3.3 Set the hot water temperature
Please set a hot water production temperature in line with current national legislation and recommendations.
NOTE!
Cetetherm recommends the hot water temperature is at least 55 °C and a hot water circulation not less
than 50 °C.
With a temperature below 50 °C there is an increased risk of bacterial growth.
Note that at temperatures above 60 °C the risk of scalding increases.
Set points above 63 °C result in an increased risk of precipitation of lime scaling on the surfaces of the heat
exchanger.
The DHW set point SP_T_Sec_Outlet, is set to 55 °C by default, at any time, all the days of the week.
Add extra temperature set points at different times of the day.
These changes will be reported to all days with the time program week, excluding the weekend time program.
1. Press the
to go back to the Main Menu, choose “S1 Menu.Sec
Outlet”, press the wheel.
2. Use the wheel and mark the clock logo, press the wheel.
3. Mark the day you want to change, press the wheel.
4. Change a time or temperature.
Mark the line and press the wheel. Change the value by turning the
wheel.
Confirm the new setting by pressing the wheel.
5. Add a new time or set point; choose
.
6. To delete a time or set point; choose;
.
In this example the set point is 60°C at 22h00.
.