DOS AND DONTS

Do…

• Read your owner’s manual.
• Close your drain valve on the pump casing before starting the engine.
• Seal up any air that could leak into the suction side.
• Charge you battery at least once every three months.
• Stop your pump before fuelling if using the fuel tank install on engine.

Do Not…

• Let your pump freeze up with water in it (drain the casing).
• Allow sand in the suction it will damage the wear ring and the mechanical seal (use floating strainer if water supply doubtful).
• Run your pump dry for more than 2 minutes at idle (prime as soon as possible).
• Run the engine with exhaust closed after the pump is primed.
• Use your pump with less than 12 in of water below the inlet of the suction hose.
• Allow your pump to run without surveillance.
• Run the pump with the discharge valve closed for more than 1 minute.

STARTING PROCEDURE

• Place your pump on a hard, stable surface within 15° from horizontal.
• Check the oil.
• Check the fuel tank level.
• Connect your suction hose. Make sure that there is a rubber seal on the adapter and screw it tight.
• Close all the drain valves (underneath the body of the discharge valve and below the casing of the pump).
• Start the engine and let it idle.
• Open the priming valve between the pump casing and the venturi connected to the exhaust system.
• Close the exhaust port.
• Speed up the engine with the throttle cable to its maximum speed.
•   When water comes out of the venturi (it should take approximately 15 to 30 sec. with a 10 ft x 2 1/2¨ suction hose),  

close the priming valve.

• Open the discharge valve to allow water to run through the pump.
• Open the exhaust port.
• Adjust the RPM to desired pressure.

N.B. 1 The exhaust system is very hot. Do not touch.
N.B. 2 When you are done with the pump, always drain the pump casing.

Содержание SM-PFP-21hpDSL-MR

Страница 1: ... single stage centrifugal pump Pump body made from resistant aluminum alloy Bronze impellers Steel pump shaft Mechanical shaft seal Stainless steel pump shaft Exhaust priming system guaranteed up to 15 4 6 meter lift One 1 1 2 38 mm delivery outlet One 2 1 2 65 mm suction inlet Dimensions Length 31 1 2 800 mm Width 26 660 mm Height 31 1 2 800 mm Weight 282 lbs 128 kg Two years warranty CONTROL PAN...

Страница 2: ...d Use your pump with less than 12 in of water below the inlet of the suction hose Allow your pump to run without surveillance Run the pump with the discharge valve closed for more than 1 minute STARTING PROCEDURE Place your pump on a hard stable surface within 15 from horizontal Check the oil Check the fuel tank level Connect your suction hose Make sure that there is a rubber seal on the adapter a...

Страница 3: ...rnals and replace hose connection caps Taking care of the pump will help prevent the pump from seizing up TROUBLESHOOTING Before calling us try the following if your pump does not operate properly If the venturi does not work properly Check the casing drain valve it should be closed Check any air leakage from suction hose If the engine seems to speed up and down lost of suction Make sure the sucti...

Страница 4: ...therwise for parts accessories or components not manufactured by it but purchased for assembly into the equipment but CET will assign to the Purchaser whatever warranty rights are extended by the supplier of such part accessory or component 2 CET incurs no liability under this warranty or otherwise for equipment which has been abused altered or improperly maintained or for equipment which has been...

Отзывы: