Operating Range is Short
If all PSDs have the same issue, see the
section above. If only one PSD has the problem, the
PSD is faulty; return to Cattron or an authorized service facility.
MSD
Error Light is On
Generally, if switching the MSD off and back on does not resolve the problem, return to Cattron or an
authorized service facility.
No Power
If all lights are off, request the services of an authorized and trained service agent to conduct the following
analysis and repair.
Verify that the 24Vdc input supply is available and if necessary check the fuse to the left of the supply
terminal and replace if necessary.
If the fuse blows again, disconnect all input and output terminals and replace the fuse again. If it blows
again, the MSD is faulty; return to Cattron or an authorized service facility. If the fuse no longer blows,
check all external wiring for an intermittent short circuit on the 24V line and correct.
Operating Range is Short
If all PSDs have the same issue see
Cannot Reset Unit after a PSD Communication Loss
Check the wiring and voltages between the reset input, the external reset button, and the 24V supply to
the reset button. If this supply is not common to the MSD supply, ensure the 0v line of the external supply
is connected to the 0V line of the MSD supply.
Battery Charger
The chargers require no special maintenance, but in the event of damage to the unit, the external power
supply or cord, contact Cattron customer service for a replacement.
Make sure contacts in charging pod and on the PSD are clean. If contacts require cleaning, disconnect
charger from power supply and wipe with a dry, lint free cloth.
Do not charge PSD batteries below 0° Celsius or above 40° Celsius.