background image

up to 5kV= optoisolation between FO and Current Loop in the signal channels,

Connection Current Loop network and power supply via screw terminal block,

Connection Fiber Optic network via fibres optic connectors type: ST® *(850nm), SC(850nm), SMA(650nm),

Protection against power supply reverse connection,

Implemented overvoltage protection on Current Loop network,

DIN 43880 standard - mounting in typical electro-installation unit,

Rail mounting according to DIN35 / TS35 standard,

Dimensions of casing contour (W x H x D) 53mm x 90mm x 62mm,

2.2. DESCRIPTION

Fiber Optic ADA-7020 is a device used to connect units with Current Loop interface without interfering with the data format. The use of
fiber optics provides complete isolation between connected devices and resistance to interference on the transmission bus. The fiber
connection is implemented by a line consisting of two fibers - one fiber for the TX signal and one for RX signal.
The converter is equipped with screw terminal block for Current Loop and power connections. To Current Loop bus built on the ADA-
7020 can be connected two converters operating in full duplex or half duplex point-to-point and 15 converters operating in half duplex
mode topology multipoint.
Surge protection on each line Current Loop have been based on diodes and fuses.
This converter has internal, low energy surge protection for each Current Loop lines, however it is recommended to use the external
lightning arresters (typical protection of telephone line) for the lightning protection of lines. 

Fig. 1. View of ADA-7020

2.3. CURRENT LOOP TRANSMITTER

ADA-7020 converter has active current loop transmitter, on the base power source generate c/- 20mA or 0-20mA (depend on
converter's version). The transmitter has short circuit protection on TX+ and TX- lines.  

4

ADA-7020

62mm

Power Supply

10 - 30 VDC

9

0

m

m

53mm

1

0

m

m

1

7

m

m

Multimode Fiber Optic

PWR

TX

RX

ADA-7020

FIBER OPTIC to CURRENT  LOOP

CONVERTER

CL

T

X

R

X

N

C

N

C

N

C

T

X

 +

T

X

 -

R

X

 +

R

X

 +

*

R

X

 -

(CURRENT LOOP)

V

 -

V

 +

10 – 30 

VDC

Current Loop

Interface

Содержание ADA-7020

Страница 1: ...User manual ADA 7020 Multimode Fibre Optic to Current Loop Converter 1 io_ada 7020_v3 19_en ADA 7020 Copyright 2001 2020 CEL MAR sp j...

Страница 2: ...6 PACK CONTENTS 3 2 PRODUCT INFORMATION 3 2 1 PROPERTIES 3 2 2 DESCRIPTION 4 2 3 CURRENT LOOP TRANSMITTER 4 2 4 CURRENT LOOP RECEIVER 5 2 5 ISOLATION 5 3 INSTALLATION 5 3 1 ASSEMBLING 5 3 2 CONNECTION...

Страница 3: ...disable from the supply network is only after disconnecting the power supply circuit voltage Do not carry out the assembly or dis assembly of the device if it is enabled This may result to short circu...

Страница 4: ...and one for RX signal The converter is equipped with screw terminal block for Current Loop and power connections To Current Loop bus built on the ADA 7020 can be connected two converters operating in...

Страница 5: ...lded cables which shield can be connected to the earthing on one end of the cable arrange signal cables in the distance not shorter than 25 cm from powering cables apply cable of adequate cross sectio...

Страница 6: ...m DC power supplies to device must not be longer than 3m Observe the polarity connect positive of DC power supplies to V and negative end to V screw terminal block ADA 7020 has the protection from opp...

Страница 7: ...CATION TECHNICAL DATA PARAMETERS Interface Fibre Optic Current Loop Connector ST type transmitter and receiver for an optical wavelength from 792nm to 865nm SC type transmitter and receiver for an opt...

Страница 8: ...ing Storage temperature 40 70 C Casing Dimensions 53 x 90 x 62mm Material ABS PC Degree of casing protection IP40 Degree of terminal protection IP20 Weight 0 10 kg According to standards DIN EN50022 D...

Отзывы: