The actual measurement value expressed in [V] AC is obtained from the read register according to the above algorithms, using the
appropriate factor value 

DW 

for register 

Uac

 (see the 

Table of divider values DW 

above).

Uac

 = 0x00DF => 223/1 => 223 [V] AC

8.3.1.7. READOUT OF CURRENT VALUE Iac ALTERNATING VOLTAGE NETWORK, 

CONNECTED TO INVERTER [4X / 3X-REFERENCES]

The measurement value of network current alternating voltage connected to the inverter, readout from 16-bit register 

Iac

 MODBUS-

RTU (see p.8.1.) is presented in the format integer 16-bit with sign (in C/C++ type short int).

Query of network current 

Iac

 from registry address 40007 / address 30007

11-03-00-06-00-01-CRCLo-CRCHi
11-04-00-06-00-01-CRCLo-CRCHi

Readout of network current 

Iac

 from registry address 40006 / address 30006

11-03-02-00-DF-CRCLo-CRCHi
11-04-02-00-DF-CRCLo-CRCHi

In respond the network current 

Iac

 is presented as 2-byte with values: 0x00DF .

The actual measurement value expressed in [A] AC is obtained from the read register according to the above algorithms, using the
appropriate factor value 

DW 

for register 

Iac

 (see the 

Table of divider values DW 

above).

Iac

 = 0x00DF => 223/100 => 2,23 [A] AC

8.3.1.8. READOUT OF POWER VALUE Pac ALTERNATING VOLTAGE NETWORK OF 

INVERTER [4X / 3X-REFERENCES]

The measurement value of network power alternating voltage connected to the inverter, readout from 16-bit register 

Pac

 MODBUS-

RTU (see p.8.1.) is presented in the format integer 16-bit with sign (in C/C++ type short int).

Query of inverter power network 

Pac

 from registry address 40008 / address 30008

11-03-00-07-00-01-CRCLo-CRCHi
11-04-00-07-00-01-CRCLo-CRCHi

Readout of inverter power network 

Pac

 from registry address 40008 / address 30008

11-03-02-00-06-CRCLo-CRCHi
11-04-02-00-06-CRCLo-CRCHi

In respond the inverter power network 

Pac

 is presented as 2-byte with values:  0x0006 .

The actual measurement value expressed in [W] AC is obtained from the read register according to the above algorithms, using the
appropriate factor value 

DW 

for register 

Pac

 (see the 

Table of divider values DW 

above).

Pac

 = 0x0006 => 6/1 => 6 [W] AC

8.3.1.9. READOUT OF ENERGY VALUE Eac TRANSFERRED TO ALTERNATING VOLTAGE 

NETWORK, CONNECTED TO INVERTER [4X / 3X-REFERENCES]

The measurement  value  of  energy transferred  to alternating  voltage  network  connected  to the  inverter,  readout  from  two  16-bit
registers 

Eac

 MODBUS-RTU (see p.8.1.) is presented in the format integer 32-bit with sign (in C/C++ type int).

Query of energy transferred to network 

Eac

 from registry address 40009 / address 30009

11-03-00-08-00-02-CRCLo-CRCHi
11-04-00-08-00-02-CRCLo-CRCHi

Readout of energy transferred to network 

Eac

 from registry address 40009 / address 30009

11-03-04-00-00-00-DF-CRCLo-CRCHi
11-04-04-00-00-00-DF-CRCLo-CRCHi

In respond the energy transferred to network 

Eac

 is presented as 4-byte with values: 0x000000DF .

The actual measurement value expressed in [kWh] AC is obtained from the read register according to the above algorithms, using the
appropriate factor value 

DW 

for register 

Eac

 (see the 

Table of divider values DW 

above).

Eac

 = 0x000000DF => 223/100 => 2,23 [kWh] AC

19

ADA-1040PC3

Содержание ADA-1040PC3

Страница 1: ...User manual ADA 1040PC3 SunMaster to MODBUS RTU converter 1 io_ada 1040pc3_v1 06_en Copyright 2001 2017 CEL MAR sp j ADA 1040PC3...

Страница 2: ...8 1 2 REGISTERS ACTUAL VALUES MEASUREMENTS AND CONDITION INVERTER READOUT BY FUNCTION 03 4X REFERENCES HOLDING REGISTERS 14 8 2 FRAME STRUCTURE OF MODBUS RTU PROTOCOL 14 8 3 USED FUNCTIONS OF MODBUS R...

Страница 3: ...to short circuit and damage the device The device can not be used for applications that determine human life and health eg Medical 1 3 CE LABEL The CE symbol on the device CEL MAR means compatibility...

Страница 4: ...and support the asynchronous transmission data with baud rate 230 4 kbps ADA 1040PC3 has DB 9F connector for connecting PC Link RS232 interface to Soladin and screw terminal block for connection of RS...

Страница 5: ...ables in the distance not shorter than 25 cm from powering cables apply cable of adequate cross section due to voltage drops for converter powering use suppression filters for powering converters that...

Страница 6: ...x PC or RS232 device 5 2 3 GND Tx A Tx B Rx Rx ADA 1040PC3 Tx 2 Rx 3 GND 5 5 2 3 DB 9F socket RS485 422 connector DB 9F RS232 connector DB 9M plug RS cable DB 9M RS232 connector USB DB 9M RS232 connec...

Страница 7: ...ON OF INVERTER WITH SOLADIN INTERFACE TO RS485 4W MODBUS RTU BUS Fig 7 Example connection of SOLADIN inverter by the use of ADA 1040PC3 to RS485 4W 4 wire bus 7 ADA 1040PC3 RS485 RS422 connector RS485...

Страница 8: ...0 W 5 0 25W are delivered with the converters 3 6 POWER SUPPLY CONNECTION To connect power supply to the converter should have DC power supplies regulated output voltage from 10 V to 30V min nominal p...

Страница 9: ...DA 1040PC3 converter can be made by the use of ADAConfig Software selling with converter To make the configuration connect converter to computer and power supply If after power on the front panel is n...

Страница 10: ...ode as in the table below SW1 1 SW1 2 OFF ON Disconnect the power and after while connect again the power After that will be loaded the factory default setting to the converter internal registers Afte...

Страница 11: ...t continuously and the converter will be in Emergency Firmware Update mode Now follow the description in the above point After successful software update set microswitch SW1 to the run mode as shown i...

Страница 12: ...ace should connect to RS485 RS422 port RS485 MODBUS RTU bus Frames of MODBUS protocol having the errors CRC are rejected by the converter Frames of SunMaster Soladin having the errors CRC are also rej...

Страница 13: ...atus R 16 bit register 30003 2 UsolH UsolL 16 bit solar panel voltage DC measurement R 16 bit register 30004 3 IsolH IsolL 16 bit solar panel current DC measurement R 16 bit register 30005 4 FacH FacL...

Страница 14: ...16 bit network power measurement AC R 16 bit register 40009 8 Hi 0x00 EacH Low R 16 bit register 40010 9 EacM EacL 24 bit energy counter kWh R 16 bit register 40011 10 TempH 0x00 TempL 8 bit inverter...

Страница 15: ...n h 60 Time from reclosing Trec s 1 Network impedance measurement Rac W 100 Algorithm 1 Readout register is saved to regular type variable float and then divide it by the factor DW Fragment of code in...

Страница 16: ...ion 0x03 0x04 are used for readout of status and measurement values from the INVERTER The measurement values readout form MODBUS RTU register is presented by two 16 bit registers The registers with th...

Страница 17: ...work energy meter Eac from registry address 40009 address 30009 11 03 04 00 00 0B 90 CRCLo CRCHi 11 04 04 00 00 0B 90 CRCLo CRCHi In respond the value of AC network energy meter Eac is presented as 4...

Страница 18: ...NCY VALUE Fac ALTERNATING VOLTAGE NETWORK CONNECTED TO INVERTER 4X 3X REFERENCES The measurement value of frequency alternating voltage network to inverter readout from 16 bit register Fac MODBUS RTU...

Страница 19: ...in C C type short int Query of inverter power network Pac from registry address 40008 address 30008 11 03 00 07 00 01 CRCLo CRCHi 11 04 00 07 00 01 CRCLo CRCHi Readout of inverter power network Pac f...

Страница 20: ...nverter s running time Ton from registry address 40012 address 30012 11 03 00 08 0B 02 CRCLo CRCHi 11 04 00 08 0B 02 CRCLo CRCHi Readout of inverter s running time Ton from registry address 40012 addr...

Страница 21: ...O 1 YES 6 Network frequency Fac Low 0 NO 1 YES 7 Inverter on 0 NO 1 YES 7 Inverter temperature High 0 NO 1 YES 9 RS232 INTERFACE PIN DESCRIPTION OF DSUB 9F DCE SOCKET Pin Signal Description ADA 1040PC...

Страница 22: ...yellow LED data transmission through RS485 RS422 interface Electrical Parameters Power requirements 10 24 30 V DC Power Cable Recommended length of power cable up to 3m Power 2W Protection from rever...

Страница 23: ...23 ADA 1040PC3...

Страница 24: ...munications products in the world such as data transmission converters with interface RS232 RS485 RS422 USB Current Loop Fibre Optic Converters and Ethernet or Wi Fi Please contact us to tell how you...

Отзывы: