background image

3. Cool to Dehumidify Mode—This mode tells the system to

operate the compressor, with limits, when there is a dehu-
midify demand and there is no cooling demand. The limits are
that the system may overcool zones by up to 3° F., while
attempting to satisfy a dehumidify demand. Within this 3°F.
range, there is an additional balance between overcooling and
humidity satisfaction. When overcooling must occur, the
dehumidify set point is adjusted upward by 2% for each
degree of zone overcooling. For example, a cooling set point
of 76°F. and a dehumidify set point of 62% is equivalent to a
cooling set point of 75° F. and a humidity set point of 64%.
This balancing of temperature and dehumidification demand
results in smoother operation of the equipment at the set
points. Adjustment of the dehumidify set point as described
above is internal to the system and does not show on the
display.

During cool to dehumidify demand, the compressor runs a
maximum of 10 minutes ON followed by 10 minutes OFF. As
in normal dehumidify, a continuous fan is turned off for 5
minutes at the end of each cooling cycle. Again, to utilize this
feature, the equipment blower off delay must be defeated.

If any of the zones are set to OUT, their dampers will fully
open while the compressor is running and a cool to dehu-
midify demand exists. While the compressor is off or if their
temperature goes below 70°F., their dampers close.

4. Vacation Dehumidify Mode—this is an extension of Cool to

Dehumidify Mode. This mode is initiated when cool to
dehumidify is selected AND all zones are set to OUT. All
zones are conditioned to keep them below 85°F. If the
humidity rises above the dehumidify set point, cooling can
occur to satisfy the dehumidify demand until zones reach 70°.
This selection is ideal for unoccupied homes in high humidity
climates. This mode can be selected — when cool to dehu-
midify is selected — by pressing HOLD, OUT , and ALL
ZONE in that order. Alternatively, each zone can be set to
HOLD and OUT, but this requires more button presses.
Remember, in vacation mode there are no temperature set
points, but a dehumidify set point must be selected. Suggested
values are 60 to 70 percent.

To exit the humidity setup mode, press HOLD/END button once.
If no button is pressed for 3 minutes, Comfort Zone II -B will
automatically save any new settings and then return back to normal
operation.

Additional Dehumidification Comments

Variable Speed Superdehumidification is selected by configuration
Option 7. It can only be implemented with Comfort Heat pump
compatible systems because it require a variable speed indoor unit
with superdehumidify capability. During a cool-to-dehumidify
call, it provides maximum dehumidification by reducing airflow to
its lowest possible value. The actual command from CZII to the
indoor unit is a Y signal without a G signal in addition to a
dehumidify signal. All other characteristics of cool-to-dehumidify
are unchanged.

Dehumidify actions are initiated when humidity rises to 2% above
set point and are terminated when humidity drops to 2% below set
point. This prevents unnecessary toggling of dehumidify actions
when humidity is near the set point.

With any dehumidify selection, if the system has 2-speed com-
pressor (DIP switch 2 is ON) and does not have a variable speed
blower (configuration option 5 is set to OFF), all cooling will be
done at high speed while a dehumidify demand exists. This is
because the combination of a 2-speed compressor without a
variable speed blower generally has poor humidity removal on low
speed.

Dehumidify Output and Equipment Connections

When there is a dehumidify demand, dehumidify output is
activated, which means that a 24vac signal is removed from the
DHUM output terminal. In other words, dehumidify output logic is
reversed — output is turned ON when no dehumidify demand
exists and is turned OFF when demand exists. This logic reversal
has come about from historical use of a standard humidistat to do
dehumidification. The humidistat contacts open on high humidity,
thus removing a 24vac signal to initiate dehumidification. Equip-
ment has been designed to operate in this manner, so Comfort
Zone must now accommodate the existing equipment.

FK and FV Series Variable-Speed Fan Coils, all 58UHV and
58UXV 80% Variable-Speed Furnaces, and 58MVP 90%
Variable-Speed Furnaces with the DE connection have dehumidify
inputs which connect directly to Comfort Zone DHUM output.
They are compatible with the reverse logic output and will reduce
their cooling CFM by approximately 20% when a dehumidify
demand is present.

The FK and FV Series Fan Coil have a terminal marked DH which
should be connected to the Comfort Zone DHUM output. Jumper
J1 on the fan coil MUST be removed. It is located behind the DH
terminal. Additionally, blower delay tap on fan coil should be set
to 0/0 (no ON delay and no OFF delay) when using cool to
dehumidify. With this selection, the blower stops when G signal is
removed, preventing re-evaporation of water from the coil which
would occur during the normal 90 sec. blower off delay. See Table
6 and Fig. 39 through 42.

On 58UHV and 58UXV furnaces, a green wire marked DHUM is
connected to a spade lug which is connected to the G input
terminal. Unplug spade lug, cut off spade receptacle from wire
end, and splice a wire between green DEHUM wire and Comfort
Zone DHUM terminal. See Table 6 and Fig. 23 through 26.

Carrier 58MVP furnaces also have a DEHUM input. The DEHUM
input acts differently depending on which style of variable-speed
furnace control you have. The older style variable-speed furnace
control DOES NOT have a DE connection while the newer style
variable-speed furnace control has a DE connection. Both of these
variable-speed furnace controls function the same except the
DEHUM logic is reversed.

On the older style variable-speed furnace controls, a field-supplied
relay is required between the equipment controller and the furnace.
The relay coil is connected between DHUM output on the
equipment controller and COM terminal on the furnace control. Its
normally closed contact is connected between R and DEHUM
terminals on the furnace control, where the DEHUM terminal is a
spade lug located next to the transformer secondary connections.
See Table 6 and Fig. 27 through 30. When a dehumidify demand
exists, relay is de-energized, and normally closed contacts supply
24vac to the furnace DEHUM terminal. As a result the furnace
control reduces the blower airflow by 15%.

On newer style variable-speed furnace controls, a field-supplied
relay IS NOT required. The DHUM output on the equipment
controller is instead connected directly to the DEHUM terminal on
the furnace control, where the DEHUM terminal is a spade lug
located next to the transformer secondary connections. In addition,
the DE jumper located next to the DEHUM terminal must be

Table 2—Displays of Available Dehumidify Modes

SELECTION

MODE DISPLAY

DEHUMIDIFY SET POINT

Dehumidify Off

Blank

OF

Normal Dehumidify

Blank

Dehum Set Point

Cool to Dehumidify

COOL

Dehum Set Point

15

Содержание ZONECC2KIT-B

Страница 1: ...entify unsafe practices which would result in minor personal injury or product and property damage INSTALLATION CONSIDERATIONS Before the actual installation of a zoning system can begin decisions need to be made to determine the number and location of zones and sensors This affects duct and damper selections For assistance with these decisions consult the Zoning Design Guide available from your d...

Страница 2: ...enter for the Comfort Zone II B system It should be located where it is easily accessible and visible to home or business owner It is also normally the Zone 1 sensor and as such needs to be located to properly measure the temperature in Zone 1 If these 2 requirements conflict a separate Remote Sensor can be added for Zone 1 When Remote Sensor is connected to Zone 1 terminals ZS1 and ZS1C of Equipm...

Страница 3: ...nce in making these selections Selection and sizing infor mation is not provided in this installation instruction If duct work requires multiple dampers for a single zone up to 5 dampers may be wired in parallel A multi damper enabler is not needed For retrofit applications older type dampers with their original actuators may be used under the following conditions 1 A single damper may be connecte...

Страница 4: ...uator 4 Insulate damper using 1 1 2 in to 2 in insulation Check your local codes See Fig 6 NOTE All zone dampers and duct work must be properly supported according to local codes or SMACNA standards RECTANGULAR FIBROUS GLASS DUCT WORK 1 Insert 1 end of zone damper into 1 end of fibrous glass duct work approximately 2 to 3 in See Fig 7 2 Screw field supplied screws and tabs into zone damper 3 Prope...

Страница 5: ...uire as few as 4 or as many as 7 conductors See Table 6 to identify the correct wiring figure NOTE Table 6 and wiring diagrams appear in sequence near the end of this document NOTE It is good practice to mark each wire as the final connection is made This will preserve its identity if it is ever disconnected When installing a 24 vac humidifier connect it directly to the HUM terminal on Equipment C...

Страница 6: ...mand for zone is 1 F 77 minus 76 F OUT FEATURE A new feature called OUT can be selected via the OUT button When this selection is made the system is being told that the selected zone is unoccupied It will normally supply no condition ing to an OUT zone If zone temperature exceeds 85 F or goes below 60 F conditioning will be supplied to maintain the zone within these limits OUT zones are also used ...

Страница 7: ...n control heat pumps furnaces and dual fuel applications CONTROL STRATEGY FOR HEATING COOLING STAGES The Comfort Zone II B system will attempt to minimize use of additional stages of heating or cooling equipment Comfort Zone II B controls multi stage equipment in response to the level of demand and the number of zones with demand In general it tries to satisfy demand with a minimum number of stage...

Страница 8: ...ic heat OFF Special 3 stage electric heat Switch 4 Selects Smart Recovery in both heating and cooling The system starts adjusting temperature 1 1 2 hours earlier than selected recovery time so it will arrive at new temperature at selected time ON Smart recovery OFF Normal recovery Switch 5 Zone system address selection When 2 zoning systems are connected together the second system should be set to...

Страница 9: ...ors At power up the User Interface displays all segments for a few sec This is followed by the selected system type for an additional few sec The system type shows as follows 1 AC 1 Speed Air Conditioner 2 HP 1 Speed Heat Pump 3 A2 2 Speed Air Conditioner 4 H2 2 Speed Heat Pump 5 HS 1 or 2 Speed Heat Pump with 3 Stage Auxiliary Heat 6 dF Dual Fuel with 1 Speed Heat Pump 7 d2 Dual Fuel with 2 Speed...

Страница 10: ...furnace or fan coil contains a variable speed ICM blower set this option ON For normal PSC blowers set to OF off This selection enables the system to use Comfort Heat features avail able only with the ICM blower Factory default is OF off AVAILABLE SELECTIONS Use UP or DOWN buttons to alternate between OF off and ON OPTION 6 COOLING LOCKOUT TEMPERATURE This option allows selection of the outdoor te...

Страница 11: ...5 selections are already made While heat pump is heating the blower speed is reduced by removal of the G signal for outdoor temperatures between 12 and 40 degrees F providing warmer leaving air temperatures For heat pumps with electric aux heat and outdoor temperatures below 12 degrees F any heat call is accompanied by a W1 signal bringing on the first stage of aux heat to again increase leaving a...

Страница 12: ...low temporary operation with a failed or missing sensor until the sensor can be replaced Factory default is OF off AVAILABLE SELECTIONS Use UP or DOWN buttons to alternate between OF off and ON NOTE ON is for temporary use only OPTION 38 SELECT AUTO CHANGEOVER TIME This option selects a 5 to 30 minute time delay between heat and cool while in auto changeover mode System must have no demand in curr...

Страница 13: ... FINAL INSTALLATION SETTINGS Humidification Description If a humidifier is included in the system Comfort Zone II B can directly control it If a conventional humidity control exists it should be removed and the zoning system used in its place Comfort Zone II B provides superior convenience and features When installing a 24 vac humidifier connect it directly to the HUM terminal on the Equipment Con...

Страница 14: ... rises above the dehumidification set point a special dehumidification routine is executed As long as zone temperatures are not more than 3 F below their cooling set points a dehumidify demand will turn on the cooling equipment but will limit its ON time to no more than 10 minutes at a time Finally OUT zones are used to their maximum capability When a zone is set to OUT it can be used to help remo...

Страница 15: ...use the combination of a 2 speed compressor without a variable speed blower generally has poor humidity removal on low speed Dehumidify Output and Equipment Connections When there is a dehumidify demand dehumidify output is activated which means that a 24vac signal is removed from the DHUM output terminal In other words dehumidify output logic is reversed output is turned ON when no dehumidify dem...

Страница 16: ...hese indicate when cooling or heating equipment is actually operating When arrows flash equipment is waiting to come on but is being held off by compressor timeguard cycle timer or because LAT or HPT has exceeded its limits and temporarily turned equipment off When the humidity screen is displayed these same arrows show the state of the humidify and dehumidify outputs Multiple Sensors in a Single ...

Страница 17: ...hat zone is going to be unoccupied press OUT button For more information regarding the Out feature read the follow ing section pertaining to Hold Off Out and All Zone 10 Press SET TIME TEMP button until the COOL icon is flashing Press UP or DOWN button until the desired cooling temperature for that period is displayed You have now programmed the time and desired heating and cooling tem peratures f...

Страница 18: ... occupied When a zone is set to OUT desired temperature will be displayed as dashes when UP and DOWN buttons are pressed VIEWING OUTDOOR TEMPERATURE AND INDOOR HUMIDITY 1 Pressing both UP and DOWN buttons simultaneously will display outdoor temperature if this feature is included and indoor humidity Outdoor temperature will be displayed first for 5 sec followed by humidity for 5 sec Smart Sensor w...

Страница 19: ...zone to occupied When a zone is set to OUT the desired temperature will be displayed as when UP and DOWN buttons are pushed ALL ZONE At the User Interface Pressing ALL ZONE button activates and deactivates ALL ZONE function When ALL ZONE function is active ALL icon is displayed This function allows the entire house to be controlled to the set points and program schedule of a single zone The zone t...

Страница 20: ...de the 32 F to 140 F range See Table 5 to determine the temperature ohm relation ship for a Remote Sensor Do not confuse dashes in the display for a zone that is set to OUT or ALL ZONE Other Helpful Hints Read and understand System Startup and Checkout to review Installer Test Setup Mode and check the equipment operation This is a good place to start in evaluating any problems associated with the ...

Страница 21: ...OT See notes 1 2 3 6 10 11 and 19 HUMIDIFIER 24 VAC Fig 15 1 Stage Furnace with 1 Speed Air Conditioner A98089 C C R Y W G Y N A SINGLE STAGE FURNACE SINGLE SPEED AIR CONDITIONER EQUIPMENT CONTROLLER N A 24 VAC HOT N A N A HUMIDIFY O B RH RC W2 W1 G Y2 Y1 DEF DHUM HUM HUMIDIFIER 24 VAC N A HEAT STAGE 1 FAN N A COOL STAGE 1 See note 19 Fig 18 1 Stage Furnace with 2 Speed Heat Pump Dual Fuel A98092 ...

Страница 22: ...N A COOL STAGE 1 See notes 12 and 19 N A N A HUMIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC Fig 22 2 Stage Furnace with 2 Speed Heat Pump Dual Fuel A98096 W W1 W2 Y Y2 TWO SPEED HEAT PUMP C O R W2 Y2 W3 C R Y1 G O B RH RC DEF W2 W1 G Y2 Y1 HEAT STAGE 4 HEAT STAGE 3 FAN COOL HEAT STAGE 2 COOL HEAT STAGE 1 See notes 1 2 3 4 6 7 8 9 10 11 12 and 19 TWO STAGE FURNACE EQUIPMENT CONTROLLER RVS COOLING DEFROST ...

Страница 23: ...MIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC HUM DHUM PL9 10 O Y1 AIRFLOW SELECT BOARD Fig 26 Variable Speed Non Condensing Furnace with 2 Speed Heat Pump Dual Fuel A98100 C C R Y2 W W1 G W2 Y Y2 O B RH RVS COOLING VSP FURNACE BOARD TWO SPEED HEAT PUMP EQUIPMENT CONTROLLER N A 24 VAC HOT RC W2 W1 G Y2 Y1 HEAT STAGE 3 HEAT STAGE 2 FAN COOL HEAT STAGE 2 COOL HEAT STAGE 1 See notes 1 2 3 4 6 7 8 9 10 11 12 ...

Страница 24: ...tes 12 15 17 and 19 N A DEHUMIDIFY HUMIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC HUM DEHUM Fig 30 Variable Speed 2 Stage Condensing Furnace W O DE Connection with 2 Speed Heat Pump A98104 C C R W2 W W1 G W2 Y Y2 O B RH RVS COOLING VSP SPEED FURNACE TWO SPEED HEAT PUMP EQUIPMENT CONTROLLER N A 24 VAC HOT RC W2 W1 G Y2 Y1 HEAT STAGE 4 HEAT STAGE 3 FAN COOL HEAT STAGE 2 COOL HEAT STAGE 1 See notes 1 2 3 4 ...

Страница 25: ...5 18 and 19 N A DEHUMIDIFY HUMIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC HUM DEHUM DE Fig 34 Variable Speed 2 Stage Condensing Furnace With DE Connection With 2 Speed Heat Pump Dual Fuel A99375 C C R W2 W W1 G W2 Y Y2 O B RH RVS COOLING VSP SPEED FURNACE TWO SPEED HEAT PUMP EQUIPMENT CONTROLLER N A 24 VAC HOT RC W2 W1 G Y2 Y1 HEAT STAGE 4 HEAT STAGE 3 FAN COOL HEAT STAGE 2 COOL HEAT STAGE 1 See notes 1 ...

Страница 26: ...FAN COOL STAGE 1 N A N A HUMIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC See note 13 Fig 38 Typical Fan Coil with 2 Speed Heat Pump A98108 C R W3 C R W3 W2 Y1 W2 G Y E O B RH RVS COOLING TYPICAL FAN COIL TWO SPEED HEAT PUMP 24 VAC HOT RC W2 W1 Y2 G Y1 HEAT STAGE 4 HEAT STAGE 3 FAN COOL HEAT STAGE 1 COOL HEAT STAGE 2 O Y2 EQUIPMENT CONTROLLER DEFROST N A N A HUMIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC See note...

Страница 27: ... N A N A DEHUMIDIFY HUMIDIFY DEF DHUM HUM HUMIDIFIER 24 VAC See notes 13 14 and 15 Fig 42 FK and FV Fan Coil with 2 Speed Heat Pump A99370 C W2 O B RVS COOLING N A R1H FK AND FV SERIES FAN COIL TWO SPEED HEAT PUMP REMOVE J1 JUMPER REMOVE J2 JUMPER FOR HEAT STAGING EQUIPMENT CONTROLLER 24 VAC HOT R1C W2 W1 G Y2 Y1 HEAT STAGE 4 HEAT STAGE 3 FAN HEAT COOL STAGE 2 HEAT COOL STAGE 1 O R Y2 Y1 C R DH W1...

Страница 28: ... indicate variable speed ICM blower motor 16 To activate dehumidify feature on variable speed 80 non condensing furnace disconnect green DHUM wire from G on furnace control board and connect to dehumidify terminal on Equipment Controller 17 To activate dehumidify feature on older style variable speed condensing furnaces i e 58MVP that do not have a DE connection a pilot duty 24vac relay must be us...

Отзывы: