10.3 Fan replacement
The fan’s life is approximately 60,000 (Sixty thousand) hours. The inverter modules have fan runtime meters and fan
failure alarm. Fan failure can result from the failing fan or driver circuit.
•
Let the module rest at least five minutes before initiating work.
•
The inverter front cover must be removed. Use a flat screwdriver, release all the four latches on side of the
module and remove the front cover.
•
Disconnect the fan supply cord and remove the fan.
•
Replace with a new fan and connect the supply cord.
•
Fix the front cover and make sure all the four latches are locked.
•
Insert the module in corresponding slot in the shelf in accordance with section 10.1.2, page 30.
•
Check the fan for operation.
•
Access T2S ETH and reset the fan run time alarm. Refer to T2S ETH user manual for more details.
Inserting/removing/replacing modules
31