17: ...ly 3 for every 1000 ft of elevation above sea level This is a natural trend and cannot be changed by adjusting the engine At high altitudes increased exhaust emissions can also result due to the incre...

Страница 18: ...mm socket and extension not included 2 Allow the oil to drain completely into an appropriate container 3 Replace the oil drain plug 4 Remove the oil fill cap dipstick to add oil MAX MIN OIL DIP STICK...

Страница 19: ...th an automatic battery charging circuit The battery will receive charging voltage when the engine is running The battery will maintain a proper charge if the unit is used on a regular basis about onc...

Страница 20: ...ll appliances are disconnected from the generator 2 Add a properly formulated fuel stabilizer to the gasoline tank 3 Turn the fuel valve to the ON position or for Dual Fuel models only set the fuel se...

Страница 21: ...tion or for Dual Fuel models ONLY set the fuel selector switch for operation on gasoline 4 After 5 minutes check the carburetor and air filter areas for any leaking gasoline If any leaks are found the...

Страница 22: ...il used based on weather conditions to suit the engine needs Fuel Specifications Use regular unleaded gasoline with a minimum octane rating of 85 and an ethanol content of less than 10 by volume DO NO...

Страница 23: ...9 30 31 32 34 35 36 37 38 39 40 41 42 43 2 3 4 5 6 7 8 9 10 11 14 15 10 16 12 17 18 51 52 53 54 55 56 57 64 65 66 67 75 77 19 20 22 21 50 50 76 78 44 33 13 58 59 60 61 62 63 45 46 48 68 69 70 71 73 74...

Страница 24: ...1 31 122 070015 01 Mount Vibration Fuel Tank 4 32 2 03 004 1 Flat Washer 24 x 6 5 x 1 5 Black 4 33 1 93 06 Lock Washer 6 4 Part Number Description Qty 34 1 5789 0620 1 Flange Bolt M6 x 20 Black 4 35 2...

Страница 25: ...ter 1 83 1 848 03 2 Washer 3 4 84 1 859 03 2 Lock Washer 3 4 85 1 6175 03 2 Nut M3 4 86 5 1460 003 Pilot Lamp 1 87 5 1040 004 Remote Excercise Button 1 88 5 1210 930 30Amp Circuit Breaker Push Button...

Страница 26: ...41 42 43 44 46 47 21 22 23 24 31 34 36 39 53 52 45 51 50 49 55 56 57 58 54 60 62 61 63 65 66 67 68 69 70 71 72 74 25 93 94 95 92 91 90 97 78 79 80 82 83 84 85 86 87 88 76 59 12 77 96 33 81 73 106 54...

Страница 27: ...buretor 1 35 27 080600 01 Air Guide Right Side 1 36 2 01 003 Stud Bolt M6 x 90 2 37 27 030100 01 Crankcase 1 Part Number Description Qty 38 21 127000 02 Oil Level Sensor 1 39 26 010100 01 Cylinder Hea...

Страница 28: ...1 95 23 020001 02 Breather Tube 112 35 1 96 1 5789 0615 Flange Bolt M6 x 15 4 97 2 01 010 Stud Bolt M8 x 35 2 98 23 030006 00 Plate Coil 1 99 27 091200 01 Cover Air Cleaner Black 1 100 23 091003 21 El...

Страница 29: ...IT BREAKER EXW FW MW1 L Y Y AVR Br 30A EARTH TERMINAL R w w G Y Y Y L L R W w 120V L5 30R R R R R R w B MW2 Y B G Y G Y R PILOT LAMP BUTTON Transition Receiver module W W C stepper motor L C Y O R B B...

Страница 30: ...on Out of fuel Fill fuel tank Low oil level Fill crankcase to the proper level Place generator on a flat level surface Generator cannot supply enough power or overheating Generator is overloaded Revie...

Страница 31: ...quired to be performed at a facility or by a person authorized by CPE Other Exclusions This warranty excludes Cosmetic defects such as paint decals etc Wear items such as filter elements o rings etc A...

Страница 32: ...l system is warranted for two years subject to provisions set forth below If during the warranty period emission related part on your engine is defective in materials or workmanship the part will be r...

Страница 33: ...ement point for that part If the part fails prior to the first scheduled replacement the part shall be repaired or replaced by CPE according to Subsection d below Any such emissions related part repai...

Страница 34: ...ets Carburetor Purge Port Connector TO OBTAIN WARRANTY SERVICE You must take your CPE engine or the product on which it is installed along with your warranty registration card or other proof of origin...

Отзывы: