Appendix C: Converting a control program with an RS Pro to a ZS Pro
ZS Sensor
CARRIER CORPORATION ©2020
Applications Guide
All rights reserved
40
Step 2: Make Alarm icon display on a ZS Pro
Place a BACnet Binary Value Status microblock and select
Generic Alarm (1024)
in the
Rnet Tag
field. See image
below. The setup shown will make the alarm bell icon show on the Home screen when the BV status is active.
NOTE
To include information about the active alarm on the Information screen, check that screen in the
Show On
field and enter
Display Active Text
.
Before
After
Step 3: Make Fan icon display on a ZS Pro
Place a BACnet Binary Value Status microblock and select
Fan Status (100)
in the
Rnet Tag
field. See image
below. The setup shown will make the fan icon show on the Home screen when the BV status is active.
NOTE
Do not check the Home screen in the
Show On
field. Checking that option causes the fan status to show up
in the rotation of the primary value field, and that is not needed.