O P T I O N A L   C O N T R O L   S E T T I N G S

1

          

         

3  

         

4

    

 

ON 

(FIRE DOOR MODE TYPE II)

 

 

OFF 

(FIRE DOOR MODE TYPE I)

 

 

1

          

         

3  

         

4

ON   

(N.C. ALARM)

 

 

OFF   

(N.O. ALARM)

 

 

Terminal
Block (J2)

Terminal
Block (J1)

Heat Sink

DIP Switch (S1)

OPTIONAL CONTROL SETTINGS

NOTE:

All functions are independent of each other and do not

require other control settings to be set at any certain
configuration. For dip switch location refer to illustration below.
All switches are factory preset to the “OFF” position.

SI-1

ALARM DELAY TO CLOSE

Alarm Delay to Close is the time between when the
operator first receives an active alarm signal and the door
starts to close (in seconds).

SI-4

INFRARED EYES STATE

The operator will support LiftMaster Infrared Safety Photo
Eyes when enabled, and ignore IR inputs when disabled.

INSTALLER CONTROL SETTINGS

SI-2

MODE

The factory default for the operator is standard Fire Door
Mode Type I (OFF). Setting S1-2 to the (ON) position
selects the Fire Door Mode Type II. When Fire Door Mode
Type I is selected, the control station is in the standard B2
wiring, momentary contact to open, close and stop. When
Fire Door Mode Type II is selected, the control station is in
revised C2 wiring, momentary contact to open and stop,
constant pressure to close with no open override. In
addition, when Fire Door Mode Type II is selected, the
door will Gravity Close (governed descent) on alarm.

SI-3

ALARM STATE

The operator can accept either a normally open or
normally closed dry contact alarm input. DO NOT INDUCE
VOLTAGE!

1

          

         

3  

         

4

ON   

(0 SECOND DELAY)

 

 

OFF 

(10 SECOND DELAY)

 

 

1

          

         

3  

         

4

ON   

(IR'S ENABLED)

 

 

OFF  

 (IR'S DISABLED) 

 

NOTICE:

This equipment has been tested and found to comply with
the limits for a Class A digital device, pursuant to Part 15 of
the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a
residential area is likely to cause harmful interference, in
which case the user will be required to correct the
interference at his own expense.

Содержание LiftMaster PROFESSIONAL K79-13493-2

Страница 1: ...to the electrical box with the screw removed in step 4 NOTE For any additional help refer to assembly drawing on page 2 HOW TO ORDER REPAIR PARTS OUR LARGE SERVICE ORGANIZATION SPANS AMERICA Installa...

Страница 2: ...2 LO G I C B O A R D R E P L A C E M E N T A S S E M B LY Existing Screws New Logic Board Existing Nylon Nuts Existing Standoff...

Страница 3: ...lack wire that runs from the battery negative terminal to J14 MOTOR NOTE Steps 1 and 2 affect motor run direction 1 Reconnect the original grey wire from the motor to pin where it was removed from eit...

Страница 4: ...DARY PRIMARY INTERNAL THERMAL SENSOR ELECTRONIC FUSELINK ALARM INPUT 2 FACTORY JUMPER SUPPLIED YE RD BL WH BK RD BK RD WH WH BL YE BK BK YE GY PU BL BK BK WH BK BR BR BK BR BR RD BK BK BK RD WH BK RD...

Страница 5: ...ICATORS 1 Reconnect the original white black wire to J2 terminal block 1 2 Reconnect the original white wire to J2 terminal block 2 3 Reconnect the low battery indicator original white wire to J2 term...

Страница 6: ...CATOR REVERSING EDGE 230 460 V 3PH POWER IN GND ALARM INPUT 1 DRY CONTACT ONLY DO NOT INDUCE VOLTAGE OPEN CLOSE STOP KEY TEST COM NO SECONDARY PRIMARY INTERNAL THERMAL SENSOR ELECTRONIC FUSELINK ALARM...

Страница 7: ...standard B2 wiring momentary contact to open close and stop When Fire Door Mode Type II is selected the control station is in revised C2 wiring momentary contact to open and stop constant pressure to...

Страница 8: ...UTTON STATION AND SYSTEM TEST STROBE LIGHT WIRING ALARM SYSTEM NO OR NC CONTACTS 5 6 Sensing Device 11 12 NC Contacts 11 12 NO Contacts J2 J2 J2 J2 J2 Must set DIP switch 3 S1 3 to ON Must set DIP swi...

Отзывы: