More Products by CBS ArcSafe

®

 

RRS-1 –

 

Universal Remote Racking System (Rotary)

 

The CBS ArcSafe® RRS-1 is a universal remote racking system capable of remotely installing and removing rotary style draw out 
circuit breakers without requiring any modification to the existing switchgear.  Operation of the simple to use RRS-1 is quite 
intuitive and requires only minimal setup.  When used properly, the RRS-1 allows technicians to remain outside of the arc flash 
boundary during the potentially dangerous racking operation. 
 

RRS-2 –

 

Universal Remote Racking System (Non-Rotary)

 

The CBS ArcSafe® RRS-2 is a universal remote racking system capable of remotely installing and removing non-rotary style draw 
out circuit breakers without requiring any modification to the existing switchgear.  Operation of the simple to use RRS-2 is quite 
intuitive and requires only minimal setup.  When used properly, the RRS-2 allows technicians to remain outside of the arc flash 
boundary during the potentially hazardous racking operation. 
 

RRS-3 –

 

Application Specific Remote Racking System (Rotary And Non-Rotary)

 

The CBS ArcSafe® RRS-3 product line is made up of various application specific remote breaker racking devices.  Each standalone 
system allows service personnel to remotely install and remove a particular type of circuit breaker safely while stationed safely 
outside of the arc flash boundary during the potentially dangerous operation.  The lightweight and compact design of the RRS-3 
systems makes them ideal for hard to access areas where space is at a premium. 
 

RRS-4 –

 

PLC Based Universal Remote Racking System (Rotary)

 

The CBS ArcSafe® RRS-4 universal remote racking system is an updated PLC based version of the best selling RRS-1.  The dual 
mode, source programmable, PLC based control system offers two different operating modes to choose from based on user 
preference or the application.  The RRS-4 is capable of remotely installing and removing rotary style draw out circuit breakers 
without requiring any modification to the existing switchgear, allowing users to remain outside of the arc flash boundary during 
the potentially hazardous racking operation. 

 

RSA –

 

Remote Switch Actuator

 

The CBS ArcSafe® Remote Switch Actuator (RSA) product line is made up of various application specific remote operating 
devices.  These products allow service personnel to remotely perform all aspects of an operation for a particular type of 
electrical equipment from outside the arc flash boundary – reducing or eliminating the possibility of serious injury or death 
resulting from an arc flash. 
 

RSO –

 

Remote Switch Operator

 

During a remote operation, the CBS ArcSafe® RSO functions as both the power supply and user interface for the device being 
remotely operated by the user.  When paired with an applicable CBS ArcSafe® device, this portable standalone system allows 
service personnel to remotely perform a racking or switching procedure from outside the arc flash boundary – reducing or 
eliminating the possibility of injury or death resulting from an arc flash 
 

Содержание RSA-138A

Страница 1: ...inted in the United States of America Reproduction adaptation or translation without prior written permission is prohibited except as is allowed by law RSA 138A Installation and Operation 2616 Sirius Road Denton TX 76208 877 4 SAFETY www cbsarcsafe com Allis Chalmers Siemens Allis LBS SE2 Rev 1 31 2019 DistanceisSafety WE DO WHAT STANDS BETWEEN YOU AND ARC FLASH DANGER ...

Страница 2: ...y install and remove a particular type of circuit breaker safely while stationed safely outside of the arc flash boundary during the potentially dangerous operation The lightweight and compactdesignofthe RRS 3 systems makes them ideal for hard to access areas where space is at a premium RRS 4 PLC Based Universal Remote Racking System Rotary The CBS ArcSafe RRS 4 universal remote racking system is ...

Страница 3: ... stickers and or placards may interfere with the proper installation of theRSA Please remove or reposition these itemsbeforeinstallingtheRSA 1 Ensure that theswitch is free from anyobstructionthatmayinterferewiththeproperinstallationofthe RSA 2 Align the RSA to the handle escutcheon on the opposite side of the switch s operating handle then slide the handle adapter of the RSA over the switch handl...

Страница 4: ...e that the upper locator on the RSA is flush with the top and side of the switch escutcheon as shown 4 Turn the handles of the twit lock magnets 180 clockwise to lock the RSA in place 5 Install the interlock defeat onto the switch handle as shown ...

Страница 5: ...RSA 138A Installation and Operation 3 The RSA is now ready for remote operation ...

Страница 6: ...RSO I AR please see the RSO I AR Manual 1 Ensure that theRSA is properly installed SeeSection3 for detailed instructions 2 Plug the RSO I AR into the motor control box 3 Exit the arc flash boundary 4 Turn the power switch on the RSO I AR to the ON posi tion 5 Ensure that the Auto Retract AR function is OFF 6 If the breaker is CLOSEDandneedstobeopened press and hold the TRIP button on the RSO I AR ...

Страница 7: ...y be done on de energized and isolated equipment to prevent possible damage or injury 3 1 Locator Adjustment The depth of the handlelocator on the RSA can be adjusted in order to avoid interference from items mounted to the switchgear door 1 Loosen the two bolts on the locator plate as shown below 2 Slide the locators up or down as necessary to position them flush to the upper and side edgeoftheha...

Страница 8: ... breaker 1 Install the RSA on the face of the breaker as described in the Installation section 2 Loosen the lock screws on the backs of the two switch wheels 3 With the RSA operator arm in the OPEN position rotate the outer limit switch cam in the direction of travel for the arm until a slight click is heard Re tighten the lock screw ...

Страница 9: ... Installation and Operation 7 4 With the RSA operator arm in the CLOSED position rotate the inner limit switch cam in the direction of travel for the arm until a slight click is heard Re tighten the lock screw ...

Страница 10: ......

Страница 11: ...RSA 138A Installation and Operation 9 Notes ...

Страница 12: ...ith that they are correctlystationedoutsidethearcflash boundary and that they comply with all applicable Federal State Local and In house safety regulations and procedures Attention should begiven to distance angle and personal protec tive equipment PPE 2616 Sirius Road Denton TX 76208 Tel 877 4 SAFETY Fax 940 382 9435 Website www CBSArcSafe com Email info CBSArcSafe com ...

Отзывы: