Operation
4.1 ES52 Startup / Shutdown Behavior
Note:
The fuel output remains on during crank rest. There is no way to disable this.
4.2 Zero Speed Restart Feature
The ES52 has a starter protection feature where it will not turn on the crank output until the engine speed is zero.
•
If the speed is not zero before cranking, preheat (timer) will be performed but the ES52 will pause until
the speed is 0 Hz or it will go into a failure (alternating Over-crank and Over-speed LEDs flashing) after
30 to 40 seconds
•
If the speed is not zero during engine rest, the ES52 will not crank until it is zero. It will sit in engine rest
for 30 to 40 seconds and then go into failure (alternating Over-crank and Over-speed LEDs flashing)
4.3 Oil Verification
If Low Oil verification is enabled (DIP Switch 6 ON) and the low oil pressure switch fails verification, the controller
will remain in crank rest after the first crank attempt until the oil switch passes verification. During this time the
low oil pressure lamp will be on solid red. The engine run lamp will be on flashing green. See the
on oil verification for more information.
4.4 Front Panel LED Indications
shows the LED indicator lights on the front panel of the ES52.
Figure 5: LED Indicators
The following table lists the conditions that are indicated by the status of each of these LEDs.
What The LEDs Look Like
Condition / Failure
No LEDs ON
“Ready” – unit waiting for start signal; +12/24 VDC to Auto terminal
“OFF” – no +12/24 VDC to Auto terminal