rev001
pg. 12
Aube Thermostat Control - Ensure the Nadi controller is disabled as a room stat and the
Aube Thermostat is activated.
Parameter 11D is factory set to 0. Change this from 0 to 1 to achieve control of the Aube
Stat.
Menu 1, and turn the knob anti-clockwise until 11D displays on the screen. Change from 0
to 1.
C3. Heating Set Point/Weather Compensation.
Determine if the heating will operate from fixed return set point or outside weather
compensation.
Return Set Point
Menu 1, parameter 0152
– ensure this is set at 0.
Menu 1, parameter 0153
– adjust the set point as
required (typically 45 for underfloor heating).
Weather Compensation
Menu 1, parameter 0152
– change to 1.
Menu 1, parameter 0159
– set the compensation curve from the graph below.
C4
Domestic Hot Water
It is essential that the correct cylinder coil is used. We advise a 3.5m
2
coil to achieve
maximum HWC temperatures. It is also advised that a temperature set point of 50
o
C.
There are 2 set points for DHW, Comfort and Economy. The comfort set point is the
required set point that needs to be changed.
We enable the Comfort set point by setting
0015 to 1
and then setting 0023:
Menu 0, parameter 0015
– ensure this is set to 1 (1= comfort, 0= economy)
Menu 0, parameter 0023
– set the comfort set point to 50
o
C.