Rev B
Doc 6001343 (01-20299)
15 of 40
NOTES
1.
Disconnecting the STOP terminal from the COMMON terminal stops the gate and prevents all
commands from having any effect. Manual Open does not activate the Reclose Timer.
2.
If gate(s) are used for bi-directional traffic, the Exit Loop should be a directional loop detector.
3.
Inside and Outside Interrupt Loops:
♦
For maximum safety, Inside and Outside Interrupt loops require separate loop detectors.
♦
If only one loop detector is used, the Outside loop must also be connected to the Inside loop
detector.
♦
♦
♦
♦
Master/Slave systems only:
To enhance safety in Bi-Parting and Bi-Parting Latch
Master/Slave systems, the Interrupt loops, Shadow loops and Interrupt Bar switches may be
connected to both gates. If this is done, when connecting the two control boards,
do not
interchange input and common terminals
. If terminals are interchanged, inputs will not be
detected and controller boards may be damaged.
4.
If AC power to the controller board is cut off, the battery will retain the correct time and date.
M. BASIC GATE OPERATOR PROGRAMMING
Even if you plan to program the gate operator by telephone, you may want to enter some immediate
instructions during installation. The following list of instructions will help you set basic controls so the
gate will operate properly until you have time for full programming, either directly or by telephone. For
complete programming instructions, refer to the enclosed manual SL 1000, SW 2000, BG 3000 and BG
3100-X1 Programming (-73 Bd), Doc. No. 6001312.
To access
programming mode: enter
✱✱✱
000000 (3 asterisks, 6 zeroes)
To program
a command:
a)
enter step number,
b)
enter required data,
c)
enter # (pound sign)
To exit
programming mode: enter 00# (2 zeroes, 1 pound sign)
Step
Purpose
# of Digits Default
Acceptable Input
01
Gate Type
1
1
0 = Slide, 1 = Swing, 2 = Barrier
02
Operator Type
1
0
0 = Single, 1 = Master, 2 = Slave
03
Pair Type
1
0
0= Bipart, 1=Latch
✔
, 2=Trap, 3=Tandem
04
Warn When
1
0
0 = Moving, 1 = Closing, 2 = Not Closed, 3 =
Alerts Only
05
Warn Time Before Moving
2
0
0 – 30 Seconds
06
Anti-Tailgate Enable (ATG)
1
0
0 = Disabled, 1 = Enabled
07 Latch
✔
Delay Time
3
6
0 – 250 Seconds (.4 sec. Increments)
08
Reclose Time (RT)
Up to 3
30
0 – 250 Seconds (0 = Disabled)
09
Maximum Retry Count
1
0
0 – 2 (0 = Do not retry)
10
Retry Pause Time
Up to 2
30
30-99 Seconds
11
Reverse Sense Backup Inches
Up to 3
3
0 – 499 Inches See note below.
✱
13
Safety Bar Backup If Closing
Up to 3
12
0 – 499 Inches See note below.
✱
14
Safety Bar Backup If Opening
Up to 3
0
0 – 499 Inches See note below.
✱
15
Return to Factory Set Defaults
6
N/A
101010 (partial), 191919 (full)
✱
IMPORTANT NOTE: BARRIER GATE BACKUP DISTANCES
Barrier gates move in
degrees
per second, so it is the length of the gate that determines how far the
edge of the gate moves each second. As a result, entering backup distances for barrier gates is different
than for slide gates. Use the following table to enter barrier gate backup distances: