background image

IOM

 

– STERLING III - ZONE 2 LED (ATEX, IECEx, Ex ec)   

 

I-ST3N-01.doc 

 

 

             Issue 8   

                December 2018  

 

 

 

0.0  Specification

 

 

 

Type Of Protection   

Ex ec,    (non-sparking).  Ex  tc,  

Protection Standards 

EN/IEC 60079-0, EN/IEC 60079-7, EN/IEC 60079-31 

Area Classification 

Zone 2 areas to EN/IEC 60079-10-1, 
Zone 22 areas to EN/IEC 60079-10-2.  

Installation 

EN/IEC 60079-14 

Certificate 

 

Type Examination Certificate CML 16ATEX 4101X 
IEC Ex Type Certificate No. IECEx CML 16.0044X 

Equipment Coding 

Ex  ec lIC T4 Gc   
Ex tc IIIC T76°C Dc IP6X

 (ambient values see tables below for details)                                

ATEX Coding 

  II 3GD    

Ingress Protection 

IP65 to EN/IEC 60529 

CE Mark 
 

The  CE  marking  of  this  product  applies  to  "The  Electrical  Equipment  (Safety)  Regulations 
2006",  "The  Electromagnetic  Compatibility  Regulations  2004",  the  “Waste  Electrical  and 
Electronic Equipment Regulations 2006” and the "Equipment and Protective Systems intended 
for use in Explosive Atmospheres Regulations 1996". [This legislation is the equivalent in UK 
law of EU directives 2014/35/EU, 2014/30/EU, 2012/19/EU and 2014/34/EU respectively]. 
 
The  Equipment  is  declared  to  meet  the  provisions  of  the  ATEX  directive  (2014/34/EU)  by 
reason  of  the  EU  Type  Examination  and  compliance  with  the  Essential  Health  and  Safety 
Requirements.  
M Poutney    Technical Manager 

 

 

 
1.0  Introduction 

– Zone 2 & Zone 22, Ex ec, Ex tc LED Luminaire 

General

 

The type of protection is Ex ec and Ex tc. The Zone 2 & Zone 22 series LED luminaires are surface mounted or 
suspended, utilising the two holes on the base of the body. They are mainly used in harsh environments, and are 
constructed using a corrosion resistant glass reinforced polyester body, attached to an injection moulded 
polycarbonate diffuser by stainless steel toggle clips. 

The control gear and LED’s are mounted on a removable 

tray that for maintenance purposes has hanging straps. 

Note: The ratings are listed in TABLES A & B. 
 
1.1  Application

 

The luminaire is designed to be safe in normal operation.  The luminaire should not be used where there are 
environmental, vibration or shock conditions above the normal for fixed installations.  The gaskets should not be 
exposed to hydrocarbons in liquid or high concentration vapour states.   
The luminaire is suitable for applications where Category 3 apparatus can be used. The type examination does 
not address suitability for portable applications.   
 

2.0   Storage

 

Luminaires are to be stored in cool dry conditions preventing ingress of moisture and condensation.  
 
 

SPECIAL CONDITIONS FOR SAFE USE 

 

The Luminaire shall only be installed where there is a low risk of mechanical damage. 

 

When refitting the diffuser, the fixing clamps are to be re-secured with the original or replacement self 

tapping screws. 

 

Fasteners through the enclosure used for mounting purpose shall be fitted with appropriate sealing 

washers to maintain the ingress protection rating of the enclosure. 

 

Содержание Sterling III

Страница 1: ...ires Ex ec ATEX IECEx INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS GRP Standard body Important Please read these instructions carefully before installing or maintaining this equipment Good electrical practices should be followed at all times and this data should be used as a guide only Technical Drawing ...

Страница 2: ...neral The type of protection is Ex ec and Ex tc The Zone 2 Zone 22 series LED luminaires are surface mounted or suspended utilising the two holes on the base of the body They are mainly used in harsh environments and are constructed using a corrosion resistant glass reinforced polyester body attached to an injection moulded polycarbonate diffuser by stainless steel toggle clips The control gear an...

Страница 3: ...eam of dry air steam etc which could generate a propagating brush static discharge 3 1 1 Use in Combustible Dust Atmospheres Where the equipment is used in ignitable dust atmospheres reference must be made to the selection and installation standards in order that the equipment is used correctly In particular this applies to the de rating of surface temperature for use where dust clouds may be pres...

Страница 4: ...an adequate seal is made to maintain the IP rating of the enclosure Sealing Washers are provided 3 6 Cabling and Cable Glands 3 6 1 Cables The GRP models have facility for through wiring but do not have a facility for looping The temperature conditions of the supply cable entry point are such that 70ºC ordinary PVC cable can be used 300 500V cable ratings are adequate and no special internal const...

Страница 5: ...thly intervals and more frequently if conditions are severe The time between lamp changes could be very infrequent and this is too long a period without inspection 3 8 1 Routine Examination The equipment must be de energised before opening Individual organisations will have their own procedures What follows are guidelines based on EN IEC 60079 17 and on our experience 1 Ensure LED s are lit when e...

Страница 6: ...on 5 0 Fuse Ratings With the availability of MCB s with a wide range of characteristics the individual engineer can make a better judgement of what is required Use MCB s suitable for inrush currents to reduce ratings Where MCB s are used the type with the higher short time tripping current ratio used for motor starting and lighting should be specified The inrush current can be calculated where cir...

Страница 7: ... Max Surface Temperature Dust 3365 Lumen 2ft Twin 120 277Vac 127 300Vdc 26W 20 C Ta 55 C T4 76 C 6218 Lumen 4Ft Twin 120 277Vac 127 300Vdc 60W 20 C Ta 50 C T4 76 C 8953 Lumen 4Ft Twin 120 277Vac 127 300Vdc 96W 20 C Ta 45 C T4 76 C Typical Standard LED Wiring Diagram Note For other Wiring Diagrams please contact the manufacturer Table B Series Circuit No Off LED Strips Gear Type Lumen Nominal Circu...

Страница 8: ...ine Änderungen erfolgt sind die einen Einfluss auf den technischen Stand des Produkts haben Terms of the directive Standard Date Certified to Standards Date Declared to Prescription de la directive Standard date certifiée à Normes date Déclaré Bestimmungen der Richtlinie Standard Datum Zertifiziert nach Standards Datum erklärt 2014 34 EU Equipment and protective systems intended for use in potenti...

Страница 9: ...ch im Namen von Chalmit dass am Tag der Lieferung des Produkts der Produkte zusammen mit dieser Erklärung das Gerät die Geräte alle technischen und regulativen Anforderungen der oben aufgeführten Direktiven erfüllt Name and Date Mark Poutney 30 08 2018 Technical Manager Nom et Date Directeur technique Name und Datum Technischer Leiter Quality Assurance Notification by Baseefa Ltd Quality Managemen...

Отзывы: