SETTINGS

The boiler is supplied with all the adjusting knobs set to 

OFF 

(fig. 13) and the potentiometers turned fully clockwise. It is

possible to adjust these settings if required.

In that case, it is necessary to open the electronic control unit.

Switch off the boiler

, remove the casing and open the unit by pressing the 2 tabs 

P

(fig. 10). The adjusting knobs are on the

electronic circuit board behind blanking cover 

E

(fig. 11).

A1 

is used to set the Heating Anti-cycle Time (HAT) period to 30 seconds or 3 minutes

HAT: period during which restarting the burner is prohibited during a heating regulation phase

A2

allows the speed of the pump in heating mode to be selected (high speed or adaptive speed)

A3

is used to adjust the heating temperature setting to 40 °C whatever the position of the heating temperature adjustment

knob 

22 

(fig. 3)

A4

enables operation in modulating heating mode or all or nothing mode

B1 

allows the duration of post-circulation in heating mode to be adjusted

B2 

allows the domestic hot water time delay (TIC) to be adjusted

-

B3 

not used

B4

not used

N.B. 

After a power cut or a board reset, the HAT is cancelled for 3 minutes.

P1

: potentiometer for reducing the heating power 

(see table page 11)

P2

: potentiometer for adjusting the ignition power (12,7 kW - 24 FF / 16 kW - 30 FF)

P3

: not used

Once adjustments have been made, replace blanking cover 

E

, close the control unit cover and refit the casing.

8. Operating

PRESSURISATION 

(fig. 12)

Heating circuit and tank:

- open cold water tap 

34

- check that the heating flow 

31

, heating backflow 

35

and tank backflow 

32

taps (compy system plus) are open

- open filling tap 

36

- close the tap again when the needle of pressure gauge 

19

(fig. 3) is at the pressure specified in § 3

- drain the installation and re-establish the pressure 

Gas circuit

- open gas tap 

33

- flush the gas circuit

- check the whole gas line for leaks

Fig. 12

31

32

33

35

34

36

Содержание Mira system FF

Страница 1: ...C COMBINATION BOILER Heating only system Heating sanitary hot water together system plus Fanned Flue System Installation and Operating Manual GB TEMP MODE MAN AUTO THERMOREGULATION C O M PAT I B L E...

Страница 2: ...chnical specifications 20 Page 1 description 3 2 dimensions 4 3 water specifications 4 4 installation requirements 5 5 air intake and burnt gas outlet connections 6 6 fitting the boiler 8 7 electrical...

Страница 3: ...t thermistor 11 main heat exchanger outlet thermistor 12 electronic control unit 14 flue gas pressure control switch 15 ignitor 16 central heating pressure relief valve 19 heating circuit pressure gau...

Страница 4: ...s the difference in metres between the highest point of the installation and the expansion vessel axis The minimum cold filling pressure of the installation is 0 7 bar recommended pressure between 1 2...

Страница 5: ...for each type of building with public access hospitals shops etc Recommendation if the area is exposed to the risk of lightning isolated ins tallation at the end of an electricity line etc install a...

Страница 6: ...t have leaks 5 2 TWIN FLOW FLUE TYPE C12 C32 C42 C52 C82 xy There is also the possibility of using an exhaust gas duct with separate tubes by using an adaptor on the outlet header and by inserting the...

Страница 7: ...to be included in the calculation of developed length 3 The exhaust gas duct should jut above the roof by at least 0 5 m 4 The intake and exhaust gas ducts in C52 cannot be installed on opposite walls...

Страница 8: ...n hole 16 MUST be connected to a waste water pipe Fit the flue device according to the type of connection chosen referring to section 5 Cleaning the appliance Once the water has been connected it is e...

Страница 9: ...able is damaged it should be replaced by the manufacturer the after sales service or a person with a similar status in order to avoid potential danger Room thermostat connection When it leaves the fac...

Страница 10: ...enables operation in modulating heating mode or all or nothing mode B1 allows the duration of post circulation in heating mode to be adjusted B2 allows the domestic hot water time delay TIC to be adju...

Страница 11: ...sec Tempo D bistat Sanitaire 0 sec C lectic OFF ON Anticycle 30 s Fonctionnement TOUT OU RIEN Consigne chauffage 40 C Consigne chauffage variable de 35 85 C Post circulation 30 s Post circulation 3 m...

Страница 12: ...ive film on the casing offer the casing up fig 14 engage hooks N in notches R operation 1 fit the top of the panel in place close the panel mounting clamps fig 15 N B It is essential to refit the lock...

Страница 13: ...the pressure to the value shown in the table nominal output table Adjusting the minimum output disconnect a variable solenoid valve power supply cable fig 18 turn screw 4 using a 5 mm open ended spann...

Страница 14: ...xchanger outlet sensor open 12 Main exchanger outlet sensor short circuited 13 Main exchanger inlet sensor open 14 Main exchanger inlet sensor short circuited 15 External sensor open 16 External senso...

Страница 15: ...15 By pass valve assembly direction 12 Particular characteristics...

Страница 16: ...re adjustment knob 23 heating temperature and operating fault indicator 24 orange burner operating indicator light 25 reset push button reset and red locking indicator light Taps and valves fig 21 31...

Страница 17: ...emperature in the heating circuit according to seasonal requirements Indicator 23 displays the temperature Turn knob 22 towards Max in cold weather towards Min in mild weather Furthermore if your home...

Страница 18: ...o you by service providers for all boiler servicing Contact your gas fitter or our commercial services The manufacturer s warranty which covers manufacturing faults should not be confused with servici...

Страница 19: ...hapter 8 Room thermostat switched off Set up the room thermostat Red indicator alight Wait for a few minutes Press on reset button 25 fig 20 the red led turn off and the boiler attempts to re light If...

Страница 20: ...re 35 to 85 C 35 to 85 C Adjustable hot water temperature system plus 40 to 60 C 40 to 60 C Electric voltage 230 volt single phase 50 Hz 230 volt single phase 50 Hz Electrical power consumption 150 W...

Отзывы: