background image

5. Relay functionality

Vehicle 

detected 

No vehicle 

detected 

Loop faulty 

Power off

N/O 

N/C

Closed

Open

Closed

Closed

Open

Closed

Open

Open

6. Tips for a successful loop installation

1.

The FLUX SA should be installed in a weatherproof location, such 
as the inside of a gate operator, as close to the loop as possible.

2.

The loop and feeder should be constructed from XLPE (cross-
linked polyethylene) insulated multi-stranded copper wire with a 

2

minimum cross-sectional area of 1.5mm . The feeder should be 
twisted at a rate of at least 20 turns per metre to improve 
reliability (Remember that twisting the feeder will shorten its 
length, so ensure a long enough feeder wire is used). Feeders 
which may pick up electrical noise should use screened cable, 
with the screen earthed at the detector. 

3.

Joints in the wire are not recommended, but where required must 
be soldered and made waterproof.

Faulty joints will lead to unreliable operation.

4.

The loop should be either square or rectangular in shape with a 
minimum distance of 1m between opposite sides. 

5.

Two to six turns of wire are typically used in the loop – see table 
below. 

Loop perimeter (metres) 

3 - 4

4 - 6

6 - 10

10 - 20

>20

Number of turns 

6

5

4

3

2

6.

When two loops are laid in close proximity to each other, it is 
recommended that different numbers of turns are used in each 
loop to prevent cross-talk.

7.

Cross-talk describes the interference between two adjacent loops, 
and can cause reliability issues.

.

8.

The most reliable form of loop is preformed and enclosed in 
conduit. This prevents water ingress, and minimizes the effects of 
vibration.

D5

D5

Evo

 To minimize cross-talk, adjacent loops should be at least two 
metres apart, and on different frequency settings

9.

Where a pre-formed loop is not practical, slots should be cut into 

o

the road using a masonry cutting tool. A 45  cut should be made 
across the corners to prevent damage to the wire on the corners. 
The slot should be about 4mm wide and 30mm to 50mm deep. 
Remember to extend the slot from one of the corners to the 
roadside to accommodate the feeder. After the loop and feeder 
wires have been placed in the slot, the slot must be filled with an 
epoxy compound or bitumen filler.

7. Mounting instructions

The housing of the 

FLUX SA

 is not weatherproof, and it should not be 

mounted externally. 

Rather mount the 

FLUX SA

 inside an operator or suitably 

protected control box. Mounting points have been incorporated 
into the design of the cover of the 

FLUX SA

 to assist you in 

obtaining the optimal position.

8. Electrical setup

Symptom    

Possible cause 

Solution

The power LED 
is not on

No power supply voltage 
on the input.

Check that the power supply is 
correctly wired to the detector. 

The sense Level 
LEDs flash 
erratically

There may be a poor 
connection in the loop or 
loop feeder.

Check all wiring. Tighten screw 
terminals. Check for broken wires.

The detector may be 
experiencing crosstalk 
with the loop of an 
adjacent detector.

Try changing frequencies using the 
frequency switch. Put the detector with 
the larger loop onto low frequency and 
the detector with the smaller loop onto 
high frequency.

Faulty loop or loop 
feeder wiring.

Check the wiring. Tighten screw 
terminals. Check for pinched or bent 
wires. Is the feeder wire twisted? 

The detector 
randomly 
detects, even 
though there is 
no vehicle 
present

Check for cracks in the road surface 
near the loop. 

Movement of the loop in 
the ground.

The loop inductance is 
too large, or the loop is 
open circuit.

Check that there is electrical continuity 
on the loop. If the loop inductance is 
too large then try reducing the number 
of turns.

The Loop Fault 
LED is flashing, 
and an audible 
tone is heard – 
two short 
tones, one long 
tone

Check that there is no short circuit on 
the loop feeder wiring or the loop. If 
there is no short circuit then the 
inductance is too small and more turns 
of wire should be added to the loop.

The loop inductance is 
too small, or the loop is 
short circuited.

The Loop Fault 
LED is 
permanently 
illuminated, 
and an audible 
tone is heard – 
one short tone, 
one long tone

Aux 12V out

D5-Evo 
controller

COM1

FRX

COM2

Free-exit 
loop

8A. D5-Evo Free-exit loop 

8B. D5-Evo Closing safety loop 

FLUX SA

Aux 12V out

D5-Evo 
controller

COM1

IRBC

COM2

Closing
safety loop

FLUX SA

10. Diagnostics

This green LED Indicator is illuminated when there is 
a vehicle detected. This LED can also be used to 
determine the loop frequency. Reset or power up, 
count the number of times the Detect LED flashes. 
Multiply this number by 10KHz. For example: if the 
LED flashes eight times, then the loop frequency is 
approximately 80KHz 

Detect 
Indicator LED

Free-exit 
loop

FLUX SA

Relay 
output

Power 
supply
(10-40V DC
7-28V AC)

8C. Generic connection diagram

Support stakes

(4 needed)

Curb

Metal-free zone
outline

1. Ensure that all low voltage systems (less than 42.4V) are 

suitably protected from damage, by disconnecting all 
sources of power such as chargers and batteries before 
doing any work.

2. All electrical work must be carried out according to the 

requirements of all applicable local electrical codes.(It is 
recommended that a licensed electrical contractor perform 
such work.)

9. Commissioning the system

Lead cable

slot

Corner stress 
relief

4mm Saw slot

Pavement surface

50mm

4mm

Saw cut

1.

With the loop connected, apply power to the FLUX SA. 

2.

The red Power LED will light up, and the green Detect LED will 
flash until the loop has stabilized, and then turn off. 

3.

If the buzzer is enabled, it will sound continuously during this 
period. 

4.

Once the loop has stabilized, only the red Power LED should be on.

5.

Bring a metal object towards the loop, and the Sense level LEDs 
will begin to light up, indicating the detection range of the loop. 

6.

Once all five lights have lit up, the unit will enter detect, with the 
green Detect LED lit. 

7.

If the buzzer is enabled, a variable tone will indicate the sense 
level, and change to a continuous tone once the unit has detected.

8.

Configure the desired operational settings using the Dipswitches 
(open the access flap to access the Dipswitches).

9.

Test the 

FLUX SA

 using a metallic object, or a vehicle.

www.centsys.com.au

0.07.B.0017 FLUX SA 

Loop Detector 

pocket manual 6Jul2012

Отзывы: