ELECTRICAL CONNECTION 

  The installation of  this appliance and the connection to the electrical network should be 

entrusted  only  to  an  electrician  who  operates  in  conformance  with  the  normative 
regulations. 

  Protection against the parts under tension must be ensured after installation. 

  The rating plate for this appliance is on the hob casing near the connection box. 

  The connection to the mains must be made using a fixed fused spur with a contact distance 

of at least 3 mm. 

  The electrical circuit must be separated from the network by adapted devices, for example: 

circuit breakers, fuses and/or isolators. 

  The  isolation  switch/fused  spur  must  be  accessible  in  accordance  with  the  installation 

regulations. 

  The mains cable must be positioned so that it does not touch any of the hot parts of the 

hob or even. 

 

Caution! 

This appliance must only be connected to a network 230 V~ 50/60 Hz. 
Always connect the earth wire. 
Respect the connection diagram. 
The green / yellow wire corresponds to the earth wire, the blue wire corresponds to the neutral 
wire and the brown wire corresponds to the live/phase. 
 

* calculated with the simultaneous factor following standard TN 60 335-2-6 

Connection of the hob 

Setting up the configuration: 
For the various kinds of connection, use the brass bridges which are in the box next the terminal 

 

Monophase  230V~1P+N 

 

Put the 1

st

 bridge between terminal 1 and 2, the 2

nd

 between 3 and 4. 

Attach the earth to the terminal 

“earth”, the neutral N to terminal 3 or 4, the Phase L either 

terminals 1 or 2. 
 
Biphase        400V~2P+N 

 

Put a bridge between terminal 3 and 4. 
Attach the earth to the terminal 

“earth”, the neutral N to terminal 3 or 4, the Phase L1 to terminal 

1 and the Phase L2 to terminal 2. 

  
Caution! 

Ensure that the cables are correctly inserted and screwed down tightly. 

 

 

Mains 

Connection 

Cable diameter 

Cable 

Protection calibre 

230V~ 50Hz 

1 Phase + N 

3 x 2,5 mm

2

 

H 05 VV - F 

H 05 RR - F 

25 A * 

400V~ 50Hz 

2  N 

4 x 1.5 mm² 

H 05 VV - F 

H 05 RR - F 

16 A * 

We cannot be held responsible for any incident resulting from incorrect connection or 
which could arise from the use of an appliance which has not been earthed or has been 
equipped with a faulty earth connection. 

Содержание HN7242FR

Страница 1: ...Customer Care Department The Group Ltd Harby Road Langar Nottinghamshire NG13 9HY T 01949 862 012 F 01949 862 003 E customer care cda eu W www cda eu www cda eu...

Страница 2: ...al Number EU Declarations of Conformity This appliance has been manufactured to the strictest standards and complies with all applicable legislation including Electrical safety LVD 2014 35 EU and Elec...

Страница 3: ...OTHER PRECAUTIONS 6 DESCRIPTION OF THE APPLIANCE 7 TECHNICAL DATA 7 CONTROL PANEL 7 USE 7 SENSITIVE TOUCHES 7 DISPLAY 8 VENTILATION 8 STARTING UP AND APPLIANCE MANAGEMENT 8 BEFORE THE FIRST USE 8 IND...

Страница 4: ...rface The appliance must be grounded and connected to ensure that it conforms to local standards Do not use any extension cable to connect the appliance The appliance cannot be used above a dishwasher...

Страница 5: ...t be carried out by children without adult supervision Precautions not to damage the appliance Raw pan bottoms cast iron pans including enamelled cast iron or damaged saucepans may damage the ceramic...

Страница 6: ...by yourself WARNING If the surface is cracked switch off the appliance to avoid the possibility of electric shock Other protections Make sure that the cookware is always centred on the cooking zone T...

Страница 7: ...Energy consumption ECcw 166 7 Wh kg The given power may change according to the dimensions and material of the pan calculated according to the method of measuring performance EN 60350 2 Control panel...

Страница 8: ...principle An induction coil is located under each heating zone When it is engaged it produces a variable electromagnetic field which produces inductive currents in the magnetic pan The result is the...

Страница 9: ...tion U active Residual heat indication After the switching off of a heating zone or turning off the hob the heating zones may still be hot If a zone remains hot then it will display an H symbol The sy...

Страница 10: ...the time Press key 1 minute After a few seconds the control light stops pulsating and the timer starts To stop the egg timer function Action Control panel Display Activate the hob Press key Timer lig...

Страница 11: ...Display Start Press key 0 on displays Unlocking the hob Press key 0 on displays Lock indicator is off Booster function The booster function P grants a boost of power to the selected heating zone If t...

Страница 12: ...a pan placed on an induction heating zone set at level 9 This water must heat in a few seconds A magnet sticks to the bottom of the pan Certain pans can make noise when they are placed on an inductio...

Страница 13: ...ays The hob must be configured according to the following procedure I Warning before starting all pots must be removed from the cooktop II Disconnect the cooktop from the main supply by turning the is...

Страница 14: ...d The touch keys are covered with grease or water An object is covering a key The control panel displays U There is no pan on the cooking zone The pan is not compatible with induction The diameter of...

Страница 15: ...15 The control panel displays E3 ou E7 The pan is not recognised change the pan If one of the symbols above persists call customer care after sales service...

Страница 16: ...re that there are no grains of dust on your ceramic hob or on the pan Sliding rough saucepans will scratch the surface Spillages of sugar jam jelly etc must be removed immediately You will thus preven...

Страница 17: ...oven or any kind of dishwasher Ensure that the underside of the hob casing has a space of 20 mm to ensure a good air circulation to the electronic devices If a drawer is placed under the hob avoid put...

Страница 18: ...the earth wire the blue wire corresponds to the neutral wire and the brown wire corresponds to the live phase calculated with the simultaneous factor following standard TN 60 335 2 6 Connection of the...

Страница 19: ...19...

Страница 20: ...www cda eu The Group Ltd Harby Road Langar Nottinghamshire NG13 9HY Copyright CDA 2016...

Отзывы: