ReCon T Energy Logger
User manual

MODBUS in ReCon T

ReCon T instruments with Ethernet have a built-in TCP-MODBUS server that allows the user to

access real time data and to integrate the ReCon T in a network with other types of instruments.

Regarding the TCP-MODBUS standard, user must be aware of two important features of the ReCon

T´s TCP-MODBUS server:

1. Only Holding Registers are available to the user (due to the lack of digital inputs and outputs).
2. The Unit Identifier of the TCP-MODBUS header of the requests will be ignored, as the IP of the unit

(or the port forwarding method explained before) is used to rout the traffic.

Available real time measurements via MODBUS

The real time measurements available through the Holding Registers function of TCP-MODBUS are:

Address Variable

Format

Units

0

L1. Mean

6

 Active power of 1 second reading

7

16 bit signed

8

 decimal

W

9

1

L2. Mean Active power of 1 second reading

16 bit signed decimal

W

2

L3. Mean Active power of 1 second reading

16 bit signed decimal

W

3

Total Mean Active power of 1 second reading

16 bit signed decimal

W

4

L1. Mean Reactive power of 1 second reading

16 bit signed decimal

var

9

5

L2. Mean Reactive power of 1 second reading

16 bit signed decimal

var

6

L3. Mean Reactive power of 1 second reading

16 bit signed decimal

var

7

Total Mean Reactive power of 1 second reading

16 bit signed decimal

var

8

L1. Mean Apparent power of 1 second reading

16 bit unsigned decimal VA

9

9

L2. Mean Apparent power of 1 second reading

16 bit unsigned decimal VA

6

Only average values are available in real time. For maximum and minimum vales, use MedcalScope

7

Real time measurements are updated every second synchronized with the internal clock. As TCP-MODBUS is

asynchronous, measurements are not initiated on MODBUS demand but on the internal real time clock
8

Two´s complement sign-magnitude format

9

See Address 34 for power scaling comments

24/39

Содержание ReCon T

Страница 1: ...ReCon T Energy Logger User manual...

Страница 2: ...e and TCP IP connection 23 MODBUS in ReCon T 24 Available real time measurements via MODBUS 24 ReCon T built in web server 26 Bluetooth configuration and use 27 Windows XP 27 Windows 7 31 Windows 10 3...

Страница 3: ...30 Figure 32 Windows XP End of Wizard outgoing port highlighted 30 Figure 33 Windows XP ReCon T connection ready 30 Figure 34 Bluetooh connection in MEDCALScope 31 Figure 35 Windows XP Make Bluetooth...

Страница 4: ...ReCon T Energy Logger User manual Figure 57 Toshiba end of wizard 38 Figure 58 Toshiba list of devices 39 Figure 59 Toshiba authentication dialog 39 4 39...

Страница 5: ...web server documentation CABL 1 6 07 02 2013 Added information on measurement methods RACB 1 7 30 10 2015 Bluetooth information added MJCG 1 8 05 03 2020 Complete revision of the document Added new f...

Страница 6: ...d boots helmet and any other required individual protection equipment 6 Do not operate the ReCon T Energy Logger in explosive hazardous areas 7 Use only insulated current probe s test leads and adapte...

Страница 7: ...rs have a marked arrow to indicate the positive sense of current The most common situation you will use the instrument for is analyzing the energy consumption of an installation Connect the flexible c...

Страница 8: ...ly disconnect the instrument in order to finish the recording session Connecting the ReCon T Energy Logger To install the ReCon T Energy Logger follow these steps 1 Place the ReCon T Energy Logger at...

Страница 9: ...the ReCon T and downloading the recorded information are done via the MEDCALScope PC application Simply click on the Set up button The set up screen is divided in 7 different areas 9 39 Figure 1 Tool...

Страница 10: ...e used to access ReCon T Either CESINEL protocol if you intend to download data via TCP IP using MEDCALScope or ModBus TCP if the instrument is integrated in a larger automation network that requires...

Страница 11: ...a wide selection of choices between 115 V and 480 V 3 Measuring in High Voltage HV sometimes the load to be analyzed is fed directly from high voltage larger than 1 kV It is possible to measure in th...

Страница 12: ...second option enables S measurement from Vrms and Irms and Q calculation from measured P and S Q is non active power then 7 Next panel is only present when instrument runs a firmware equal to or high...

Страница 13: ...and time as PC synchronizes the ReCon T internal clock with the PC s clock 4 Reset energy counter clears the internal energy registers of the ReCon T These registers are not cleared when memory is era...

Страница 14: ...sensors or even an absence of current sensors from firmware V2 61 on voltage only recording session is possible so there is no need to attach current sensors what makes transportation and installatio...

Страница 15: ...er clicks Apply and start recording and stops recording when Erase recorded data is clicked The instrument measures and records data even during downloading of data setting up of the instrument unless...

Страница 16: ...date and time is reached If memory is setup as linear memory the programmed session could end before stop date and time If circular memory is selected programmed session will end at the specified dat...

Страница 17: ...rted The available trigger variables are the three measured voltages and currents Once the trigger is fired the recording lasts until memory is full if linear memory is selected or user stops it via M...

Страница 18: ...Figure 10 Connection for 3 Phase Wye Star topology 2 3 Delta triangle topology Figure 11 Connection for 3 Phase Delta Triangle topology 3 1 Phase with Neutral topology Figure 12 Connection for single...

Страница 19: ...zing as said before measurements must be synchronized with multiples of Recording interval Once recording is allowed to start through any method of those explained before there is a certain time inter...

Страница 20: ...local IP address of the unit is enough to access the data Medcal S cop e software provides an Instrument Name IP Address table which will be stored in memory and therefore available every time Medcal...

Страница 21: ...er s configuration utility if the router is DHCP configured or must be provided by the ISP internet server provider from whom you rent your internet connection if a static IP address is rented Routers...

Страница 22: ...e software With the configuration of the previous figures and supposing that our router s public IP address is 80 10 3 247 14 we could access data via MedcalScope Modbus software or web browser from a...

Страница 23: ...Then when download or setup actions are triggered through menu items or toolbar buttons a TCP IP selector dialog appears see Figure 12 so that the user can choose an existing item or add a new one to...

Страница 24: ...t signed8 decimal W9 1 L2 Mean Active power of 1 second reading 16 bit signed decimal W 2 L3 Mean Active power of 1 second reading 16 bit signed decimal W 3 Total Mean Active power of 1 second reading...

Страница 25: ...Energy 16 bit 24 L2 Mid Low word of Accumulated Active Energy 16 bit 25 L2 Lowest word of Accumulated Active Energy 16 bit Wh 26 L3 Highest word of Accumulated Active Energy 16 bit 27 L3 Mid High word...

Страница 26: ...ReCon T Energy Logger User manual 26 39...

Страница 27: ...vious sections on how to access a ReCon T from outside inside its LAN The web page has an auto refresh interval of 5 seconds although the user may always refresh the web page via web browser commands...

Страница 28: ...PC s operating system Windows XP 1 Start Control panel or double click Bluetooth icon Bluetooth devices Add a new Bluetooth device 2 Make sure that you check the My device is configured and ready to b...

Страница 29: ...and then type that key in the associated field13 6 The PC will connect to the ReCon T instrument exchange access keys and install virtual serial ports 13 The key is by default equal to the 4 last digi...

Страница 30: ...serial ports created Since the ReCon T instrument will never start the communication and will always be treated as slave during the process we must pay attention to the Output serial port 9 The ReCon...

Страница 31: ...n in the notification area option 12 If you are not going to work with the Bluetooth ReCon T device for a long time it is recommend ed to remove the instrument from the Bluetooth devices list since th...

Страница 32: ...ReCon T Energy Logger User manual Windows 7 1 Start Control panel or double click Bluetooth icon Add new device 32 39 Figure 37 Windows 7 Control Panel Figure 38 Windows 7 Add new device...

Страница 33: ...ded key and click Next The PC will connect with the ReCon T instrument and will install the device controller software A pop up message will appear when the process is finished and the device will be...

Страница 34: ...n T icon and select Properties Go to Services tab and the virtual serial port identifier will be displayed there 34 39 Figure 42 Windows 7 End of installation of device Figure 43 Windows 7 Device prop...

Страница 35: ...Con T device for a long time it is recommended to remove the instrument from the Bluetooth devices list since the virtual serial ports are not automatically removed and new ones are created for every...

Страница 36: ...new device 2 Click on the ReCon T instrument and wait for Windows to ask for PIN Enter PIN code and click Connect 36 39 Figure 45 Windows 10 Bluetooth and devices Figure 46 Windows 10 add Bluetooth d...

Страница 37: ...s and printers right click on ReCon T and click Properties to guess COM port under Services tab 37 39 Figure 50 Windows 10 devices and printers in setup Figure 52 Windows 10 properties of paired ReCon...

Страница 38: ...th stack different than the one provided by Windows Toshiba for instance you must use the tools provided by the manufacturer 1 Create a new connection 38 39 Figure 53 Bluetooh icon Figure 55 Toshiba B...

Страница 39: ...rgy Logger User manual 2 An access key will be required the first time that you try to connect with the ReCon T instrument either using MEDCALScope or the assistant 39 39 Figure 59 Toshiba authenticat...

Отзывы: