REVO S
2PH from 60A to 800A - 690V
User’s manual
31
Internal Fuse
The thyristor unit have internal fuse extrarapid at low I²t for the thyristor protection of against the short-circuits.
The Fuses must have I²t 20% less than thyristor’s I²t. The warranty of thyristor is null if no proper fuses are used.
Size
200 kARMS Symmetrical A.I.C.
Qty
Fuse CODE
Current
(ARMS)
FUSE I2T value
Suggested A2s (at500V)*
FUSE I2T value
Suggested A2s (at660V)
Vac
60A (S11)
20 282 20.160
160
15400
16940
690
3
90A (S11)
20 282 20.160
160
15400
16940
690
3
120A (S13)
20 282 20.160
160
15400
16940
690
3
150A (S13)
20 282 20.200
200
25000
27500
690
3
180A (S13)
20 282 20.250
250
44000
48400
690
3
210A (S13)
20 282 20.315
315
77000
84700
690
3
300A (S14)
FMM400
400
72500
79750
690
3
400A (S14)
FMM550
550
215000
236500
690
3
450A (S14)
2x FM315
2 x 315
308000
338800
690
3
500A (S14)
2x FM315
2 x 315
308000
338800
690
3
600A (S14)
2x FMM450
2 x 450
420000
462000
690
2
700A (S14)
2x FMM450
2 x 450
420000
462000
690
2
800A (S16)
4x 20 559 20.250
4 x 250
352000
387200
690
2
*I2T are multiplied for K value in function of Vac at 690V K is equal
to 1,1 (ex:15400 X 1,1 = 16940). At 660Vac K is equal to 1
Fuses replacement: Open the cover and remove the screws,
then replace it with the correct fuse, use the screws with a proper
suggested torque indicated below
TYPE
Screw
Torque Lb-in
(N-m)
60A-210A
M6
44.2 (5.0)
300A-800A
M8
133.7(15.0)
Caution:
High speed fuses are used only for the thyristor
protection and can not be used to protect the installation.
Caution:
The warranty of thyristor is null if no proper fuses
are used. See tab.
Warning:
When it is supply, the Thyristor unit is subject to
dangerous voltage, don’t open the Fuse-holder module and
don’t touch the electric equipments.
12
1.2
1.0
0.8
0.6
0.4
0.2
200 400 600 800
1.1
690
Vac
K
(Line voltage)