CENTRAL HEATING i-KI Скачать руководство пользователя страница 2

 

rev001

 

 

pg. 2 

 

necessary as the compressor is only designed to compress gas and if any liquid 
refrigerant is in the compressor when it starts it could be damaged. 

In the interim steps 3 and 4, setting the clock, can be completed.  

3.  What happens when you turn on the main isolator 

The Nadi controller room unit will go through an initialisation phase 
that can last a few minutes and will show 

Cn

 followed by

 init

 before 

showing 

Off

 with the time.  

Do not put it into DHW or heating mode for 2 hours.  During this 
time you can set the clock and change any necessary parameters. 

4. 

 

 

 

Set the clock 

 

 

Содержание i-KI

Страница 1: ...nstalled in accordance with the installation manual B Ensure the power is isolated to the unit C Remove the side cover of the unit to expose the water pump compressor and electrical enclosure D Check...

Страница 2: ...tting the clock can be completed 3 What happens when you turn on the main isolator The Nadi controller room unit will go through an initialisation phase that can last a few minutes and will show Cn fo...

Страница 3: ...he menu within the Nadi Controller press and hold the and for 3 secs if the sun symbol on the top left hand corner appears press the mode button to turn it off we do wish for the heat pump to run yet...

Страница 4: ...red parameter on the screen press the knob to confirm Turn the knob to adjust the setting Press the knob to confirm the adjusted setting 7 Menu Settings The table below shows the various menus for acc...

Страница 5: ...e correct pockets Heating is controlled with the Aube Thermostat It must be connected to SA1 via a relay The schematic on the next page shows an Omron Relay and the relevant connections Should an alte...

Страница 6: ...sation Determine if the heating will operate from fixed return set point or outside weather compensation Return Set Point Menu 1 parameter 0152 weather compensation ensure this is set at 0 0 disabled...

Страница 7: ...lash This will keep flashing as long as the sniffing is in process This is defaulted at 3 minutes In addition once the water has reached temperature the heat pump will also sniff for a period of 10 mi...

Страница 8: ...s necessary It is recommended that a flow switch is installed Should you not install a flow switch then it is necessary to install a bridge between terminals 39 and 40 i KI Internal Module Final Wirin...

Страница 9: ...CHNZ if an alternative tank is being used It is also advised that a temperature set point of 50 o C There are 2 set points for DHW Comfort and Economy The comfort set point is the required set point t...

Страница 10: ...at pump is trying to provide heating Before the heat pump runs the compressor to produce heat it first runs it s circulating pump to test the temperature of the water passing through the heat pump Thi...

Страница 11: ...ed with the Aube Thermostat It must be connected to SA3 via a relay The schematic below shows an Omron Relay and the relevant connections Should an alternative relay be used please ensure you check th...

Страница 12: ...arameter 0153 adjust the set point as required typically 45 for underfloor heating Weather Compensation Menu 1 parameter 0152 change to 1 Menu 1 parameter 0159 set the compensation curve from the grap...

Страница 13: ...or a while and then resume or it may continue to run Either way while the compressor is running the three way valve will swing over to the open position and start to heat the cylinder Check for the co...

Страница 14: ...placed inside the wiring module Check BT1 and BT2 probes are in the correct pockets Heating is controlled using the Nadi Controller SA1 is supplied with a loop This must be left in placed to control t...

Страница 15: ...ump is sniffing the pump symbol at the bottom of the screen will flash This will keep flashing as long as the sniffing is in process This is defaulted at 3 minutes In addition once the water has reach...

Страница 16: ...shows what the temperature sensors are reading 0900 return temperature 0901 flow temperature 0902 DHW sensor temperature 0904 Storage tank buffer tank temperature The buffer tank sensor is not normal...

Отзывы: