Electrical Data Sheet
Model
ES-15
Phase Configuration
Three Phase 120/208V AC WYE/Delta
Maximum Line Voltage
208V AC
Maximum Power
15 kVar
Steps
5
Monitoring
PF, kVA, kVar, Volt, Current, KW, %THD-V
Internal Temperature & Capacitor Status
Accuracy
0.333 kVar each Phase, 1 Kvar three Phase
Frequency
60Hz
Protection
Capacitor Inbuilt Protection P2, capacitor short circuit 10,000A
Capacitor over current protection.
Equipment Protection
Internal design has adequate clearance and creepage distance
against line transients. MOVs not required.
Circuit breaker Required
60 Amp 3 pole
Low Losses
1.5 Watt each step
Human Protection
All High voltage shielded from contact.
Operating temperature range
40
o
C Ambient
Dimensions(L X H X D)
20” X 20” X 8.5” ( 500 x 500 x 210 mm) Metal Enclosure Type 1
Operating Life
Switching tested up to 25,000 times, 6,000 as per UL
Dielectric Strength
Tested up to 3.5 kV, 1.42 kV for 1 min. as per UL
Wire Gauge & Rating
6 AWG Str for Power, 18-22 AWG Str for CT, 10 AWG Str for Bonding
Unit Weight
28 kg (62 Pounds)