61
MessengerBLE
User Guide
Parameters for Digital Channel Configuration
(channel numbers 1-50 are pre-defined digital channels)
Parameter
Code
Reference
Description
Default
1
Name
A representative name to reference
the channel by.
Channel
Specific
ASCII Text
30 characters max
2
Mode
Defines operating mode of channel.
Status Only
[1]
0 = disabled
1 = Status Only (value is monitored, no
testing of value against limits)
2 = Report on Alarm (value is
monitored and tested against limits)
3
Alarm
Delay
The continuous time the value must
exceed a limit before it is considered
to be in violation of that limit.
10
Range 0 – 65535 seconds
0 = no delay time, immediate alarm
Source
Data
Register
This defines the source register of the
value for this channel. Reference
Appendix B.
10
Delta
Debounce
10
Alarm
Output
Data
Register
An output data register that can be set
when this channel goes into alarm,
referenced as a data register.
Reference Appendix B.
Disabled
[0]
Output
State on
Normal
0 – de-
activate
Range 0-3
0 = de-activate (open)
1 = activate (close)
2 = undefined
3 = static (do not change the current
state)
1 - activate