background image

AquaEfficiency 

Quick installation manual

 

 

 

 

3.3  Set the hot water temperature 

Please set a hot water production temperature in line with current national legislation and recommendations. 

 

NOTE!

 Cetetherm recommends the hot water temperature is at least 55 °C and a hot water circulation not less 

than 50 °C. 

With a temperature below 50 °C there is an increased risk of bacterial growth. 

Note that at temperatures above 60 °C the risk of scalding increases. 

 

Set points above 63 °C result in an increased risk of precipitation of lime scaling on the surfaces of the heat 

exchanger. 

 

The DHW set point SP_T_Sec_Outlet, is set to 55 °C by default, at any time, all the days of the week. 

 

Add extra temperature set points at different times of the day. 

These changes will be reported to all days with the time program week, excluding the weekend time program. 

 

1.  Press the 

to go back to the Main Menu, choose “S1 Menu.Sec 

Outlet”, press the wheel. 

2.  Use the wheel and mark the clock logo, press the wheel. 

 

 

 

3.  Mark the day you want to change, press the wheel. 

 

 

4.  Change a time or temperature.  

Mark the line and press the wheel. Change the value by turning the 

wheel.  

Confirm the new setting by pressing the wheel.  

5.  Add a new time or set point; choose 

6.  To delete a time or set point; choose;

In this example the set point is 60°C at 22h00.

 

 

 

 

 

 

Содержание AquaEfficiency

Страница 1: ...manual AquaEfficiency Quick installation guide Domestic hot water system Content 1 General information 2 1 1 Information about the document 2 2 Electrical installation 2 2 1 Open the control box 2 2...

Страница 2: ...this document are general images AquaEfficiency is available in different models and levels of equipment 2 Electrical installation Power supply the control box with 230VAC 50 Hz AquaEfficiency must be...

Страница 3: ...agram 1 ModBus terminal 2 ModBus terminal 3 I O terminal 2 2 1 Power terminal 230V output to pumps and valves 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 N Ph N Ph N Ph N Ph N Ph N Ph N DO9...

Страница 4: ...nge a highlighted value simply press the wheel Works like an Enter key Press to exit a level and return to the previous menu parameter Works like an ESC key Press to access the maintenance monitoring...

Страница 5: ...iable the year 3 When the year flashes increase or reduce the set value by rotating the wheel Once the right value is displayed press the wheel to confirm the setting Next parameter to change starts t...

Страница 6: ...f the heat exchanger The DHW set point SP_T_Sec_Outlet is set to 55 C by default at any time all the days of the week Add extra temperature set points at different times of the day These changes will...

Страница 7: ...ters can be reloaded 4 1 Spara inst llningar och parametrar 1 Press the key to open the Service menu select Login Installer press the wheel Enter the password 3333 press the wheel to confirm 2 Select...

Страница 8: ...Select Show application press the wheel to see a list of all saved configurations saved with date and time 5 Factory reset 1 Press both and for 5 seconds 2 Rotate the wheel and select in the list the...

Отзывы: