Receiving Inspection

Upon receiving the pump, it should be 
inspected for damage or shortages.   
If damage has occurred, file a claim 
immediately with the company that 
delivered the pump. If the manual is 
removed from the packaging, do not 
lose or misplace.

Storage

Any product that is stored for a period 
longer than six (6) months from the 
date of purchase should be bench 
tested prior to installation.  A bench 
test consists of,  checking the impeller 
to assure it is free turning and a run 
test to assure the motor (and switch 
if provided) operate properly.  Do not 
pump out of liquid.

Controls

Manual models require a separate 
approved pump control device or panel 
for automatic operation.  Be sure the 
electrical specifi cation of the control 
selected properly match the electrical 
specifi cations of the pump.

Submergence

The pump should always be operated in 
the submerged condition.  The minimum 
sump liquid level should never be less than 
above the pump’s volute (See Figure 1).

Installation

These pumps are recommended for 
use in a sump, basin or lift station. 
The sump, basin or lift station shall be 
sealed and vented in accordance with 
local plumbing codes. 

This pump is 

designed to pump sewage, effl

  uent 

or wastewater, nonexplosive and 
noncorrosive liquids and shall NOT 
be installed in locations classifi ed as 
hazardous in accordance with the 
National Electrical Code (NEC) ANSI/
NFPA 70 or Canadian Electric Code 
(CEC).

 The pump should never be 

installed in a trench, ditch, or hole with 
a dirt bottom. The legs will sink into 
the dirt and the suction will become 
plugged.

The installation should be at a suffi

  cient 

depth to ensure that all plumbing is 
below the frost line. If this is not feasible, 
remove the check valve and size the 
basin to accommodate the additional 
backfl ow volume.

Pumps are most commonly installed 
in simplex or duplex stations or basins 
with a slide rail system, which allows 
the pump(s) to be installed or removed 
without requiring personnel to enter 
the station, or resting on the basin fl oor. 

Discharge Piping

Discharge piping should be as short 
as possible and sized no smaller than 
the pump discharge.  

Do not reduce 

the discharge pipe size below that 
which is provided on the pump.

  Both 

a check valve and a shut-off  valve are 
recommended for each pump.  The 
check valve is used to prevent backflow 
into the sump.  The shut-off  valve is 
used to manually stop system flow 
during pump servicing.

Liquid Level Controls

The level control(s) should be mounted 
on the discharge piping, a cable rack 
or fl oat pole.  The level control should 
have adequate clearance so it cannot 
hang up in it’s swing and that the pump 
is completely submerged when the 
level control is in the “Off ” mode.  By 
adjusting the cord tether the control 
level can be changed.  One cycle of 
operation should be observed, so that any 
potential problems can be corrected.

It is recommended that the level control 
fl oat should be set to insure that the liquid 
in the sump never drops below the top of 
the motor housing or a minimum level of 
10 inches above the basin fl oor.

Electrical Connections

Power cable:

The power cable mounted to the pump 
must not be modified in any way except 
for shortening to a specific application.
Any splice between the pump and the
control panel must be made in 
accordance with the electric codes. It is
recommended that a junction box, if used, 
be mounted outside the sump or be of 
at a minimum Nema 4 construction if 
located within the wet well. 

DO NOT USE 

THE POWER CABLE TO LIFT PUMP. 

Always rely upon a Certifi ed Electrician 
for installation.

Overload Protection:
Single Phase

 - The stator in-winding

overload protector used is referred to 
as an inherent overheating protector 
and operates on the combined eff ect 
of temperature and current. This means 
that the overload protector will trip out 
and shut the pump off  if the windings 
become too hot, or the load current 
passing through them becomes too high. 

Figure 1

Recommended
Submergence Level

Minimum
Submergence Level

10”

Bottom of Feet

Receiving & Installation

Содержание CPSE

Страница 1: ...and OH 44805 Phone 419 281 4500 toll free 800 659 4491 fax 419 616 1100 Series CPSE1524 CPSE1594 CPSE1544 CPSE2024 CPSE2094 CPSE2044 CPSE3024 CPSE3094 CPSE3044 1750 RPM 60 Hz www championpump com No C...

Страница 2: ...king on pumps Ground Fault Circuit Interrupter GFCI to be used with plug in type power cord Do not us these pumps in water over 104 F Consult Power Flo for high temperature pump models The Uniform Plu...

Страница 3: ...ance 5 at terminal block Rated operation at 10 voltage at motor DISCHARGE 3 NPT Female Vertical bolt on flange LIQUID TEMPERATURE 104 F Continuous MOTOR HOUSING Cast Iron Class 30 VOLUTE Cast Iron Cla...

Страница 4: ...Champion Pump Company Inc P O Box 528 Ashland OH 44805 Phone 419 281 4500 toll free 800 659 4491 fax 419 616 1100 For Models CPSE1594 1544 2094 2044 For Models CPSE1524 2024 3094 3034 3044 Dimensions...

Страница 5: ...5 Champion Pump Company Inc P O Box 528 Ashland OH 44805 Phone 419 281 4500 toll free 800 659 4491 fax 419 616 1100 Performance...

Страница 6: ...ns with a slide rail system which allows the pump s to be installed or removed without requiring personnel to enter the station or resting on the basin floor Discharge Piping Discharge piping should b...

Страница 7: ...be recorded 5 Pump DownTest Be sure pump has been properly wired lowered into the basin sump or lift station check the system by filling with liquid and allowing the pump to operate through its pumpin...

Страница 8: ...us hydraulic pressure which can destroy the pump and create a hazard Overfilling oil voids warranty Cooling Oil Recommended Supplier Grade BP Enerpar SE100 Conoco Pale Paraffin 22 Mobile D T E Oil Lig...

Страница 9: ...Make sure spring is seated in retaining ring and spring is lined up on rotating member and not cocked or resting on bellows tail Bearing Motor 6 Slide rotor shaft with bearing 8 and seal parts 6 into...

Страница 10: ...friction ring 24 grommet 25 one friction ring 24 and gland nut 23 into motor housing 4 or conduit box cable assembly 33 and torque gland nut 23 to 15 ft lbs 19 on models CPSE1594 2094 2044 refill wit...

Страница 11: ...44805 Phone 419 281 4500 toll free 800 659 4491 fax 419 616 1100 For Repair Part Please supply Model Number and MFG Date as shown on Name Plate and Part Description and Part Number as shown on Parts...

Страница 12: ...44805 Phone 419 281 4500 toll free 800 659 4491 fax 419 616 1100 Repair Parts For Repair Part Please supply Model Number and MFG Date as shown on Name Plate and Part Description and Part Number as sh...

Страница 13: ...d Cap Screw 1 4 20 x 1 Lg Stainless 18 1 6 O ring PF92010083 19 1 6 O ring PF92010082 20 1 Pipe Plug 3 4 NPT 21 1 Eye Bolt 1 2 13 x 1 Lg Power Cable Assy Includes 22 23 24 25 26 PF053165 22 1 Power Ca...

Страница 14: ...4805 Phone 419 281 4500 toll free 800 659 4491 fax 419 616 1100 Repair Parts For Repair Part Please supply Model Number and MFG Date as shown on Name Plate and Part Description and Part Number as show...

Страница 15: ...44805 Phone 419 281 4500 toll free 800 659 4491 fax 419 616 1100 Parts List For Repair Part Please supply Model Number and MFG Date as shown on Name Plate and Part Description and Part Number as shown...

Страница 16: ...Stainless 10 4 Hex Nut 3 8 16 Stainless 11 1 6 Gasket PF92010125 12 1 6 Impeller Nut 5 8 18 Stainless PF91010442 13 1 6 Washer 5 8 Stainless PF91010063 14 1 6 Shaft Key PF91010111 15 1 6 Washer Impell...

Страница 17: ...shing PF31190021 30 1 6 Washer Bushing PF91010054 31 2 Screw 1 2 13 x 1 75 Lg Stainless 32 1 Lockwasher 1 2 Stainless 33 1 Conduit Box PF03100010 34 1 Capacitor 45 MFD 370V CPSE1524 2024 3024 PF310300...

Страница 18: ...hole 10 Check rotation If power supply is three phase reverse any two of three power supply leads to ensure proper impeller rotation 11 Repair fixtures as required to eliminate leakage 12 Check pump...

Страница 19: ...19 Champion Pump Company Inc P O Box 528 Ashland OH 44805 Phone 419 281 4500 toll free 800 659 4491 fax 419 616 1100 Notes...

Страница 20: ...application neglect alteration accident or act of God that has not been installed operated or maintained in accordance with Manufacturer s installation instructions that has been exposed to outside su...

Страница 21: ...acket Good________Fair________________Poor_____________ Was equipment stored ___________How long _________________________________ Liquid being pumped__________________________________________________...

Отзывы: