3.3.3. GND TERMINALS CONNECTION 

Connection of GND terminals of RS485/422 interfaces, devices connected to RS485/422 bus, should be done in the case of a 

potential difference of the signals grounds on interfaces RS485 / RS422, which prevents proper data transmission.

Cannot connect to the GND terminal - cables screens, PE circuit of electrical installation, signals grounds of other devices. 

3.3.4. LINE TERMINATION Rt 

The application of Line Termination (terminator) Rt = 120 ohms will reduce electrical reflection in data line at high baud rate. It is not 

needed below 9600Bd. Should be used the Line Termination resistor if the distance is over 1000m @ 9600Bd or 700m @ 19200Bd, 
and if the disturbance in transmission will appear. Example connection of Rt are shown on the figures below. Four Rt=120 

, 0,25W 

are delivered with the converters.

3.4. POWER SUPPLY CONNECTION 

We recommend for powering of ADA-4040PC8 to use individual, stabilized power supply with output voltage from 10 V= to 30V=, min. 

nominal power 2W, e.g. HDR-15-24. Power cable from DC power supplies to device can not be longer than 3m. Should connect 

positive (+) end of DC power supplies to V+ device terminal and negative (-) end to V- on terminal block. 

ADA-4040PC8 has protection against power supply reverse connection.

4. START-UP

The converter can be power on after properly connection according to section above.

If   after   connection   power   supply   on   front   panel   will   not   light   green   led   PWR,   check   correctness   of   power   supply   connecting

(polarization). When data is present the LEDs Tx and Rx should blink

ATTENTION! 

AT BAUD RATE ABOVE 38.4 KBPS OF THE TX DIODE, MORE POORLY WILL LIGHT RX DURING THE DATA TRANSFER 

4.1. DESCRIPTION OF SIGNALLING LEDS 

LED 

Description 

PWR 

Signalling of Power Supply

RX 

Signalling of data receiving through ADA-4040PC8 from RTU RS485/RS422 port.

TX 

Signalling of data transmitting from ADA-4040PC8 through RTU RS485/RS422 port.

Yellow LED by SW1 

Not light – signalling of normal operating mode (RUN)
Blinking at frequency 1 Hz - signalling of configuration mode or data flow of software to the converter.
Blinking at frequency 2 Hz - signalling of factory default mode
Lit continuously – signalling of emergency firmware update

4.2. TROUBLESHOOTING 

Problem 

Solutions 

PWR LED is not lit

Check polarization and parameters of connected power supply.

Rx LED lights 

continuously

RS485(4W) /422 network. Wrong polarization on terminals: Rx+, Rx- RTU port; change polarization.

No transmission

Tx LED is blinking

RS485(4W) / RS422 network. Check correctness of connection to terminals Tx, Rx; according to 

point 3 and the converter configuration.

5. CONFIGURATION 

5.1. OPERATION MODE 

ADA-4040PC8 converter can operates in and few modes: 

RUN, 

configuration, 

factory default, 

emergency firmware update mode, 

Those modes can be set by use SW1 located by terminal block JCT port. To set the switch section, should remove terminal cover 

marked as SW1 and make the appropriate settings by the use a small, flat screwdriver.

All available adjusting the SW1 switch are shown in table below.

Operation modes 

SW1 - 1  SW1 - 2 

Mode 

Yellow LED 

OFF

OFF

Run

Not lit

ON

OFF

Configuration

Flashes every 1 sec.

OFF

ON

Factory default

Flashes every 0,5 sec. 

ON

ON

Emergency firmware update

Continuous light

7

ADA-4040PC8 

Содержание ADA-4040PC8

Страница 1: ...User manual ADA 4040PC8 VIRAP JCT ASCII to MODBUS RTU Protocol Converter 1 ADA 4040PC8 Copyright 2001 2021 CEL MAR io_ada 4040pc8_v1 02_en...

Страница 2: ...ING 7 5 CONFIGURATION 7 5 1 OPERATION MODE 7 5 2 CONFIGURATION BY USING ADACONFIG 8 5 3 FIRMWARE UPDATE 9 5 4 EMERGENCY FIRMWARE UPDATE 10 5 5 FACTORY DEFAULT 10 6 DATA TRANSMISSION DIAGNOSTICS 10 7 O...

Страница 3: ...the power supply circuit voltage Do not carry out the assembly or disassembly of the device if it is enabled This may result to short circuit and damage the device The device can not be used for appli...

Страница 4: ...reliability ADA 4040PC8 supports asynchronous data transmission with baudrate up to 230 4 kbps through two or one pair of twisted pairs connected to screw terminals The device for its operation uses...

Страница 5: ...e the rail upper part of the cover then press bottom part it hear characteristic Click sound 3 2 COMPUTER CONNECTION To connect ADA 4040PC8 to computer is needed additional converter e g ADA I9141 USB...

Страница 6: ...bus and JCT1 controller to ADA 4040PC8 6 ADA 4040PC8 RS485 RS422 connector RS485 4W BUS 19200Bd 8 N 1 MODBUS RTU MASTER MODBUS RTU DEVICE SLAVE 1 MODBUS RTU GND Rt Rt Rx Rx Tx A Tx B RS485 2W 9600Bd 8...

Страница 7: ...the LEDs Tx and Rx should blink ATTENTION AT BAUD RATE ABOVE 38 4 KBPS OF THE TX DIODE MORE POORLY WILL LIGHT RX DURING THE DATA TRANSFER 4 1 DESCRIPTION OF SIGNALLING LEDS LED Description PWR Signal...

Страница 8: ...nd in the field Address enter the MODBUS RTU converter address from the RTU port 4 setting the address of the connected VIRAP JCT device to the JTC RS485 port Mapped Address field range 1 99 In the se...

Страница 9: ...e the software delivered by manufacturer The Select File window will open fig below and select the bin file then click Open software will be load to ADAConfig buffer storage and will be checked If the...

Страница 10: ...tes 4 4 Set SW1 microswitch mode as in the table below SW1 1 SW1 2 OFF ON Disconnect the power and after while connect again the power After that will be loaded the factory default setting to the conv...

Страница 11: ...IMPLEMENTATION OF THE MODBUS RTU PROTOCOL MODBUS protocol frames with the CRC error are rejected by the converter JCT ASCII protocol frames with a checksum error are rejected by the converter In case...

Страница 12: ...000 0 2000 1000 EV Event value 15 30135 Read 0 1 0 1 1 CM Communication mode 16 30136 Read 0 1 0 1 1 AM Automatic manual mode 17 30137 Read 0 1 0 1 1 SR Execution stop mode 18 30138 No Read 0 100 0 1...

Страница 13: ...saved to regular type variable float and then divide it by the DW factor Fragment of code in C language VS6 0 presenting above algorithm short int siMeasureReg float fMeasureVal fMeasureVal float siMe...

Страница 14: ...ave values to 16 bits of the MODBUS register of the ADA 4040PC8 converter The saved value in the register is processed and transmitted to the JCT controller MODBUS registers are in the format of the 1...

Страница 15: ...1 Byte 40 01 to F7 01 Code of the function 1 Byte 86 02 Error code 1 Byte 01 unknown function 02 unknown data address 03 unknown amount of data 04 JCT controller is not responding is not connected or...

Страница 16: ...ate from RTU of ports RS485 RS422 TX yellow LED date transmission through RTU of ports RS485 RS422 Electrical Parameters Power requirements 10 24 30 V DC Power Cable Recommended length of power cable...

Страница 17: ...data transmission converters with interface RS232 RS485 RS422 USB Current Loop Fibre Optic Converters and Ethernet or Wi Fi Please contact us to tell how you like our products and how we can satisfy y...

Отзывы: