alligator clip of the test leads connected. The indicator should read 

00.0

Ω.  When  the  leads  are  not  connected  the  display w ill  read 

infinity indicated by “OL”. This w ill ensure that test lead are under 
w orking condition. 

2-4 Rotary Sw itch positions 

Turn    the Tester on by selecting   any measurement 

Lift 

      1000v,500v,250v,125v (4000M

Ω)          

OFF    400

Ω/BZ, 1000VDC,750VAC     

> 

Right 

2-5 Buttons and a display Indicators 

a). Button 

HOLD/MAX.MIN :

 Instant-pressing the 

“HOLD” button the 1st time,   

the current values w ill be hold in the primary display., but it w ill return   

in the 2nd pressing ; pressing 2 seconds ,it w ill enter directly into the   
“MAX”status, and one another instant-pressing will switch to the  
“MIN”,  if instant-pressing once more, it w ill recycle ,but exit if   
pressing 2 seconds again.  

LOCK :

In  the insulation resistance testing function ,press   the   

“LOCK” button ,and then push down the “ TEST” key, it w ill occur the   
high-voltage and enter the insulation resistance testing status. Press   

the 

“TEST” button once more ,it w ill shutoff the high-voltage and exit  

from the insulation resistance testing status. 

TEST : 

In the insulation resistance testing function ,press ing and  

holding the 

“TEST”  button, The meter w ill bring high-voltage, and   

enter into the insulation resistance testing, being free from the   
“TEST” , it w ill cutoff the high-voltage and exit form the insulation   
resistance testing. 

ZERO/LIGHT  :

Iinstant-pressing 

the “ZERO/LIGHT”  button in the 1st  

time, the current values in the primary display w ill be set   

zero,(mainly used for 400

Ω, the low  resistance testing), ,it will return  

Содержание DT-5505

Страница 1: ...750V 1000V Insulation Tester 400 125V 250V 500V 1000V TEST LOBAT HV 1 POL1 2 1 OHM BZ 2 2 POL2 4 1 BAR 1 8 5 CEM DT 5505 IGITAL INSULATION TESTER NSTRUCTION MANUAL...

Страница 2: ...orking around bare conductors or bus bars Accidental contact with the conductor could result in electric shock Use the meter only as specified in this manual otherw ise the protection provided by the...

Страница 3: ...Environmentconditions Installation Categories Pollution Degree 2 Altitude up to 2000 meters Indoor use only Relatively humidity 80 max Operation Ambient 0 40 C Maintenance Clearing Repairs or servici...

Страница 4: ...C 14 F to 140 F and Humidity below 70 RH Power source DC9V 6x1 5V Size AA batteryor Equivalent Dimensions 200 L x 92 W x 50 H mm Weight Approx 700g include battery Accessories Test leads 6pcsbattery C...

Страница 5: ...1 2 10 10M 750Vrms Meg OHMS Terminal Voltage Range Resoluti on Accuracy Test Current Short circuit current 125V 0 10 0 125 4 000 M 0 001M 2 10 1mA load 125k 1mA 4 001 40 00 M 0 01M 2 10 40 01 400 0 M...

Страница 6: ...est leads On M Range and 400 BZ ACV DCV Connect the red test lead into the V terminal and the black lead into the COM terminal 2 2 Battery Check UP Replacement a As battery power is not sufficient LCD...

Страница 7: ...to the MIN if instant pressing once more it w illrecycle but exit if pressing 2 seconds again LOCK In the insulation resistance testing function press the LOCK button and then push down the TEST key...

Страница 8: ...nous with the primary display While testing the insulation resistance the symbol flashes frequently if the voltage is over 30V While testing the insulation resistance the symbol flashes frequently and...

Страница 9: ...rous or its voltage is low er than 30V it will enter into the formal testing process and brings the high voltage on the primary display the insulation resistance in M is indicated in phase w ith analo...

Страница 10: ...w ith the analog bar d When the impedance on circuit is below approximately 35 It w illindicate by a continuous beeper e The current is from 200 to 220mA while the tested resistance is 0 f The high v...

Страница 11: ...terminals or by opening the main sw itch If the main switch is used and the motor also has a starter then the starter must be held by some means in the ON position In the latter case the measured resi...

Страница 12: ...armature field coils and brush rigging by connecting one megohmmeter lead to each of them individually leaving the other connected to the grounded motor housing The above also applies to DC Gemerator...

Страница 13: ...from other equipment Check each conductor to ground and or lead sheath by connecting one megohmmeter lead to a ground and or lead sheather and the other megohmmeter lead to each of the conductors in t...

Отзывы: