CET Electric Technology
92
6076
RW
Dip/Swell Trigger 1
UINT16
0=None
1 to 3=DO1 ~ DO3
4 to 7=HS DR 1 ~ 4
8 to 19=Standard DR 1 ~ 12
20 to 21=WR 1 ~ WR 2
22= Alarm Email
20
6077
RW
Dip/Swell Trigger 2
UINT16
0
6078
RW
Reserved
UINT16
-
-
6079
RW
Time Zone
UINT16
0 to 32
26
6080
RW
Reserved
UINT16
-
-
6081
RW
SNTP IP Address
UINT32
If IP address is 192.168.8.94,
write “0xC0A8085E” to this
register
0.0.0.0
6083
RW
SMTP IP Port
UINT16
0 to 65535
25
6084
RW
SNTP Server IP
UINT32
If address is 191.168.0.94,
write “0xC0A805E” to this
register
192.168.0.94
6086~6121
RW
Sender Email
UINT16
See Note 15)
6122~6141
RW
Logon Password
UINT16
See Note 16)
6142~6177
RW
Receiver Email
UINT16
See Note 17)
6178
RW
Transient Enable
UINT16
0=Disabled, 1=Enabled
1
6179
RW
Transient Limit
UINT16
5 to 500 (x0.01 Ull
nominal
)
35
6180
RW
Transient Trigger 1
UINT16
0=None
1 to 3=DO1 ~ DO3
4 to 7=HS DR 1 ~ 4
8 to 19=Standard DR 1 ~ 12
20 to 21=WR 1 ~ WR 2
22= Alarm Email
20
6181
RW
Transient Trigger 2
UINT16
0
6182
RW
Email Language
UINT16
0=English, 1=Chinese
0
6183
RW
Backlight Time-out
UINT16
0 to 60 (mins)
3
6184
RW
Interruption Limit
UINT16
0 to 50 (x0.01Un)
10
6185
RW
Arm before Execute
UINT16
0=Disabled 1=Enabled
0
6186
RW
kvarh Type
UINT16
0=RMS kvarh
1=Fundamental kvarh
0
6187
RW
EN Period
UINT16
5 to 60min
60
6188~6199
RW
Reserved
UINT16
-
-
6200
RW
Current On Threshold
UINT16
1 to 1000 (x0.001Iprim)
1
6201
RW
Swell Hysteresis
UINT16
1 to 1000
(x0.001 Ull
nominal
)
5
6202
RW
Dip Hysteresis
UINT16
6203
RW
Interruption Hysteresis
UINT16
6204
RW
Date Format
UINT16
0=YYMMDD
1=MMDDYY
2=DDMMYY
0
6205
RW
LCD Contrast (%)
UINT16
50 to 100
90
6206
RW
Phase A Color
UINT16
0=Brown, 1=Red
2=Pink, 3=Orange
4=Yellow
5=Yellow-green
6=Green
7=Light-blue
8=Dark-blue
9=Purple, 10=Gray
11=Natural Gray
12=White, 13=Black
4
6207
RW
Phase B Color
UINT16
6
6208
RW
Phase C Color
UINT16
1
6209
RW
Phase N Color
UINT16
13
6210
RW
Ground Wire Color
UINT16
0=Green, 1=Yellow-green
1
6211
RW
Clock Source
UINT16
0=RTC, 1=SNTP, 2=GPS
0
6212
RW
Gateway Port
UINT16
1 to 65535
Using the same port in
different applications will
cause conflict
6000
6213
RW
Modbus RTU Port
UINT16
27011
6214
RW
Modbus TCP Port
UINT16
502
6215
RW
Web Port
UINT16
80
6216
RW
Delimiter
UINT16
See Note 21)
0
Table 5-35 Basic Setup Parameters
Notes:
1)
PT Ratio= PT Ratio-Integer Part + (PT Ratio-Decimal Part/10000)
For 1A configuration, PT Ratio × CT Ratio must be less than 5,000,000
For 5A configuration, PT Ratio × CT Ratio must be less than 1,000,000