ObjectC 100

  Programmer's 

Guide

 

 

8

 

http://csa.cedes.com/ 

© CEDES Safety & Automation AG

 

2.2.5.6.

 

Get number of beams (18 [12 Hex]) 

Indicates the number of beams in the attached light curtain. 

 
Table 13: Command 12 Hex 

Command 18 [12 Hex] 

Response 19 [13 Hex] 

 Bit 

Value 

 

Bit 

Value 

Byte 3 

0-7 

0-254 

Number of used beams  

 

Byte 4 

0-7 

0-254 

Number of physical beams 

Byte 3 - 8 

0 - 7 

0  

(not used) 

Byte 5-8 

  Not 

used 

Note: The used beams count from "fb_offset" to "lb_offset", considering the pitch factor

 

2.2.5.7.

 

Trigger (1 standard scan) (20 [14 Hex]) 

When a standard scan is triggered, the object height will be ascertained by monitoring the condition of the entire 
light curtain. Only one scan will be carried out and then the beam information will automatically be sent enclosed 
in response 21. 

 

Table 14: Command 20 Hex 

Command 20 [14 Hex] 

Response 21 [15 Hex] 

 

Bit Value

 

 

Bit Value 

Byte 3 

0-7 

No beam interrupted 

 

1-254 

First interrupted beam 1) 

Byte 4 

0-7 

No beam interrupted 

 

1-254 

Last interrupted beam 1) 

Byte 5 

0-7 

No beam interrupted 

 

1-254 

Maximum number of interrupted beams 

Byte 6 

0-7 

1-254 

Number of used beams 1) 

Byte 7 

0-1 0 

No 

overheight 

 1  Overheight 

Byte 3 - 8 
 
 

0-7 0  Not 

used 

 
 

Byte 8 

0-1 00 

No 

overhang 

 01 Front 

overhang 

 10 Back 

overhang 

 

11 

Front and back overhang 

Note 1) The used beams count from "fb_offset" to "lb_offset", considering the pitch factor.

 

 

2.2.5.8.

 

Start permanent standard scan (22 [16 Hex]) 

In the event of a standard height measurement (standard scan) the object height will be ascertained by 
monitoring the condition of the entire light curtain. Continuous scans will be executed and the lowest and highest 
interrupted beams will be ascertained until the ‘stop’ command is received. This command lends itself well for 
measuring various object types, even those that do not start at beam one or those with open spaces. 
Sending command 22 anew, before sending command 24, will reset the scan counter and reset the status values 
noted in command 24 (see 2.2.5.9) 
 

Table 15: Command 16 Hex 

Command 22 [16 Hex] 

Response 23 [17 Hex] 

 

Bit Value

 

 

Bit Value 

Byte 3 - 8 

0-7 0  Not 

used 

Byte 3-8 

0-7 0  Not 

used 

 

Содержание ObjectC 100 CAN

Страница 1: ...NT NOTICE FOLLOW THE INSTRUCTIONS GIVEN IN THIS MANUAL CAREFULLY FAILURE TO DO SO MAY CAUSE CUSTOMER COMPLAINTS AND SERIOUS CALL BACKS KEEP INSTRUCTION MANUAL ON SITE OBJECTC 100 OBJECT100 SYSTEMS ARE...

Страница 2: ...42 2A Hex 13 2 2 5 19 Restart 44 2C Hex 14 2 2 5 20 Get beam status with light curtain status 100 64 Hex 14 2 3 Extended CAN mode 14 2 3 1 Boot up message 15 2 3 2 Watchdog message 15 2 3 3 Initializa...

Страница 3: ...ll as consulting the valid laws and regulations at the time of installation Should these instructions not be followed or only partially this may lead to a premature malfunction of the system The insta...

Страница 4: ...e parameter determines if a status telegram 1 01 Hex is sent if 1 The light curtain status changes interrupted not interrupted A telegram is sent if all beams are uninterrupted or a light beam is inte...

Страница 5: ...tain status Data Byte 3 8 Data which must be transmitted with a command This command delays the response times according Operation manual Part No 104 906 Chapter 11 2 Table 7 ObjectC 100 CAN response...

Страница 6: ...1 Emitter and receiver have different beam numbers or no light curtain connected 3 0 No overheight 1 Overheight detected 4 5 00 No overhang 01 Front overhang 10 Back overhang 11 Front and back overha...

Страница 7: ...ested Table 11 Command 06 Hex Command 6 06 Hex Response 7 07 Hex Bit Value Bit Value Byte 3 0 7 0 Light curtain okay 1 Light curtain defective Byte 3 8 0 7 0 not used Byte 4 8 0 7 0 Not used 2 2 5 5 G...

Страница 8: ...ted 1 254 Last interrupted beam 1 Byte 5 0 7 0 No beam interrupted 1 254 Maximum number of interrupted beams Byte 6 0 7 1 254 Number of used beams 1 Byte 7 0 1 0 No overheight 1 Overheight Byte 3 8 0...

Страница 9: ...the pitch factor 2 2 5 10 Get scan counter 26 1A Hex The responses to this command contain the number of light curtain scans which have been made since the last command start stop permanent scan comma...

