Channel Configuration – Type 9
Parameters for Analog Channel Configuration
(channel numbers 51-300 are pre-defined analog channels)
Parameter
Code
Reference Description
Default
1
Name
A representative name to reference the
channel by.
Channel
Specific
ASCII Text
30 characters max
2
Mode
Defines operating mode of channel.
Status Only
[1]
0 = disabled
1 = Status Only (value is monitored, no
testing of value against limits)
2 = Report on Alarm (value is monitored
and tested against limits)
3
Alarm
Delay
The continuous time the value must
exceed a limit before it is considered to
be in violation of that limit.
10
Range 0 – 65535 seconds
0 = no delay time, immediate alarm
Source
Data
Register
This defines the source register of the
value for this channel. Reference
Appendix B.
10
Delta
Threshold
10
Delta
Debounce
10
Alarm
Output
Data
Register
An output data register that can be set
when this channel goes into alarm,
referenced as a data register. Reference
Appendix B.
Disabled
[0]
Output
State on
Normal
0 – de-
activate
Range 0-3
0 = de-activate (open)
1 = activate (close)
2 = undefined
3 = static (do not change the current
state)
1 - activate