10
2
INSTALLATION
2.1
Environment Selection
◆
Working Temperature
:
0-40
℃
◆
Storage Temperature
:
-40-70
℃(
without battery
)
-20-55
℃(
with battery
)
◆
Relative humidity
:
5%
~
95%
,
Non condensing
◆
Altitude
:
1500m
,
appeal to GB3859.2-93
◆
The tolerance of uprightness
:
No vibration, bumps and the vertical gradient
should be no more than 5 degrees.
UPS installed environment should be adequate ventilation, cool, low humidity
and no dust. Recommended working temperature is 20~25
℃
, humidity is about 50%.
UPS should work in the place with the altitude below 1000m; When the altitude
is above 1000m,we recommend to operate UPS according to below descending table.
Altitude(m) 1500
2000
2500
3000
3500
4000
4500
5000
Descending
coefficient
100%
95%
91%
86%
82%
78%
74%
70%
2.2
Placement
The provided AC power capacity must meet the requirement of UPS normal
working. Please use unique air switch for input and output connection
Install UPS as close as possible to the utility power outlet.
The floor board of UPS installed place should be good enough to support the
weight of UPS. Any dange rous installation is forbidden.
No storage of flammable, explosive and other dangerous goods in the place and
there must have fire equipment
Keep good ventilation around UPS, don’t obstruct the cooling channels.
Keep each side of the UPS at least 1 meter away from the wall so that there have
a enough space for future maintainance and operation.
Recommend professional to manage the UPS house and stop the entery of
non-related people.
2.3
Unpacking
Before unpacking, inspect if the packaging is damaged during the transport and
if it is the correct model you ordered. After unpacking, check if all the accessories are