STANDBY POWER UNIT (SPU) DIAGNOSTICS

GREEN LED:
All systems are normal.
•  A solid LED light indicates the batteries are fully charged.
•  A flashing LED indicates the batteries are being charged.
NOTE: Batteries do not have to be fully charged to operate the 

motor unit.

YELLOW LED:
The motor unit has lost power and is operating off of the SPU.
•  A solid LED with beep, sounding approximately every 2 seconds, 

indicates the motor unit is activating the door and is operating 

off of the SPU.

•  A flashing LED with beep, sounding every 30 seconds, indicates 

batteries are low.

•  Once the power is restored, the SPU will recharge. This is 

indicated by a flashing green LED.

RED LED:
An error has been detected and the SPU will automatically shut 

off. The SPU will attempt to restart by reconnecting to the 

batteries. If the error is still present it will shut itself off again. 

This process will repeat every 5 minutes or until the error has 

been resolved. This is used to prevent further draining of the 

batteries.
•  If a red LED remains on when the power is restored, and is 

accompanied by a beep sounding every 30 seconds, please call 

for service.

 

©2009, The Chamberlain Group, Inc.

114A2745F 

All Rights Reserved

OPERATION
1. Test the installed SPU with the motor unit.
To test the SPU, disconnect the motor unit power cord from the 

electrical outlet.
•  A solid yellow LED indicates the SPU is operating on battery 

power.

•  A flashing yellow LED with beep indicates the SPU is operating 

on battery power and that the battery charge is low.

•  To test whether the SPU is functioning properly, open and close 

the garage door.

•  Re-connect the motor unit power cord back into the electrical 

outlet.

•  Verify that the green LED is flashing on the SPU (indicates that 

the SPU is now charging).

• Test completed.

2. Charge the battery.
•  Allow the batteries 24 to 48 hours to fully charge before using 

the SPU system.

A fully charged SPU supplies 24 Vdc to the motor unit for one to 

two days of normal operation during an electrical power outage. If 

the battery voltage drops too low, the batteries will disconnect 

and the motor unit will no longer operate under battery power.
After the electrical power has been restored, the batteries will 

recharge within 48 hours. Under normal usage batteries will last 

3 to 5 years.
To obtain maximum battery life and prevent damage, also 

disconnect the standby power if you unplug the motor unit while 

on vacation or any other extended period of time.

NOTE: Door operation may be limited until batteries are fully 

charged. The motor unit’s lights will not turn on during SPU 

mode.

To reduce the risk of FIRE or INJURY to persons use only 

Chamberlain part #41B591 for replacement batteries.

Replacement Parts

12V Rechargeable Batteries (2) . . . . . . . . . . . . . . . . . . . . . 41B591
Power Supply Board  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41A5726
Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72A35

FOR SERVICE, DIAL OUR TOLL-FREE NUMBER:

1-800-528-9131

(Green LED)

(Yellow LED)

(Red LED)