background image

2191

JDV28 cover

12/10/99  djt

INSTALLER / CONSUMER 

SAFETY INFORMATION

30004177  3/08  Rev. 2

PLEASE READ THIS MANUAL 
BEFORE INSTALLING AND USING 
APPLIANCE.

WARNING!

IF THE INFORMATION IN THIS 
MANUAL IS NOT FOLLOWED 
EXACTLY, A FIRE OR EXPLOSION 
MAY RESULT CAUSING 
PROPERTY DAMAGE, PERSONAL 
INJURY OR LOSS OF LIFE.

FOR YOUR SAFETY

Installation and service must be 
performed by a qualified installer, 
service agency or the gas suppler.

WHAT TO DO IF 

YOU SMELL GAS:

• 

Do not try to light any appliance.

• 

Do not touch any electric switch; do 
not use any phone in your building.

• 

Immediately call your gas supplier 
from your neighbor’s phone. Follow 
the gas supplier’s instructions.

• 

If you cannot reach your gas supplier, 
call the fire department.

DO NOT STORE OR USE 
GASOLINE OR OTHER 
FLAMMABLE VAPORS AND 
LIQUIDS IN THE VICINITY OF THIS 
OR ANY OTHER APPLIANCE.

This appliance may be installed in an 
after market permanently located 
manufactured (mobile) home where not 
prohibited by local codes.

This appliance is only for use with the 
type of gas indicated on the rating plate.

This appliance is not convertible for use 
with other gases unless a certified kit is 
used.

Jefferson
Direct Vent/Natural Vent 
Gas Heater

Model: JDVBRN

Homeowner’s Installation 

and Operating Manual

CERTIFIED

DESIGN

CERTIFIED

INSTALLER: Leave this manual with the appliance.

CONSUMER: Retain this manual for future reference.

Содержание JDVBRN

Страница 1: ...supplier from your neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE This appliance may be installed in an after market permanently located manufactured mobile home where not prohibited by local codes This appliance is...

Страница 2: ...ral Vent ONLY 12 Venting Requirements and Options Direct Vent ONLY 13 Assembly Procedures Tools Required 14 Unpack the Stove 14 Install Optional Fan 14 Venting System Assembly Direct Vent 15 Install Vent Adapter Pipe CFM Corporation Components 15 Install Vent Adapter Pipe Simpson Dura Vent Components 16 Side Wall Termination Assembly 17 Vent Termination Below Grade 18 Vertical Through the Roof Ven...

Страница 3: ...gh the roof to the atmosphere This appliance is approved for bedroom installations in the U S and Canada Check local codes for natural vent requirements This appliance may be installed in an aftermarket manufactured mobile home where not prohibited by state or local codes WARNING Operation of this heater when not connected to a properly installed and maintained venting system can result in carbon ...

Страница 4: ...ly vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observes carbon monoxide detectors and signage...

Страница 5: ...ped from the factory as a Direct Vent Gas Heater This heater may be converted into a Natural Vent unit in the field If a Natural Vent Heater is desired the CFM Corporation Z31B00 FSD HAG Draft Hood must be directly installed to the top of the unit according to the installation instructions The Draft Hood Adapter is available in the 7FSDHASK stove kit or as a separate item When the Jefferson stove i...

Страница 6: ... 2 Possible stove locations Direct Vent System Only A B E C D ST207a Stardance Stove locations 9 28 00 djt Clearance Requirements Minimum Clearances to Combustible Materials Measure side clearances as shown in Figures 3 and 4 from the outer edge of the cast iron stove top Measure rear clearances from the outermost surface of the steel rear skirt The Jefferson heater is approved for installation in...

Страница 7: ...ces and flue centerlines Corner Installation Minimum Clearance and Flue Centerline Direct Vent Natural Vent ST129b Stardance corner specs 9 28 00 djt A A B B Stove Clearance A 4 102 mm Pipe Centerline B 14 375 mm ST129b Fig 4 Corner installation minimum corner clearance and flue centerline Wall Centerline from Floor ST131a wall thimble 12 3 99 djt A Effective Minimum Wall Thimble 58 1480 mm CFM Pipe...

Страница 8: ...n for installations at elevations above 4 500 feet 1 370m WARNING Improper installation adjust ment alteration service or maintenance can cause injury or property damage Refer to this manual for correct installation and operational procedures For assistance or additional information consult a qualified installer service agency or the gas supplier Horizontal Termination Direct Vent ONLY The vent mus...

Страница 9: ... all vertically terminated vent systems Refer to Figure 8 NOTE The restrictor plate supplied with the vertical termination should be discarded Install restrictor plate supplied with stove directly at stove outlet A vertically terminated vent system must also conform to the following criteria No more than two 90 elbows may be used Two 45 elbows may be substituted for one 90 elbow No more than six e...

Страница 10: ...rminals shall not be recessed into a wall or siding Horizontal venting must be installed on a level plane without an inclining or declining slope There must not be any obstruction such as bushes garden sheds fences decks or utility buildings within 24 from the front of the termination hood Do not locate termination hood where excessive snow or ice build up may occur Be sure to check vent termi nat...

Страница 11: ...vent outlet 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30cm for 10 000 Btuh 3kW 9 other appliances appliances 10 000 Btuh 3kW and 23cm for appliances 10 000 100 000 Btuh 30kW 36 91cm Btuh 3kW and 50 000 Btuh for appliances 100 000 Btuh 30kW 15kW 12 30cm for appliances 50 0...

Страница 12: ... soffits 1 There must be a 3 914 mm minimum between termination caps 2 All mechanical air intakes within 10 1 m of a termination cap must be a minimum of 3 914 mm below the termination cap 3 All gravity air intakes within 3 914 mm of a termination cap must be a minimum of 1 305 mm below the termination cap FP567 NVBR NVBC VENTING RUNS 11 12 97 Venting Runs Horizontal Run in feet Vertical Run in fee...

Страница 13: ...harcoal Gray paint Consult your dealer about other vent parts that may be appropriate to complete the installation Min Through the Wall Vent Kit 7TFSSK 1 90 Degree Elbow CG 1 24 Straight pipe CG 1 24 42 Adjustable Straight Pipe 1 Side Wall Termination 1 Firestop 1 Zero clearance sleeve 1 Hardware package 1 Finishing plate CG 1 Finishing collar CG 4 Charcoal Gray flue pipe rings Starter Kit for Belo...

Страница 14: ...y on a flat padded surface such as a counter protected by a towel 4 Take the logset and all other loose parts out of the firebox and set them aside in a protected area for installation after the venting is complete WARNING This appliance is equipped with a three prong grounded plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle...

Страница 15: ...the assembly with three sheet metal screws Fig 17 3 Dry fit the Inner Pipe assembly to the stove for the purpose of determining the center line of the pipe on the wall Side Wall Terminations Dry fit the outer elbow with the vertical outer vent and confirm the centerline alignment with the wall thimble opening 3 Attach the fan to the rear shroud by engaging the upper flange of the fan skirt under the l...

Страница 16: ...ig 19 ST213 install outer adpater 12 6 99 djt ST213 Fig 19 Fasten outer pipe with 12 x 1 2 sheet metal screws Install the Vent Adapter Pipe Simpson Dura Vent Components 1 Install the Restrictor Plate Consult the Vertical Terminations on Page 9 to determine whether the restrictor plate is needed If so put the restrictor plate in place within the inner flue collar as shown in Figure 16 2 Discard the ...

Страница 17: ... Wall VO584 100 Fig 22 Locate vent opening CFM System DuraVent System 10 254mm 10 254mm For DuraVent pipe only Install vent pipe by align ing the locking system together sliding the pipes together and twisting clockwise Install 90 elbow Twist lock as before Slide the wall plate over horizontal run before at taching the horizontal run to the elbow Fasten wall plate to wall 4 For CFM Vent Pipe only ...

Страница 18: ...nts if desired ST217 install wall terminal 12 6 99 djt Seal Both Terminal Ends Caulk Plate Joint with Weatherproof Sealant ST217 Fig 27 Install the vent terminal Vent Termination Below Grade Install Snorkel Kit 7FSDVSKS when it is not possible to meet the required vent termination clearances of 12 305 mm above grade level The snorkel kit will allow installation depth of down to 7 178 mm below grad...

Страница 19: ...ll vertically terminated installations must where specified use the restrictor plate to comply with Vertical Termination Window Page 9 Figure 8 included in the hardware bag Make certain the vent system conforms to all other requirements for vertical termination as specified on Page 9 This installation will require you to first determine the roof pitch and use the appropriate vent components Refer to ...

Страница 20: ...Z22 1 For Canadian installations The venting system must conform to the current CSA B149 1 installation code Install the Vent Pipe Apply a bead of sealant around bottom end of inner starter pipe found in bag with logset and attach to stove Apply a bead of sealant around top of inner starter pipe and install the Z31B00 FSDHAG Draft Hood according to Draft Hood instructions Fig 33 Attach the first se...

Страница 21: ...ack of the firebox Fig 34 3 Install the left 2 and right 3 middle logs by engaging holes on their bottoms with pins on the burner brackets Fig 34 ST224 JDV28 install logs 2 12 6 99 djt Top Log 5 Upper Log 4 Lava Rock ST224 Figure 35 4 Loosely sprinkle the lava rocks directly on top of the burner between the decorative grate and the middle logs Do not place any ember material behind the middle logs ...

Страница 22: ...ld pressure of 10 0 between a minimum inlet supply of 11 0 w c and maximum of 14 0 w c CAUTION Burner Information The appliance must only use the gas specified on the rating plate unless converted using a CFM Corporation Fuel Conversion Kit To convert from Natural Gas to LP use Kit 30004180 Conversion instructions are provided with each kit and beginning on Page 28 in this manual THIS APPLIANCE SHO...

Страница 23: ...lly open Fig 40 You may have to try more than once to find the correct air shutter opening for best results depending on your altitude ST352 jefferson air shutter new position 3 20 00 djt Air Shutter Original Position Burner See Table 1 ST352 Fig 39 Air shutter in original from the factory position ST351 jefferson air shutter original position 3 20 00 djt Front Injector Air Inlet Air Shutter May be...

Страница 24: ...ear shroud Install the Stove Front The front panel attaches to the stove by four 4 steel tabs that engage with corresponding cast ribs on the sides and bottom of the stove body Position the front about 3 down from the stove top and lift the plate to engage the upper tabs behind the adjacent ribs on the side Fig 44 Then lower the plate into position so the lower tabs engage with the corresponding r...

Страница 25: ...erate the heater until the pilot flame is correct Follow regular maintenance procedures as described on Page 30 Flame Temperature Adjustment For stoves equipped with HI LO valves flame adjust ment is accomplished by rotating the HI LO adjustment knob located near the center of the gas control valve Fig 47 Turn counterclockwise to decrease flame height Turn clockwise to increase flame height HV102 Fi...

Страница 26: ...LIGHTING smell all around the heater area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any fireplace Do not touch any electric switch Do not use any phone in your building Immediately call your gas supplier from a neigh bor s phone Follow the gas supplier s instruc tions To Turn Off Gas To ...

Страница 27: ...rmocou ple operates the pilot flame Tighten the thermocouple The thermopile operates the main valve ON and OFF Clean and or adjust pilot for maximum flame impinge ment on thermocouple and thermopile Turn valve knob to Pilot Maintain flow to pilot millivolt meter should read greater than 10mV If the reading is okay and the pilot does not stay on replace the gas valve NOTE An interrupter block not supp...

Страница 28: ...ting the electrical power before pro ceeding with the conversion ST226 attach gas line 12 8 99 djt Main Gas Line Gas Supply Inlet ST226 Fig 51 Attach the gas line to the left side of the valve ST350 Jefferson air shutter adj 3 20 00 djt Remove Screws Rear Log Bracket Pilot Left Right Log Bracket Assembly ST350 Fig 53 Remove rear log bracket and left and right log bracket assembly Conversion Proced...

Страница 29: ...lot Orifice CO106b Fig 57 Remove pilot orifice 16 Replace burner Slide the burner in at an angle with left side lower than the right side slide the left side onto the injectors making sure the burner leg remains at a 90 angle to the base Lower the right hand side down in to place Make sure the burner is as far left as possible and the injector shoulders are inside the burner NOTE It is very critical...

Страница 30: ...e stove paints available through your local dealer to touch up areas as needed Clean areas to be painted with a wire brush and be sure to cover the logs burner and valve assembly glass and frame assembly Apply the paint sparingly two light coats of paint will give bet ter results than a single heavy coat Clean porcelain enamel surfaces with a soft damp cloth Do not use abrasive cleaning agents If ...

Страница 31: ...ali fied technician Shut off the main gas supply before inspecting the system Both the inner exhaust pipe and the outer combustion supply pipe must be checked to confirm that they are unblocked and in good condition Check the Gas Flame Regularly To ensure that the stove is operating properly check the flames periodically to confirm that they match Page 24 The flames will be blue during the first 15 20 m...

Страница 32: ...OTOR SNAPSTAT ON OFF RHEOSTAT WHT WHT BLK BLK BLK GRN BLK ST236 FK26 wiring diagram 12 99 Schematic Diagram ST236 ST153 Wiring Diagrams ST124c Fig 62 On off switch and optional thermostat circuit Optional Thermostat Wiring On Off Switch Wiring ST124b OFF ON Thermostat Optional Thermopile Black Black Millivolt Gas Valve St124b on off switch wiring 1 11 00 djt TP TH TP TH Thermostat Optional Thermop...

Страница 33: ...s in design materials specifications prices and discontinue colors and products at any time without notice Jefferson Direct Vent Natural Vent Gas Heater Model JDVBRN Ref Description JDVB 1 Gas Log Set 20002182 1a Log Back 20002183 1b Log Left Upper 20002187 1c Log Right Upper 20002186 1d Log Left 20002185 1e Log Right 20002184 2 Lava Rocks Burner 57897 3 Top 30000680 4 Grille 30000685 5 Screen Gril...

Страница 34: ...le 18 RS 51827 7533113 26 Nut Electrode SIT 0 974 144 57886 27 Tubing Pilot w Fittings 1 8 x 24 10001296 28a Orifice Hood 69 Front LP not shown 30000513 28b Orifice Hood 54 Front NG not shown 20000130 28c Orifice Hood 54 Rear LP not shown 20000130 28d Orifice Hood 44 Rear NG not shown 30000334 29 Wiring Harness FSDV32RN JDV 10002582 30 Switch ON OFF RN RP Models 30000874 31 Bracket Right Log 20002166 ...

Страница 35: ...regular maintenance however periodic cleaning of the fan and the surround ing area is required Installation Refer to Page 14 for installation instructions Remote Controls The remote control allows you to turn the heater on or off from anywhere in the room Refer to Page 32 for wiring diagrams These remote controls are for use with RN RP models Model Functions Controlled RC1 ON OFF RC2 ON OFF and Te...

Страница 36: ...3636 Jefferson Direct Vent Natural Vent Gas Heater 30004177 ...

Страница 37: ...37 Jefferson Direct Vent Natural Vent Gas Heater 30004177 ...

Страница 38: ...3838 Jefferson Direct Vent Natural Vent Gas Heater 30004177 ...

Страница 39: ...ndensation for prolonged periods or iv that have been damaged due to water or weather 7 Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner 8 To make claim under this warranty the original consumer purchaser shall notify CFM at 1 800 668 5323 within ten 10 days of the discovery of the alleged d...

Страница 40: ...Efficiency Ratings Model EnerGuide Ratings Fireplace Efficiency JDVBRN 60 7 JDVBRP 60 7 2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation ...

Отзывы: