background image

4. Press HOLD/END key to exit.

Select system Mode:

1. Press MODE button to select HEAT or COOL.

2. Press HOLD/END button to turn on HOLD icon.

3. Press UP or DOWN button until the desired temperature is

displayed.

4. Press ALL ZONE button to turn on ALL ZONE icon if this

desired temperature is needed for every zone. With ALL
ZONE selected, all zones are controlled to a single set point,
providing even temperatures in all zones. Otherwise press
NEXT ZONE button, and repeat HOLD function in selecting
the desired temperature for each zone.

QUICK PROGRAMMING OF COMFORT SCHEDULES

The following is a brief overview of how to access and program
schedules in your new zoning system. We highly recommend that
you read and follow the programming information provided in the
Owner’s Guide for detail step-by-step instructions.

Before proceeding, set the correct Time and Day at the User
Interface (see above Quick Start).

However, if you followed the above Quick Start procedure in
selecting the system mode, you will need to reverse the ALL
ZONE and/or HOLD functions before proceeding. Simply press
ALL ZONE and/or HOLD button to remove these icons from the
display. (See Fig. 14.) Make sure HOLD is removed from each
zone.

During the programming process, you will have access to 4
program time periods, e.g., WAKE, DAY, EVE, and SLEEP. You
will be able to select program start times and the heat/cool set
points for each time period and zone. Use the Keypad to enter and
move around inside the program. Use the temperature UP and
DOWN buttons to adjust the start times and to raise and lower set
points. When inside the program, the blinking icon indicates that a
setting may now be changed.

1. Decide on a program schedule that you desire. Table 4 is an

example of what already exists in the User Interface as the
Energy Star recommended settings.

2. To begin programming, press PROGRAM button.

3. Press NEXT ZONE button until ZONE 1 appears on the LCD

display.

4. Press NEXT DAY button until Monday (Mo) is displayed.

5. Press NEXT PERIOD button until the WAKE period is

displayed.

6. Press SET TIME/TEMP button until the TIME icon is

flashing.

7. Start programming ZONE 1 beginning with the WAKE start

time. Press the UP or DOWN button until the desired starting
time is displayed, make sure that the AM is correct.

8. Press SET TIME/TEMP button until the HEAT icon is

flashing. Press UP or DOWN button until the desired heating
temperature for that period is displayed.

9. If that zone is going to be unoccupied, press OUT button. For

more information regarding the Out feature, read the follow-
ing section pertaining to Hold, Off, Out, and All Zone.

10. Press SET TIME/TEMP button until the COOL icon is

flashing. Press UP or DOWN button until the desired cooling
temperature for that period is displayed. You have now
programmed the time and desired heating and cooling tem-
peratures for Monday, ZONE 1, in the WAKE time period.

11. Press NEXT PERIOD button to change from WAKE to the

DAY period. Repeat steps 6 through 11 for programming the
time and desired heating and cooling temperatures for Mon-
day, ZONE 1, in the DAY time period. Use NEXT PERIOD
button again to select EVE and SLEEP, and repeat procedure.

12. After Monday ZONE 1 is completely programmed, you may

select NEXT DAY and advance to Tuesday. You can now
press COPY DAY button and copy the program schedule from
Monday into Tuesday. This can be repeated as needed for each
remaining day in the week. However, if copying the previous
day is not desired, you may individually program each day
using the NEXT DAY button and repeating steps 6 through
12. Press HOLD/END button to exit programming mode.

You may also use the button pair marked COPY ZONE (COPY
PERIOD and COPY DAY buttons simultaneously) to copy a full
week from 1 zone to the next. First use NEXT ZONE to select the
new zone, and then press COPY ZONE pair to copy the entire
week from the original zone into the new zone.

NOTE:

Other ways to program comfort schedules with their

function keys can be found in the Owner’s Manual.

HOLD, OFF, OUT, AND ALL ZONE

The following will provide detailed information regarding HOLD,
OFF, OUT, and ALL ZONE functions: (See Fig. 14.)

HOLD FUNCTION

At the User Interface or Smart Sensor(s):

Pressing HOLD button activates and deactivates HOLD function
for a single zone.

When HOLD function is active, HOLD icon is displayed, and the
current set points will be used until the user cancels the HOLD
function. The HOLD function prevents the set points from

Table 3—Outputs vs. Stages

SYSTEM TYPE

COOL 2

COOL 1

HEAT 1

HEAT 2

HEAT 3

HEAT 4

HEAT 5

1-Speed AC

N/A

Y1

W1

W1,W2

N/A

N/A

N/A

2-Speed AC

Y1,Y2

Y1

W1

W1,W2

N/A

N/A

N/A

1-Speed HP

N/A

Y1,O

Y1

Y1,W1

Y1,W1,W2

N/A

N/A

with 3-Stage Heat

N/A

Y1,O

Y1

Y1,W1

Y1,W2

Y1,W1,W2

N/A

2-Speed HP

Y1,Y2,O

Y1,O

Y1

Y1,Y2

Y1,Y2,W1

Y1,Y2,W1,W2

N/A

with 3-Stage Heat

Y1,Y2,O

Y1,O

Y1

Y1,Y2

Y1,Y2,W1

Y1,Y2,W2

Y1,Y2,W1,W2

1-Speed Dual Fuel

N/A

Y1,O

Y1

W1

W1,W2

N/A

N/A

2-Speed Dual Fuel

Y1,Y2,O

Y1,O

Y1

Y1,Y2

W1

W1,W2

N/A

Table 4—User Interface Settings

TIME

COOL

HEAT

WAKE

6:00 AM

78

68

DAY

8:00 AM

85

60

EVE

5:00 PM

78

68

SLEEP

10:00 PM

82

60

17

Содержание ZONECC2KIT-B

Страница 1: ...entify unsafe practices which would result in minor personal injury or product and property damage INSTALLATION CONSIDERATIONS Before the actual installation of a zoning system can begin decisions need to be made to determine the number and location of zones and sensors This affects duct and damper selections For assistance with these decisions consult the Zoning Design Guide available from your d...

Страница 2: ...enter for the Comfort Zone II B system It should be located where it is easily accessible and visible to home or business owner It is also normally the Zone 1 sensor and as such needs to be located to properly measure the temperature in Zone 1 If these 2 requirements conflict a separate Remote Sensor can be added for Zone 1 When Remote Sensor is connected to Zone 1 terminals ZS1 and ZS1C of Equipm...

Страница 3: ...nce in making these selections Selection and sizing infor mation is not provided in this installation instruction If duct work requires multiple dampers for a single zone up to 5 dampers may be wired in parallel A multi damper enabler is not needed For retrofit applications older type dampers with their original actuators may be used under the following conditions 1 A single damper may be connecte...

Страница 4: ...uator 4 Insulate damper using 1 1 2 in to 2 in insulation Check your local codes See Fig 6 NOTE All zone dampers and duct work must be properly supported according to local codes or SMACNA standards RECTANGULAR FIBROUS GLASS DUCT WORK 1 Insert 1 end of zone damper into 1 end of fibrous glass duct work approximately 2 to 3 in See Fig 7 2 Screw field supplied screws and tabs into zone damper 3 Prope...

Страница 5: ...uire as few as 4 or as many as 7 conductors See Table 6 to identify the correct wiring figure NOTE Table 6 and wiring diagrams appear in sequence near the end of this document NOTE It is good practice to mark each wire as the final connection is made This will preserve its identity if it is ever disconnected When installing a 24 vac humidifier connect it directly to the HUM terminal on Equipment C...

Страница 6: ...mand for zone is 1 F 77 minus 76 F OUT FEATURE A new feature called OUT can be selected via the OUT button When this selection is made the system is being told that the selected zone is unoccupied It will normally supply no condition ing to an OUT zone If zone temperature exceeds 85 F or goes below 60 F conditioning will be supplied to maintain the zone within these limits OUT zones are also used ...

Страница 7: ...n control heat pumps furnaces and dual fuel applications CONTROL STRATEGY FOR HEATING COOLING STAGES The Comfort Zone II B system will attempt to minimize use of additional stages of heating or cooling equipment Comfort Zone II B controls multi stage equipment in response to the level of demand and the number of zones with demand In general it tries to satisfy demand with a minimum number of stage...

Страница 8: ...ic heat OFF Special 3 stage electric heat Switch 4 Selects Smart Recovery in both heating and cooling The system starts adjusting temperature 1 1 2 hours earlier than selected recovery time so it will arrive at new temperature at selected time ON Smart recovery OFF Normal recovery Switch 5 Zone system address selection When 2 zoning systems are connected together the second system should be set to...

Страница 9: ...ors At power up the User Interface displays all segments for a few sec This is followed by the selected system type for an additional few sec The system type shows as follows 1 AC 1 Speed Air Conditioner 2 HP 1 Speed Heat Pump 3 A2 2 Speed Air Conditioner 4 H2 2 Speed Heat Pump 5 HS 1 or 2 Speed Heat Pump with 3 Stage Auxiliary Heat 6 dF Dual Fuel with 1 Speed Heat Pump 7 d2 Dual Fuel with 2 Speed...

Страница 10: ...furnace or fan coil contains a variable speed ICM blower set this option ON For normal PSC blowers set to OF off This selection enables the system to use Comfort Heat features avail able only with the ICM blower Factory default is OF off AVAILABLE SELECTIONS Use UP or DOWN buttons to alternate between OF off and ON OPTION 6 COOLING LOCKOUT TEMPERATURE This option allows selection of the outdoor te...

Страница 11: ...5 selections are already made While heat pump is heating the blower speed is reduced by removal of the G signal for outdoor temperatures between 12 and 40 degrees F providing warmer leaving air temperatures For heat pumps with electric aux heat and outdoor temperatures below 12 degrees F any heat call is accompanied by a W1 signal bringing on the first stage of aux heat to again increase leaving a...

Страница 12: ...low temporary operation with a failed or missing sensor until the sensor can be replaced Factory default is OF off AVAILABLE SELECTIONS Use UP or DOWN buttons to alternate between OF off and ON NOTE ON is for temporary use only OPTION 38 SELECT AUTO CHANGEOVER TIME This option selects a 5 to 30 minute time delay between heat and cool while in auto changeover mode System must have no demand in curr...

Страница 13: ... FINAL INSTALLATION SETTINGS Humidification Description If a humidifier is included in the system Comfort Zone II B can directly control it If a conventional humidity control exists it should be removed and the zoning system used in its place Comfort Zone II B provides superior convenience and features When installing a 24 vac humidifier connect it directly to the HUM terminal on the Equipment Con...

Страница 14: ... rises above the dehumidification set point a special dehumidification routine is executed As long as zone temperatures are not more than 3 F below their cooling set points a dehumidify demand will turn on the cooling equipment but will limit its ON time to no more than 10 minutes at a time Finally OUT zones are used to their maximum capability When a zone is set to OUT it can be used to help remo...

Страница 15: ...use the combination of a 2 speed compressor without a variable speed blower generally has poor humidity removal on low speed Dehumidify Output and Equipment Connections When there is a dehumidify demand dehumidify output is activated which means that a 24vac signal is removed from the DHUM output terminal In other words dehumidify output logic is reversed output is turned ON when no dehumidify dem...

Страница 16: ...hese indicate when cooling or heating equipment is actually operating When arrows flash equipment is waiting to come on but is being held off by compressor timeguard cycle timer or because LAT or HPT has exceeded its limits and temporarily turned equipment off When the humidity screen is displayed these same arrows show the state of the humidify and dehumidify outputs Multiple Sensors in a Single ...

Страница 17: ...hat zone is going to be unoccupied press OUT button For more information regarding the Out feature read the follow ing section pertaining to Hold Off Out and All Zone 10 Press SET TIME TEMP button until the COOL icon is flashing Press UP or DOWN button until the desired cooling temperature for that period is displayed You have now programmed the time and desired heating and cooling tem peratures f...

Страница 18: ... occupied When a zone is set to OUT desired temperature will be displayed as dashes when UP and DOWN buttons are pressed VIEWING OUTDOOR TEMPERATURE AND INDOOR HUMIDITY 1 Pressing both UP and DOWN buttons simultaneously will display outdoor temperature if this feature is included and indoor humidity Outdoor temperature will be displayed first for 5 sec followed by humidity for 5 sec Smart Sensor w...

Страница 19: ...zone to occupied When a zone is set to OUT the desired temperature will be displayed as when UP and DOWN buttons are pushed ALL ZONE At the User Interface Pressing ALL ZONE button activates and deactivates ALL ZONE function When ALL ZONE function is active ALL icon is displayed This function allows the entire house to be controlled to the set points and program schedule of a single zone The zone t...

Страница 20: ...de the 32 F to 140 F range See Table 5 to determine the temperature ohm relation ship for a Remote Sensor Do not confuse dashes in the display for a zone that is set to OUT or ALL ZONE Other Helpful Hints Read and understand System Startup and Checkout to review Installer Test Setup Mode and check the equipment operation This is a good place to start in evaluating any problems associated with the ...

Страница 21: ...OT See notes 1 2 3 6 10 11 and 19 HUMIDIFIER 24 VAC Fig 15 1 Stage Furnace with 1 Speed Air Conditioner A98089 C C R Y W G Y N A SINGLE STAGE FURNACE SINGLE SPEED AIR CONDITIONER EQUIPMENT CONTROLLER N A 24 VAC HOT N A N A HUMIDIFY O B RH RC W2 W1 G Y2 Y1 DEF DHUM HUM HUMIDIFIER 24 VAC N A HEAT STAGE 1 FAN N A COOL STAGE 1 See note 19 Fig 18 1 Stage Furnace with 2 Speed Heat Pump Dual Fuel A98092 ...

Страница 22: ...N A COOL STAGE 1 See notes 12 and 19 N A N A HUMIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC Fig 22 2 Stage Furnace with 2 Speed Heat Pump Dual Fuel A98096 W W1 W2 Y Y2 TWO SPEED HEAT PUMP C O R W2 Y2 W3 C R Y1 G O B RH RC DEF W2 W1 G Y2 Y1 HEAT STAGE 4 HEAT STAGE 3 FAN COOL HEAT STAGE 2 COOL HEAT STAGE 1 See notes 1 2 3 4 6 7 8 9 10 11 12 and 19 TWO STAGE FURNACE EQUIPMENT CONTROLLER RVS COOLING DEFROST ...

Страница 23: ...MIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC HUM DHUM PL9 10 O Y1 AIRFLOW SELECT BOARD Fig 26 Variable Speed Non Condensing Furnace with 2 Speed Heat Pump Dual Fuel A98100 C C R Y2 W W1 G W2 Y Y2 O B RH RVS COOLING VSP FURNACE BOARD TWO SPEED HEAT PUMP EQUIPMENT CONTROLLER N A 24 VAC HOT RC W2 W1 G Y2 Y1 HEAT STAGE 3 HEAT STAGE 2 FAN COOL HEAT STAGE 2 COOL HEAT STAGE 1 See notes 1 2 3 4 6 7 8 9 10 11 12 ...

Страница 24: ...tes 12 15 17 and 19 N A DEHUMIDIFY HUMIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC HUM DEHUM Fig 30 Variable Speed 2 Stage Condensing Furnace W O DE Connection with 2 Speed Heat Pump A98104 C C R W2 W W1 G W2 Y Y2 O B RH RVS COOLING VSP SPEED FURNACE TWO SPEED HEAT PUMP EQUIPMENT CONTROLLER N A 24 VAC HOT RC W2 W1 G Y2 Y1 HEAT STAGE 4 HEAT STAGE 3 FAN COOL HEAT STAGE 2 COOL HEAT STAGE 1 See notes 1 2 3 4 ...

Страница 25: ...5 18 and 19 N A DEHUMIDIFY HUMIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC HUM DEHUM DE Fig 34 Variable Speed 2 Stage Condensing Furnace With DE Connection With 2 Speed Heat Pump Dual Fuel A99375 C C R W2 W W1 G W2 Y Y2 O B RH RVS COOLING VSP SPEED FURNACE TWO SPEED HEAT PUMP EQUIPMENT CONTROLLER N A 24 VAC HOT RC W2 W1 G Y2 Y1 HEAT STAGE 4 HEAT STAGE 3 FAN COOL HEAT STAGE 2 COOL HEAT STAGE 1 See notes 1 ...

Страница 26: ...FAN COOL STAGE 1 N A N A HUMIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC See note 13 Fig 38 Typical Fan Coil with 2 Speed Heat Pump A98108 C R W3 C R W3 W2 Y1 W2 G Y E O B RH RVS COOLING TYPICAL FAN COIL TWO SPEED HEAT PUMP 24 VAC HOT RC W2 W1 Y2 G Y1 HEAT STAGE 4 HEAT STAGE 3 FAN COOL HEAT STAGE 1 COOL HEAT STAGE 2 O Y2 EQUIPMENT CONTROLLER DEFROST N A N A HUMIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC See note...

Страница 27: ... N A N A DEHUMIDIFY HUMIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC See notes 13 14 and 15 Fig 42 FK and FV Fan Coil with 2 Speed Heat Pump A99370 C W2 O B RVS COOLING N A R1H FK AND FV SERIES FAN COIL TWO SPEED HEAT PUMP REMOVE J1 JUMPER REMOVE J2 JUMPER FOR HEAT STAGING EQUIPMENT CONTROLLER 24 VAC HOT R1C W2 W1 G Y2 Y1 HEAT STAGE 4 HEAT STAGE 3 FAN HEAT COOL STAGE 2 HEAT COOL STAGE 1 O R Y2 Y1 C R DH W1...

Страница 28: ... indicate variable speed ICM blower motor 16 To activate dehumidify feature on variable speed 80 non condensing furnace disconnect green DHUM wire from G on furnace control board and connect to dehumidify terminal on Equipment Controller 17 To activate dehumidify feature on older style variable speed condensing furnaces i e 58MVP that do not have a DE connection a pilot duty 24vac relay must be us...

Отзывы: