6. Set DIP switch 5 to ON.
7. Use DIP switches 1-4 to set the reader addresses for the connected units.
DIP
Function
1 – 4
Setting the reader address
5
Baud rate (always ON)
6
Bus terminating resistor for RS485
8. Shorten the connecting cable and strip back the cable to reveal the strands (5–
6 cm).
9. Guide the cable strands through the cover cap and wire them to the terminal
in accordance with the connection diagram.
Risk of damage Perform all work on and in the device with the power
supply disconnected.
10. Attach the connection terminal.
11. Replace the cover cap.
Risk of equipment damage by entry of moisture
Careful sealing is required to satisfy protection class IP 65.
12. Seal the cover cap with the sealing tape provided.