Страница 10: ...verhang with time delay Bit 2 1 Sensor Overhang Bit 3 1 Handle zones Bit 4 1 Handle Potentiometers Bit 5 Not used Bit 6 1 Handle Teaching button Bit 7 Not used See Chapter 4 9 See Chapter 4 10 See Cha...

Страница 11: ...s 1 This mode may cause a high telegram frequency and may cause problems with the Bus communication 2 Select if potentiometer is active or values set by parameter 63 65 3 Delay time 1 n x 13 1 ms 10 m...

Страница 12: ...factor 2 Overhang front means that an overhang is detected as the tray is pulled into the light curtain area 3 Overhang back means that an overhang is detected as the tray is pulled out of the light...

Страница 13: ...verify the response Use command 100 64 Hex instead 2 2 5 17 Get zone status 40 28 Hex This command is a simple way to get the status of a certain zone The zone can be defined by setting a first beam a...

Страница 14: ...m interrupted 7 Beam x 31 Byte 7 0 Beam x 32 0 Beam not interrupted 1 Beam interrupted 7 Beam x 39 Byte 8 0 0 Light curtain free 1 Light curtain interrupted 1 0 Light curtain state not changed 1 Light...

Страница 15: ...x Status Remark Id Std 0764 Hex Address Offset 0764 0765 etc up to 0773 Hex see chapter 6 4 Operation Manual Table 32 Watchdog state State 0 Boot up 4 Stopped 5 Operational 127 Pre operational 2 3 3 I...

Страница 16: ...see chapter 1 1 1 The response to this command sends for each sector of the X axis one bit indicating 0 for not interrupted and 1 for interrupted Table 38 Command 40 Hex Command 64 40 Hex Response 65...

Страница 17: ...ght curtain carries out a measurement effects the result The following chapters describe these effects The event mode is activated using the following parameters Table 40 Settings for event mode Param...

Страница 18: ...eters Table 42 Parameters for periodic mode Parameter Value n Description 75 4B Hex Periodic measuring 3 255 Periodic mode active with time constant tp 77 4D Hex Event measuring 0 Event mode inactive...

Страница 19: ...in Figure 5 with telegram 65 41 Hex and 67 43 Hex Minimum refers to the lowest interrupted beam number and maximum refers to the highest interrupted beam In this case objects that are too small or th...

Страница 20: ...he ObjectC 100 CAN controller is carried out thus Table 44 CAN commands for the configuration of the example above Byte Command Par Value Add ress DLC 1 2 3 4 5 6 7 8 Deactivation of periodic mode 28...

Страница 21: ...06 Inverted Address Command High byte Command Low byte Data Data Data Data Data Data ETX 03 Table 47 RS485 command example Hex Direction Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Byte7 Byte8 Master PLC to O...

Страница 22: ...Byte 8 Data 00 0000 0000 ETX 03 Hex 0000 0011 3 1 4 Timing RS485 Example for a Baud rate of 19 200 Baud and 1 Stop bit tpd tquestion tanswer Question Master Light curtain Answer Light curtain Master...

Страница 23: ...sses 0 15 Parity None Protocol None Stop bits 1 Baud rates 2 400 Baud 9 600 Baud 19 200 Baud 57 600 Baud 4 Advanced Features 4 1 Light curtain design Applications like height measurement require infor...

Страница 24: ...beam counting direction Beam 1 first beam is located at the physical end of the light curtain inverted Figure 10 Object100 beam definitions and beam counting direction Table 51 Reference to Figure 10...

Страница 25: ...point is defined as the end of the red light curtain housing see Figure 11 Standard beam counting direction Reverse beam counting direction Figure 11 Example of a 25 mm pitch Object100 light curtain...

Страница 26: ...nimal position of the object hmax Max position of the object before the next beam state is active b Height of the aperture 8 mm p Pitch 10 or 25 mm Figure 12 a Object is not recognized from element at...

Страница 27: ...7 Blanked beams The Object100 can be mounted behind a frame e g on a conveyor belt see Figure 14 Therefore the top and or bottom beams may be physically blocked By defining the first beam offset fb_o...

Страница 28: ...ight 1 0 0 1 1 Goods with height 2 0 1 1 1 Goods with height 3 1 1 1 1 Goods with height 4 Zones can be defined as overlapping and zones may contain as few as one beam or as many as all beams Figure 1...

Страница 29: ...output signal if the transported goods exceed a certain height This is easily done with the Object 100 light curtain by defining the beam oh Beam oh defines a beam which when it or any higher beam is...

Страница 30: ...arrier zone CZ and goods zone GZ When a beam in the goods zone is interrupted at least one beam from the carrier zone must also be interrupted otherwise the overhang output will be activated If a cert...

Страница 31: ...wed is adjusted by simply altering the front and back sensors physical distance to the light curtain When the carrier interrupts the front sensor the sensor sends a negative slope signal to the Object...

Страница 32: ...hold Depending on the hardware and the configuration the ObjectC 100 provides a function whereby the outputs Out 1 and Out 2 J12 will be held regardless of the status of the light curtain This functi...

Отзывы: