9
For the mounting and op-
eration of electrical ap-
paratus, the respective
national safety regulations
(e. g. equipment safety law for
Germany) as well as the general
rules of engineering will have to
be observed.
Prior to installation turn off all
power supplies and secure against
unauthorized switching!
Pay attention to a tight fit of the
terminal screws! Unused cable
entries are left with their locking plug
fitted (IP protection).
4. Installation
SL 3301 CG/SL 3301
r
Dismount lamp.
r
A slotted screw driver is
inserted into the lateral
recess on the cover to
remove the cover.
r
Remove electronic
ballast (EVG); turn EVG
counterclockwise until
latch can be unlocked.
r
While installed into
recessed ceilings: effective
aperture Ø 112 mm.
Insert wiring through the
enclosure.
r
Fix enclosure.
r
Connect mains to terminals
L (U), N (0) (fig. 4).
r
Adress luminaire (see
chapter 5),
r
Insert EVG; turn EVG
clockwise until it click into
place.
r
close cover.
r
Insert lamp.
r
Mark luminaire.
RZ 3301 CG/RZ 3301
See SL 3301... Prior to fixing
the mounting plate for the
Exit-cube has to be slipped
onto the enclosure.
r
Set Exit-cube onto
mounting plate and rotate
to fix to the bayonet of the
mounting plate.
r
Mark luminaire
5. Addressing
Before fitting the screen or bowl,
the addressing of the individual
luminaires will have to be per-
formed. To do so, the desired
address (1 - 20) is set on the
address switch by means of a
suitable screw driver (Arrowhead
to No., fig. 5, 6, 7). If the luminaire
should not be monitored the code
0/0 has to be selected.
The luminaires SL/RZ 3301 is not
equipped with monitoring circuit
and will not be addressable.
6. Function test
After complete installation a func-
tional test of the whole system
is reqired.
7. Servicing /Mainte-
nance
Observe the relevant national reg-
ulations which apply to the main-
tenance, servicing and check of
electrical apparatus (in Germany
DIN VDE 0105, part 9)! On condi-
tion of an appropriate operation
and of observing the mounting
instructions and environmental
conditions, no permanent servic-
ing will be required.
For replacement of the lamp see
chapter 4 “Installation“
8. Disposal / Recycling
When a defective apparatus
is disposed of, the respective
national regulations on waste dis-
posal and recycling will have to
be observed. Plastic parts have
been provided with respective
symbols.
fig. 5
Switch 1 Switch 2
fig. 6
Address switch 1
Address switch 2
Luminaire address
0
0
Monitoring off
0
1
1
0
2
2
...
...
...
1
0
10
1
1
11
...
...
...
...
...
...
2
0
20
2
1
not permissable
...
...
2
9
not permissable
fig. 7
We reserve the right to carry
out technical changes!