Rev B
Doc 6001343 (01-20299)
17 of 40
7. Alternate
Action
1.
If you want the CYCLE input (Entry system) or RADIO input (Transmitter) to both open and close
the gate, disable RECLOSE TIMER and ATG.
2.
Activate the CYCLE command, wait until the gate is fully open, the activate the CYCLE command
again. The gate should close, verifying the Alternate Action operation.
Note:
If you select Alternate Action, you cannot enable the ATG and RECLOSE TIMER in procedures
8 and 9 that follow.
8. Reclose
Timer
1.
If you want a fully open gate to automatically close after a period of time, enable the RECLOSE
TIMER.
2.
If you don’t want the gate to close automatically, disable the RECLOSE TIMER.
3.
Activate any entry command (except Manual OPEN) to open the gate and verify the Reclose Timer
operation.
Note:
Reclose Timer is not functional when the Manual OPEN command is used.
9.
Inside Interrupt Loop and ATG (when exiting)
1.
If you want the gate to stop when a vehicle drives onto the Interrupt Loop and to restart when the
vehicle drives off the Interrupt Loop, set Gate Type = Swing and disable the ATG.
2.
If you want the gate to stop when a vehicle drives onto the Interrupt Loop and to close when the
vehicle drives off the Interrupt Loop, set Gate Type = Swing and enable the ATG.
3.
If you want a closing gate to open when a vehicle drive on the Interrupt Loop, set Gate Type =
Barrier and disable the ATG.
4.
If you want a closing gate to stop when a vehicle drives on the Interrupt Loop and an opening or
closing gate to close when the vehicle drives off the Interrupt Loop, set Gate Type = Barrier and
enable the ATG.
5.
Activate the CYCLE command, drive over the Interrupt Loop, and verify its operation.
10. Interrupt
Bar
While the gate is opening, push on the Interrupt Bar. The gate should stop or reverse.
11. Maglock
Verify that the maglock activates when the gate is fully closed.
12. Automatic Gate Closure
1.
To automatically close a fully open gate after power is restored, enable the RECLOSE TIMER.
2.
Open the gate fully, then cycle the unit power switch to verify Automatic Gate Closure operation.
13. Power Fail Option
1.
Verify that switch S2 (Power Fail Open Direction switch) is set to the desired position (Figure 5).