8” SAER MOTORS
3 PHASE SUBMERSIBLE
MOTOR SPECIFICATIONS
& TESTING PARAMETERS
HORSEPOWER
MOTOR DIA.
MAKE & RPM
VOLTS PHASE
Hz
SERVICE
FACTOR
FULL
LOAD
AMPS
MAX
LOAD
AMPS
LINE to LINE
RESISTANCE
IN OHMS
LOCKED
ROTOR
AMPS
20 HP
8” SAER
1800 RPM
230V
3 PH
60 Hz
1.15
58.0
66.7
0.10 - 0.30
N/A
460V
28.0
32.0
0.90 - 1.1
N/A
25 HP
8” SAER
1800 RPM
230V
3 PH
60 Hz
1.15
70.0
80.5
0.22 - 0.26
N/A
460V
34.0
40.0
0.87 - 1.07
N/A
30 HP
8” SAER
1800 RPM
230V
3 PH
60 Hz
1.15
80.0
92.0
0.13 - 0.33
N/A
460V
40.0
45.0
0.70 - 0.90
N/A
Carry Manufacturing, Inc.
·
1360 Prospect Ave.
·
Caro, MI 48723
www.carrypumps.com
·
800-492-2779
·
ALL ELECTRICAL WORK
MUST BE PERFORMED
BY A LICENSED
ELECTRICIAN
DO NOT
test Winding resistance with the
motor connected to the Control Box or Var-
iable Frequency Drive (VFD).
A bound pump will cause locked rotor amps
and over-current fault/shut down. Check
for obstructions in the pump and/or the
amps on the Black wire at start-up.
Test the windings by using a Multimeter or
Ohmmeter to measure Ohms (Resistance)
between Yellow or White to Red, Yellow or
White to Black, and Red to Black.
IMPORTANT
Resistance measured between any combi-
nation of wires should be a similar value.