LOCATION

  

The heater can be positioned in the corner of a ceiling but for better heat distribution at least 600mm from 

each wall is preferable.

The unit should not be positioned over desks, counters or high level display racking wherever a constant flow 

of heated air may be uncomfortable or cause overheating of equipment.

If required the unit can be covered with non flammable insulating material to maintain the integrity of the 

ceiling insulation.

The heater must be installed at a minimum of 2 m and a maximum of 3m from the floor.

CONTROL

Remote Switch

Thermostat

 

The Remote Switching Unit allows ON/OFF, Fan only with 2.25 or 4.5 kW.

A thermostat of 25A rating can be connected in the power supply to the Remote switch thus switching the 

unit off totally when set temperature is reached. Alternatively a thermostat and contactor can be used.

CONTENTS

Remove from carton and check contents ;

- heater unit

- ODH-RSW three switch control unit

5mm fixing holes

Heater cover

Connection cover

SAFETY

The correct procedures for working at height must be adopted when installing this heater.

The heater must be installed by a suitably qualified person in accordance with current regulations.