background image

8

13

CONTROL WIRING

THREE PHASE FIELD WIRING

Standard C2 or B2 Wiring
Standard operators are shipped from the factory with
jumper set for C2 wiring, which requires constant
pressure on button to close the door.  If momentary
contact on close direction is desired (B2 wiring) you
must include an entrapment protection device.  See
close control jumper setting below.

Constant pressure on close (C2 wiring)
Red jumper wire was placed on terminal #2 in 
electrical enclosure.  The operator will require 
constant pressure on close control in order to keep
door moving in the close direction.

Momentary contact on close (B2 wiring)
Move red jumper wire from terminal #2 to terminal 
#3. The operator will require only momentary 
contact to close the door.

LOCATING THE CONTROL STATION
All operators are supplied with some type of control station. Gener ally a three button station
(OPEN/CLOSE/STOP) is provided. A two-position key switch or control station (OPEN/CLOSE) may be added or
substituted when requested at the time of  order. Mount the control station near the door.

WARNING

CAUTION

WARNING

WARNING

INSTALL THE CONTROL STATION WHERE THE
DOOR IS VISIBLE, BUT AWAY FROM THE DOOR AND
ITS HARDWARE. IF CONTROL STATION CANNOT BE
INSTALLED WHERE DOOR IS VISIBLE, OR IF ANY
DEVICE OTHER THAN THE CONTROL STATION IS
USED TO ACTIVATE THE DOOR, 

A REVERSING EDGE

MUST BE INSTALLED ON THE BOTTOM OF THE
DOOR. FAILURE TO INSTALL A REVERSING EDGE
UNDER THESE CIRCUMSTANCES MAY RESULT IN
SERIOUS INJURY OR DEATH TO PERSONS
TRAPPED BENEATH THE DOOR.

W A R N I N G

TO PREVENT ENTRAPMENT

DO NOT START DOOR  DOWNWARD

UNLESS DOORWAY IS CLEAR

OPEN

CLOSE

CLOSE

STOP

Control Station

WARNING Notice

Push

Buttons

IMPORTANT: Mount WARNING NOTICE beside or
below the push button station.

MOUNT WARNING NOTICE

DETERMINE WIRING TYPE
Refer to the wiring diagram located on the inside cover the electrical box to determine the type of control wiring. 

SPECIAL CONTROL WIRING

If your operator was shipped from the factory with
non-standard control wir ing or with optional
accessories that require addition instructions, refer to
the wiring diagram(s) indicated in the special control
wiring data box.  When a replacement wiring diagram
is present, wiring diagrams in this manual will not
apply.  Refer only to the replacement wiring diagram
for all connections.

IMPORTANT NOTE:  If your wiring diagram is
missing, or you are unsure of the wiring type for
your operator, contact the customer service
department @ 1-800-528-2806.

1942

Содержание GH 5HP

Страница 1: ...L INTERLOCK 3 10 4 5 4 5 Remove Jumper When Interlock is Used ONE 2 OR MORE STANDARD 1 2 3 4 Stop Close Open IMPORTANT NOTES 1 The 3 Button Control Station provided must be connected for operation 2 If a STOP button is not used a jumper must be placed between termianls 3 and 4 3 Auxiliary control equipment may be any normally open two wire device such as pullswitch single button loop detector card...

Страница 2: ...al door operation ELECTRICAL TRANSFORMER 3PH 208 230 480 VAC 24VAC OR 3PH 575VAC 24VAC CONTROL STATION NEMA 1 three button station OPEN CLOSE STOP WIRING TYPE Standard C2 Wiring Standard operators are shipped from the factory set for C2 wiring which requires momentary contact to open constant pressure to close stop on release Optional B2 Wiring Which requires momentary contact to open close and st...

Страница 3: ...uide The GH operator may be mounted on either the right standard or left side of door and in either a vertical standard or horizontal mounting position Refer to the steps below if you require the hand chain and or disconnect chain to be on the opposite side of the operator Or if the operator is being mounted in a horizontal position Hand Chain Right Left Conversion Remove the outer snap ring secur...

Страница 4: ...ter link 4 Raise operator to approximate mounting position using suitable lifting apparatus and position chain over operator sprocket 5 Raise or lower operator until the chain is taut not tight Make sure the operator output shaft is parallel to door shaft and sprockets are aligned When in position secure the operator to wall or mounting bracket 6 Align sprockets and secure see Figure 5 FIGURE 4 FI...

Страница 5: ...Actuator Radial Ball Bearing Spacer Shim Washer Shoulder Bolt 3 8 Body x 5 8 Long 1 1 2 2 6 4 09 17987 1 10 17983 12 18052 31 18054 80 10022 82 SH31 10S K75 18324 HAND CHAIN SHAFT KIT ITEM PART DESCRIPTION QTY H1 H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 Bevel Gear Bevel Gear Shaft Flanged Bearing Compression Spring Spacer Shim Washer 050 Thk Shim Washer 3 8 I D x 010 Thk Dowel Pin 3 16 Dia x 1 25 Long ...

Страница 6: ...ORIES OPTIONAL IT IS STRONGLY RECOMMENDED THAT A SENSING EDGE OR OTHER ENTRAPMENT PROTECTION DEVICE BE USED IN CONJUNCTION WITH THIS OPERATOR If other problems persist call our toll free number for assistance 1 800 528 2806 1 To adjust limit nuts depress retaining plate to allow nut to spin freely After adjustment release plate and ensure it seats fully in slots of both nuts 2 To increase door tra...

Страница 7: ...ange Bearing Bearing Seal 3 8 I D Limit Nut Neoprene Gasket Sprocket 48B18 x 3 8 Bore Washer Shim Screw 8 32 Nut 8 32 Serrated Flange Roll Pin 1 8 DIA x 1 Long E Ring 3 8 Qty 1 2 2 2 2 1 32 4 4 1 2 P N 11 10480 12 10481 12 10483 13 10024 13 10516 15 48B18AXX 80 10026 82 PX08 10T 84 FN 08 86 RP04 100 87 E 038 COMPLETE ELECTRICAL BOX KITS Item 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Description...

Страница 8: ...LE BUT AWAY FROM THE DOOR AND ITS HARDWARE IF CONTROL STATION CANNOT BE INSTALLED WHERE DOOR IS VISIBLE OR IF ANY DEVICE OTHER THAN THE CONTROL STATION IS USED TO ACTIVATE THE DOOR A REVERSING EDGE MUST BE INSTALLED ON THE BOTTOM OF THE DOOR FAILURE TO INSTALL A REVERSING EDGE UNDER THESE CIRCUMSTANCES MAY RESULT IN SERIOUS INJURY OR DEATH TO PERSONS TRAPPED BENEATH THE DOOR W A R N I N G TO PREVE...

Страница 9: ...allel with the OPEN button More than one device may be connected in this manner Use 16 gauge wire or larger for all controls DO NOT USE THE CONTROL CIRCUIT TRANSFORMER 24VAC IN THE OPERATOR TO POWER ANY ACCESS CONTROL EQUIPMENT OTHER THAN A STANDARD TYPE RADIO RECEIVER External Interlock Switch The operator has a terminal connection for an external interlock switch This switch must be a normally c...

Страница 10: ... the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to ...

Страница 11: ... the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to ...

Страница 12: ...allel with the OPEN button More than one device may be connected in this manner Use 16 gauge wire or larger for all controls DO NOT USE THE CONTROL CIRCUIT TRANSFORMER 24VAC IN THE OPERATOR TO POWER ANY ACCESS CONTROL EQUIPMENT OTHER THAN A STANDARD TYPE RADIO RECEIVER External Interlock Switch The operator has a terminal connection for an external interlock switch This switch must be a normally c...

Страница 13: ...LE BUT AWAY FROM THE DOOR AND ITS HARDWARE IF CONTROL STATION CANNOT BE INSTALLED WHERE DOOR IS VISIBLE OR IF ANY DEVICE OTHER THAN THE CONTROL STATION IS USED TO ACTIVATE THE DOOR A REVERSING EDGE MUST BE INSTALLED ON THE BOTTOM OF THE DOOR FAILURE TO INSTALL A REVERSING EDGE UNDER THESE CIRCUMSTANCES MAY RESULT IN SERIOUS INJURY OR DEATH TO PERSONS TRAPPED BENEATH THE DOOR W A R N I N G TO PREVE...

Страница 14: ...ange Bearing Bearing Seal 3 8 I D Limit Nut Neoprene Gasket Sprocket 48B18 x 3 8 Bore Washer Shim Screw 8 32 Nut 8 32 Serrated Flange Roll Pin 1 8 DIA x 1 Long E Ring 3 8 Qty 1 2 2 2 2 1 32 4 4 1 2 P N 11 10480 12 10481 12 10483 13 10024 13 10516 15 48B18AXX 80 10026 82 PX08 10T 84 FN 08 86 RP04 100 87 E 038 COMPLETE ELECTRICAL BOX KITS Item 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Description...

Страница 15: ...ORIES OPTIONAL IT IS STRONGLY RECOMMENDED THAT A SENSING EDGE OR OTHER ENTRAPMENT PROTECTION DEVICE BE USED IN CONJUNCTION WITH THIS OPERATOR If other problems persist call our toll free number for assistance 1 800 528 2806 1 To adjust limit nuts depress retaining plate to allow nut to spin freely After adjustment release plate and ensure it seats fully in slots of both nuts 2 To increase door tra...

Страница 16: ...Actuator Radial Ball Bearing Spacer Shim Washer Shoulder Bolt 3 8 Body x 5 8 Long 1 1 2 2 6 4 09 17987 1 10 17983 12 18052 31 18054 80 10022 82 SH31 10S K75 18324 HAND CHAIN SHAFT KIT ITEM PART DESCRIPTION QTY H1 H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 Bevel Gear Bevel Gear Shaft Flanged Bearing Compression Spring Spacer Shim Washer 050 Thk Shim Washer 3 8 I D x 010 Thk Dowel Pin 3 16 Dia x 1 25 Long ...

Страница 17: ...ter link 4 Raise operator to approximate mounting position using suitable lifting apparatus and position chain over operator sprocket 5 Raise or lower operator until the chain is taut not tight Make sure the operator output shaft is parallel to door shaft and sprockets are aligned When in position secure the operator to wall or mounting bracket 6 Align sprockets and secure see Figure 5 FIGURE 4 FI...

Страница 18: ...uide The GH operator may be mounted on either the right standard or left side of door and in either a vertical standard or horizontal mounting position Refer to the steps below if you require the hand chain and or disconnect chain to be on the opposite side of the operator Or if the operator is being mounted in a horizontal position Hand Chain Right Left Conversion Remove the outer snap ring secur...

Страница 19: ...al door operation ELECTRICAL TRANSFORMER 3PH 208 230 480 VAC 24VAC OR 3PH 575VAC 24VAC CONTROL STATION NEMA 1 three button station OPEN CLOSE STOP WIRING TYPE Standard C2 Wiring Standard operators are shipped from the factory set for C2 wiring which requires momentary contact to open constant pressure to close stop on release Optional B2 Wiring Which requires momentary contact to open close and st...

Страница 20: ...L INTERLOCK 3 10 4 5 4 5 Remove Jumper When Interlock is Used ONE 2 OR MORE STANDARD 1 2 3 4 Stop Close Open IMPORTANT NOTES 1 The 3 Button Control Station provided must be connected for operation 2 If a STOP button is not used a jumper must be placed between termianls 3 and 4 3 Auxiliary control equipment may be any normally open two wire device such as pullswitch single button loop detector card...

Отзывы: