background image

877-4-SAFETY

 | 

Fax: 940-382-9435

CBS

Safe

®

A Group CBS Company

Arc

2.0 Safety Information 

ALWAYS connect the control cable to the actuator BEFORE 
installing the Chicken Switch®.  

2.1 Finger Pinch Points 

NEVER place your fingers in the area where the actuator 
extends when the control station is connected to the 
actuator.  The actuator could pinch your hand/fingers 
against something nearby.

Also, keep fingers clear of the bottom of the actuator near 
the magnets when the actuator is near a ferrous surface.

2.2 Strong Magnets 

The holding magnets are very strong.  Keep magnetically-
sensitive objects such as watches or computer disks away 
from the bottom of the actuator.

3.0 Battery Requirements 

•  Eight (8) AA alkaline cells are required. Carefully observe 

polarity when installing cells. 

•  Only Alkaline batteries should be used. 

3.1 Battery Life 

•  A set of fresh alkaline cells should give hundreds of 

operations. 

3.2 Battery Replacement 

•  ALWAYS disconnect the control cable before replacing 

batteries to avoid possible static damage of the 
electronics!

•  Turn the control station upside down, remove the 

endplate retaining knob.  Remove the endplate and slide 
the cover out as shown below.

3.3 To connect/Disconnect Batteries:

3.4 CAUTION: Static Discharge Potential 

•  To avoid possible damage to electronic components 

disconnect the control cable before replacing batteries.

4.0 Operation 

ALWAYS connect the control cable to the actuator BEFORE 
installing the Chicken Switch®. 

4.1 Connecting the Control Cable: 

1.  Align the arrow on the cable end with the top of the 

receptacle.

2.  Push in and engage the threads on the coupling nut 

and turn clockwise.

3.  After one or two turns of the coupling nut, push in on the 

cable end.  Repeat this until the connector is fully seated.

4.  Use a similar technique of turn-stop-and-pull to 

disengage the cable ends.

TO AVOID POSSIBLE DAMAGE TO 

ELECTRONIC COMPONENTS DISCONNECT 

CONTROL CABLE BEFORE REPLACING 

BATTERIES.

WARNING

Содержание RSK-SPB1

Страница 1: ...DANGER CBS Safe A Group CBS Company Arc CBSArcSafe com Email info CBSArcSafe com 877 4 SAFETY Fax 940 382 9435 WE DO RSK SPB1 AND RSK SPB2 A Portable Actuator for Remotely Operating Westinghouse SPB100 Breakers USERS MANUAL Rev August 2019 ...

Страница 2: ...HOULD ONLY BE USED BY QUALIFIED PERSONS AFTER CAREFUL ANALYSIS OF THE HAZARDS DANGER 1 0 Arc blast Hazards The hazards associated with electrical arc blasts are well documented Studies conducted by numerous industries and professional organizations have sought to quantify the intensity of arc blast the risks to personnel and various methodologies for mitigating the risks Without doubt increasing t...

Страница 3: ... should give hundreds of operations 3 2 Battery Replacement ALWAYS disconnect the control cable before replacing batteries to avoid possible static damage of the electronics Turn the control station upside down remove the endplate retaining knob Remove the endplate and slide the cover out as shown below 3 3To connect Disconnect Batteries 3 4 CAUTION Static Discharge Potential To avoid possible dam...

Страница 4: ... that would prevent the actuator from seating firmly over the face of the breaker Any such obstructions will need to be relocated to allow proper installation of the actuator To attach the actuator complete the following steps STEP 1 Align opening in actuator over the raised portion on the face of the breaker STEP 2 Rotate the upper magnet lever upward to latch magnet onto breaker door STEP 3 Rota...

Страница 5: ...has the same affect as releasing both RED and GREEN pushbuttons the actuator will retract both plungers Note If a pushbutton is held in the trip or close position for an extended amount of time the plunger will remain in the extended position When the pushbutton or the enable button is released the plunger will retract 5 0 Care and Storage 5 1 Cleaning the magnets Over a period of time the magnets...

Страница 6: ...TY IN NO EVENT WILL CBS ARCSAFE S LIABILITY FOR DAMAGES WHETHER ARISING FROM BREACH OF CONTRACT OR WARRANTY NEGLIGENCE STRICT LIABILITY OR OTHERWISE EXCEED THE PURCHASE PRICE OF THE PRODUCT CONCERNED NOR WILL CBS ARCSAFE BE LIABLE FOR PUNITIVE INCIDENTAL CONSEQUENTIAL OR SPECIAL DAMAGES INCLUDING WITHOUT LIMITATION LOST PROFITS EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGES This warranty does ...

Страница 7: ...DC Fuse 3 amp quick blow AGC 3 Power supply 8 AA alkaline disposable batteries When used properly one set of batteries should yield over 700 operations Control Cable 30 feet in length 9 1 meters 5 conductor extra flexible PUR insulation Controller Requires two hand operation The enable button must be depressed while operating the OPEN or CLOSE buttons A programmable micro controller manages contro...

Страница 8: ... 4411 Fx 940 382 9435 info CBSArcSafe com Charleston WV Facility 4782 Chimney Drive Charleston WV 25302 Ph 800 248 4958 Ph 304 965 9220 Fx 304 965 9221 U K Europe Office 27 Cressey Avenue Shenley Brook End Milton Keynes Buckinghamshire United Kingdom MK57EL Phone 447 770 500577 Chicken Switch is a Registered Trademark of CBS ArcSafe US Patent 7 623 011 opyright 2004 2016 CBSArcSafe All rights rese...

Отзывы: