Technical instructions for the commissioning and adjustment
9
5. Start/stop
To strt the boiler press “ON/OFF” button and
confirm it pressing the “OK” button
To stop the boiler press “ON/OFF” button and
confirm it pressing the “OK” button
To start the boiler press “ON/OFF” button and
confirm it pressing the “OK” button
To stop the boiler press “ON/OFF” button and
confirm it pressing the “OK” button
6. Draught of the chimney
Chimney of appropriate size is one of conditions for proper operation of the boiler. Chimney has to be
select according to diagram for solid fuel firing (see Technical instructions EKO-CK P or EKO-CKB P)
or a chimney with the following minimum draughts has to be select for certain powers:
-
Cm Pelet-set 60 = 24 Pa
-
Cm Pelet-set 70 = 25 Pa
-
Cm Pelet-set 90 = 28 Pa