*CET is a trademark of CET F
ire Pumps Mfg Ltd
.
75 Hector St., P.O. Box 90, Pierreville (Québec) Canada J0G 1J0 Telephone: 1-800-567-2719 Fax: 1-800-434-2613
www.fire-pump.com
ACCEPT ONLY THE BEST
A C E N T U R Y O F E N G I N E E R I N G F O R T H E B R AV E S T
SM-PFP-21hpDSL-MR
INSTRUCTIONS MANUAL
DOS AND DONTS
Do…
• Read your owner’s manual.
• Close your drain valve on the pump casing before starting the engine.
• Seal up any air that could leak into the suction side.
• Charge you battery at least once every three months.
• Stop your pump before fuelling if using the fuel tank install on engine.
Do Not…
• Let your pump freeze up with water in it (drain the casing).
• Allow sand in the suction it will damage the wear ring and the mechanical seal (use floating strainer if water supply doubtful).
• Run your pump dry for more than 2 minutes at idle (prime as soon as possible).
• Run the engine with exhaust closed after the pump is primed.
• Use your pump with less than 12 in of water below the inlet of the suction hose.
• Allow your pump to run without surveillance.
• Run the pump with the discharge valve closed for more than 1 minute.
STARTING PROCEDURE
• Place your pump on a hard, stable surface within 15° from horizontal.
• Check the oil.
• Check the fuel tank level.
• Connect your suction hose. Make sure that there is a rubber seal on the adapter and screw it tight.
• Close all the drain valves (underneath the body of the discharge valve and below the casing of the pump).
• Start the engine and let it idle.
• Open the priming valve between the pump casing and the venturi connected to the exhaust system.
• Close the exhaust port.
• Speed up the engine with the throttle cable to its maximum speed.
• When water comes out of the venturi (it should take approximately 15 to 30 sec. with a 10 ft x 2 1/2¨ suction hose),
close the priming valve.
• Open the discharge valve to allow water to run through the pump.
• Open the exhaust port.
• Adjust the RPM to desired pressure.
N.B. 1 The exhaust system is very hot. Do not touch.