CGS Merlin CO2 TFT Скачать руководство пользователя страница 9

Installation, Operation & Maintenance                                                                                   Merlin CO2 TFT

 

 

 

Rev 1   05-21 

9  

   Traffic Light Indicator 

 

Your CO2-TFT displays both current CO

2

 and temperature levels in a traffic light style indication.

 

 

 

 

   Alarms & Configuration

 

 

NAT. - 

Natural Ventilation Mode (N) 

 

Green:   <1300ppm   <23 °C/ 73.4°F 
Yellow:  >1300ppm   >23 °C/ 73.4°F    
Red:       >1500ppm   >25 °C/ 77.0°F 
CO

Pre-alarm relay switch: 1300ppm 

CO

Alarm relay switch:        1500ppm 

0-10V Analogue Output Progression. 

Min output (1-5V) from 600ppm   23 °C/ 73.4°F 
Max  output (10V) from 1500ppm   27 °C/ 80.6°F 

Boost from: 400

 

- 1499ppm   0°C/32°F – 26.9°C/80.4°F 

 

 

 
MECH.
 - 

Mechanical Ventilation Mode (M) 

 

Green:   <800ppm   <23 °C/ 73.4°F 
Yellow:  >800ppm   >23 °C/ 73.4°F    
Red:       >1000ppm   >25 °C/ 77.0°F 
CO

Pre-alarm relay switch: 800ppm 

CO

Alarm relay switch:       1000ppm 

0-10V Analogue Output Progression. 

Min output (1-5V) from 600ppm   23 °C/ 73.4°F 
Max  output (10V) from 1000ppm   27 °C/ 80.6°F 

Boost from: 400 - 999ppm   0°C/32°F – 26.9°C/80.4°F 
 

 

 
KITCH.
 – 

Kitchen/Gas in Use Ventilation Mode (K) Default 

 

Green:   <1500ppm   <23 °C/ 73.4°F 
Yellow:  >1500ppm   >23 °C/ 73.4°F    
Red:       >2800ppm   >25 °C/ 77.0°F 
CO

Pre-alarm relay switch: 2800ppm 

CO

Alarm relay switch:       4500ppm 

0-10V Analogue Output Progression. 

Min output (1-5V) from 600ppm    23 °C/ 73.4°F 
Max  output (10V) from 2800ppm   27 °C/ 80.6°F 

Boost from: 400 - 2799ppm   0°C/32°F – 26.9°C/80.4°F 
Buzzer alarm/ Mute 
from: >2800ppm  

 

 

The alarm thresholds and configuration will depend on which ventilation mode your CO2 TFT has been set.  
There is no audio alarm for high temperatures. 

 

   Screen Saver Mode 

 
If the screen saver mode is switched on (see settings), the CO2 TFT monitor screen will switch off when both CO

2

 

and Temperature levels are at safe levels (green). No readings or messages will be visible during this time.

 

The 

screen will exit screen the saver mode when either the CO

2

 or Temperature changes status (yellow or red).

  

To view the screen during this mode, press the touch button, the screen will be visible for 10 seconds.

 

 

SAFE 

Safe CO

levels or temperature will 

be displayed GREEN. 

ATTENTION! 

Low CO

2

 levels or temperature will 

be displayed YELLOW. 

DANGER! 

High CO

2

 levels or temperature will 

be displayed RED. 

Содержание Merlin CO2 TFT

Страница 1: ...omatically switch between ventilation programs when gas is used Boost Mute and Wake Up feature Installation Operation Maintenance Please read this manual carefully and retain for future use The Merlin...

Страница 2: ...unting 4 Board Overview 4 Wiring your CO2 TFT 5 Configuration Settings 6 Configuration 6 Factory Set Condition 7 Operation 8 Initial Power Up Indicators 8 Traffic Light Indicator 9 Alarms Configuratio...

Страница 3: ...ed to replacement of the product with repaired product at the discretion of the manufacturer This warranty is void if the product has been damaged by accident unreasonable use neglect tampering or oth...

Страница 4: ...here possible monitors must be fixed in such a position as to allow natural air circulation These recommended heights may vary based on airflow and temperature conditions in addition to the proposed a...

Страница 5: ...n mode until the gas supply is turned off see Settings for configuration Recommended for teaching areas with gas appliances such as laboratories and food technology rooms CO2 ALARM Not a mains output...

Страница 6: ...hts setting red Press to save desired setting Configuration NAT Natural Ventilation Mode Recommended for buildings without mechanical ventilation Pre Alarm 1300ppm 23 C 73 4 F Alarm 1500ppm 25 C 77 0...

Страница 7: ...minutes Boost can be activated only if analogue outputs are set to either CO2 or DUAL mode only Select 1 2 3 4 5 6 7 8 9 10 minute s FAN ENABLE Fan switch is energised by CO2 ON 600ppm OFF 550ppm TEM...

Страница 8: ...ears when the touch button f is pressed The audible alarm buzzer must be set to on or every 10 minutes and can only occur when gas is in use or KITCH Ventilation mode is selected and when CO2 levels r...

Страница 9: ...Default Green 1500ppm 23 C 73 4 F Yellow 1500ppm 23 C 73 4 F Red 2800ppm 25 C 77 0 F CO2 Pre alarm relay switch 2800ppm CO2 Alarm relay switch 4500ppm 0 10V Analogue Output Progression Min output 1 5...

Страница 10: ...e device High concentrations of alcohol found in many products may damage deteriorate or affect the gas sensing elements such as wine deodorants stain removers thinners etc Auto Calibration Our CO2 se...

Страница 11: ...30mm 5 51 x 3 74 x 1 18 Unit Weight Approx 0 08kg Housing Material Polylac PA765 Environmental Ingress Protection IP40 Storage Conditions Dry Temp 10 50 C 14 122 F 30 80 rh Compliance CE EN 50270 EN 6...

Страница 12: ...or any errors or omissions in this document or their consequences CGS would greatly appreciate being informed of any errors or omissions that may be found in the content of this document For informati...

Отзывы: