______________________________________________________________________________________ 

 

ES-15

 

              Field Installation Manual 

Connection Type#3 

Use this instruction  

If  60  Amp  circuit  breaker  is  unavailable  and  require  a  new  disconnect  switch  or 
other approved device. 
 

ES-15  unit  is  designed  for  use  with  Customer  Main  Breaker  Panel  Three  Phase 
120/208V AC WYE/Delta Connection, up to 600 Ampere.

 

Representative must purchase 60 Amp Blade-Fused Disconnect Switch     or                        
60 Amp Circuit Breaker for connection of ES-15 to Customer Main Breaker Panel. 

 

1.

 

Install  new  60  Amp  Blade-Fused  disconnect  or  External  Circuit  Breaker  switch  to  wall  or  existing 

backboard. Qualified Representative should note if codes allow for direct connection to bus bars in 

main breaker panel or requires installation of an additional sub panel. 

2.

 

Wire in rigid conduit between customer main breaker panel & external disconnect switch. Connect 

to ES-15 using 3/4‘’conduit. 

3.

 

Locate  earth  ground  connection  in  ES-15 and  connect  to  grounding bar  or  to  earth  ground  rod in 

main breaker panel. 

4.

 

For rest of connection follow the Connection type#1 on page 5. 

 
 
 
 
 

Содержание ES-15

Страница 1: ..._______________________ 1 ES 15 Field Installation Manual INDEX Important Instructions 2 Product Specifications 3 Unpacking Mounting 4 Connection Type 1 5 Connection Diagram 6 Connection Type 2 7 Connection Type 3 8 Electrical Data Sheet 9 Recommended Part List 10 ...

Страница 2: ...nstallation and all components of the installation must be UL listed UL approved and as per NEC code WARNING Celec manufacture components parts that can be used in a wide variety of industrial commercial applications The selection and application of Celec products remains the responsibility of the equipment designer or end user Celec accepts no responsibility for how its products may be incorporat...

Страница 3: ...p per phase Maximum kVar 14 6 Maximum Ambient Temperature 400 C Enclosure Type 1 Specified as per UL Nominal Current in CT Circuit is less then 100 mA May use 18 22 AWG Str Sol Connection Terminal Connection Type Size Wire Type Temperature Torque N m Lb in T1 Power Circuit 6 AWG CU 60 75o C 2 17 70 T2 CT Circuit 10 AWG Str Sol CU 60 75o C 0 5 7 Earthing Terminals Bonding Circuit 10 AWG Str Sol CU ...

Страница 4: ... during transportation 4 Install the Load Break Switch handle on the door 5 Do not use ES 15 in case of any Breakage or loose connections or Oil Spill inside MOUNTING CAUTION Indoor Use Only Type 1 Enclosure 1 Choose the dry and Clean Wall to Install the ES 15 taking care conduit connections from Bottom side Enclosure Size is 500 x 500 x 210 mm and weight 28kg 62 Pounds 2 Premark the Mounting hole...

Страница 5: ...of earth wire to main breaker panel ground rod Ensure all mechanical connections are secure and making full contact 1 13 Locate existing 3 Pole 60 Amp Circuit Breaker in the Main Breaker Panel Connect the wire L1 to Phase 1 of 60 Amp circuit breaker b Connect the wire L2 to Phase 2 of 60 Amp circuit breaker C Connect the wire L3 to Phase 3 of 60 Amp circuit breaker 1 14 Qualified Representative mu...

Страница 6: ...______________________________________________________________________________________ 6 ...

Страница 7: ...ith Customer Main Breaker Panel Three Phase 120 208V AC WYE Delta Connection up to 600 Ampere ES 15 units should be mounted with four appropriate sized fasteners before connect to Main Breaker Panel 1 Switch off the external handle of load break switch LBS using panel key open the door of ES 15 exposing connections 2 Remove existing 3 Pole breaker blanks and install new 3 Pole 60 Amp circuit Break...

Страница 8: ...h or 60 Amp Circuit Breaker for connection of ES 15 to Customer Main Breaker Panel 1 Install new 60 Amp Blade Fused disconnect or External Circuit Breaker switch to wall or existing backboard Qualified Representative should note if codes allow for direct connection to bus bars in main breaker panel or requires installation of an additional sub panel 2 Wire in rigid conduit between customer main br...

Страница 9: ...r short circuit 10 000A Capacitor over current protection Equipment Protection Internal design has adequate clearance and creepage distance against line transients MOVs not required Circuit breaker Required 60 Amp 3 pole Low Losses 1 5 Watt each step Human Protection All High voltage shielded from contact Operating temperature range 40oC Ambient Dimensions L X H X D 20 X 20 X 8 5 500 x 500 x 210 m...

Страница 10: ...nsor Megnelab SCT 1250 600 1 Wall Plug pin type Size 10 x 75 mm Any 4 1 2 Conduit Connector Any 4 1 2 Tube Conduit Any As required 3 4 Conduit Connector Any 4 3 4 Tube Conduit Any As required All the Parts used in installation must be UL recognized or UL listed NOTE Installation of material and workmanship at the customer s Main Breaker Panel shall be the responsibility of the qualified Electricia...

Отзывы: