background image

6. VERSIONS

DES-300E -

Temperature sensor can be mixed with relative humidity

sensor or lighting sensor or sunlight sensor

Order example::

Product symbol: 

DES-300E-T-H

T-H 

- temperature and relative humidity sensor

Sensor Type:

Temperature sensor (-20°C ... +70°C)

T

Temperature sensor (-20°C ... +70°C) with power supply 12VDC

T12

Relative humidity sensor ( 0% ... 100% RH)

H

Lighting sensor ( 0% ... 100% Lux)

L

Sunlight sensor ( 0% ... 100% SLux)

SL

7. SPECIFICATIONS

Parameters 

Data

Parameters of Temperature Sensor

Measuring range of temperature

-20°C ... +70°C

1-WIRE Transducer

DS18B20

Measuring accuracy of temperature  transducer

+/-0,5°C in the scope -10°C...+85°C

Temperature transducer resolution

12 bytes (0,06°C)

Parameters of Humidity Sensor

Measuring range of relative humidity

0%  ... 100% RH

Measuring accuracy of relative humidity

+/-3,50% RH

Parameters of Lighting Sensor

Measuring range of lighting

0%  ... 100% Lux

Measuring accuracy of lighting

+/-0,5% Lux

Parameters of Sunlight Sensor

Measuring range of sunlight

0%  ... 100% SLux

Measuring accuracy of sunlight

+/-0,5% Lux

General Parameters

Supply voltage

From 1-WIRE bus VDD=5VDC

or

from 12VDC stable power supply 

Max. power

10mW – 600mW (depend on version)

Protection from reverse power polarization

YES

Warning! for reverse power on is shorted VDD to GND 

Bus cabling

Recommended UTP 4x2x0.5 AWG24 twisted cable

Operating temperature

from -20°C to +70°C

Material

ABS

Protection degree

IP20

Dimensions

80 x 80 x 25 mm

Weight

0,05 kg

Storing and Transportation

Storage temperature

-20°C ÷ +70°C

Humidity

5 ÷ 95% - non-condensing

9

DES-300E

Содержание DES-300E

Страница 1: ...User manual DES 300E Digital environmental parameters sensor 1 io_des 300e_v1 00_en DES 300E Copyright 2001 2017 CEL MAR sp j...

Страница 2: ...2 APPLICATION 3 3 COOPERATION WITH OTHER 1 WIRE DEVICES 4 4 VIEW OF SENSOR 4 5 CONNECTION OF 1 WIRE BUS 5 5 1 CONNECTION TO 1 WIRE BUS SENSOR POWER SUPPLY FROM ADA 401WP 5 5 1 1 EXAMPLE OF CONNECTION...

Страница 3: ...merse device in water or no other liquid Do not put the fire opened on device sources candles an oil lamps and the like 1 3 CE LABEL CE symbol on organizing the company CEL MAR a conformity of the dev...

Страница 4: ...toring and control systems for environmental parameters ADA 401WP Measuring Module 1 WIRE to MODBUS RTU DNB 400 Passive 1 WIRE Bus Splitter DNB 215 Passive 1 WIRE Bus Splitter DNB 200 Passive 1 WIRE B...

Страница 5: ...nect the bus to terminal block described as below 5V powering the bus 5VDC 1 W 1 WIRE data transmission GND signal ground b after connection 1 WIRE bus to terminals 5V 1 W GND of DES 300E set the S1 s...

Страница 6: ...S485 MODBUS ADA I1040 ADAI9140 DES 300E T GND Rx 1 W VDD L RS232 USB RS485 MODBUS PE GND Tx B Tx A Rx GND Rx RS232 USB Vss Vss Unused twisted pair cables are connected together and connected to PE ele...

Страница 7: ...owering from additional power supply 1 W data transmission 1 WIRE GND signal ground b after connection 1 WIRE bus to terminals 12VDC 1 W GND of DES 300E set the S1 switch to 12V position Not applicabl...

Страница 8: ...S PE GND Tx B Tx A Rx GND Rx RS232 USB Vss Vss 230V V N V 12V ADA 401WP DES 300E T H DES 300E T H GND NC VDD 12V 1 W GND NC VDD 12V 1 W GND NC VDD 12V 1 W Computer with Free SCADA or PLC with support...

Страница 9: ...s 0 06 C Parameters of Humidity Sensor Measuring range of relative humidity 0 100 RH Measuring accuracy of relative humidity 3 50 RH Parameters of Lighting Sensor Measuring range of lighting 0 100 Lux...

Страница 10: ...10 DES 300E...

Страница 11: ...11 DES 300E...

Страница 12: ...c Converters 1 Wire ETHERNET Wi Fi digital sensors as temperature humidity pressure illumination power supply Please express your opinion by e mail or phone on this product and advise us how we can sa...

Отзывы: